DOI QR코드

DOI QR Code

A Case Study for Energy Consumption Characteristics of High School Facilities in Seoul

서울지역 고등학교 건물의 에너지소비특성에 관한 사례분석

  • Kim, Sung-Bum (Department of Architectural Engineering, Graduate School, Daejeon University) ;
  • Oh, Byung-Chil (School of Design, Space Design Major, Shinhan University) ;
  • Shin, U-Cheul (Department of Architectural Engineering, Daejeon University)
  • 김성범 (대전대학교 대학원 건축공학과) ;
  • 오병칠 (신한대학교 디자인학부 공간디자인전공) ;
  • 신우철 (대전대학교 건축공학과)
  • Received : 2016.10.13
  • Accepted : 2016.12.07
  • Published : 2016.12.30

Abstract

In this study, we analyzed five-year(2011~2015) data for D high school in Seoul area to analyze energy consumption characteristics in high school. The results are summarized as follows. (1) In the result of comparison analysis about 2015 energy consumption by usage, based on primary energy, 18% of energy was consumed in cafeteria, and 82% was consumed in main building. In the case of main building, base and constant load excepting hot water supply in restroom took 40%, heating including freeze protection took 20%, hot water supply in restroom took 14%, and cooling took 8% in order. (2) In the 2015 total energy consumption in D high school based on primary energy, heating energy takes 28%. The range and limit of energy savings coming from the reinforcement of insulation and window performance could be estimated. (3) To introduce new & renewable energy system in high school, electricity-based system is suitable than heat-based system because usage of electric energy is larger than that of heat energy in high school. (4) Five-year energy consumption unit according to heating degree-day showed a linearly increasing trend, and the coefficient of determination(R2) was 0.9763, which means high correlation.

Keywords

References

  1. Ministry of Education, Green School Project Overview, 2009.
  2. Seoul Metropolitan Government, Building Retrofit Project, 2014.
  3. Park, K. H., A Study on Energy Efficiency School Retrofit, Korea Energy Economics Institute, 2014.
  4. Yoon, J. H., Shin, U. C., Cho, J. I., Kim, H. J., and Lee, C. S., A Study on Analysis of Energy Consumption of a High School Facilities in Korea, Journal of the Korean Solar Energy Society, Vol. 30, No. 4, pp. 55-62, 2010.
  5. Kim, K. S., Park, J. W., Yoon, J. H., and Shin, U. C., A Case Study of Characteristics of Energy Consumption of a High School Education Facilities, Journal of the Korean Solar Energy Society, Vol. 31, No. 5, pp. 99-104, 2011.
  6. Lhee, S. C., Choi, Y. J., and Choi, Y., Evaluating Performance of Energy Conservation Measures for Remodeling Educational Facilities - Focused on Deteriorated Middle School Buildings, Journal of the Korea Institute of Ecological Architecture and Environment, Vol. 12, No. 4, pp. 105-110, 2012.

Cited by

  1. 어린이집의 넷 에너지 제로화 구현에 관한 사례분석 vol.35, pp.4, 2016, https://doi.org/10.5659/jaik_sc.2019.35.4.185
  2. 교육시설의 건축물에너지효율등급 사례분석을 통한 에너지자립률 평가 vol.18, pp.4, 2016, https://doi.org/10.7743/kisee.2019.18.4.058
  3. A heuristic solution and multi-objective optimization model for life-cycle cost analysis of solar PV/GSHP system: A case study of campus residential building in Korea vol.47, pp.None, 2016, https://doi.org/10.1016/j.seta.2021.101490