Abstract

It is made compulsory to install SPD for the purpose of protecting electric and electronic devices when an abnormal voltage such as lightning occurs to power line using power frequency of 60Hz. Recently, the high speed communication technology utilizing power line is receiving attention again as a communication technology for smart grid. The SPD influences the performances of power line communication when using SPD and power line communication system together. In order to improve the performance of power line communication, a proposed scheme for series connection of gas discharge tube to ZnO varistor was presented. This paper measured the impacts of series connection of GDT to SPD using ZnO varistor on the limit voltage of Class III SPD. This paper also presented the DC operating voltage of GDT which satisfies the limit voltage of power line communication system and SPD simultaneously.

Keywords

References

  1. J. Zyren, "The HomePlug Green PHY Specification & the In-Home Smart Grid", Proc. of IEEE International Conference on Consumer Electronics, pp 241-242, 2011.
  2. M. Gotz, M. Rapp, and K. Dostert, "Power line channel characteristics and their effect on communication system design," IEEE Commun. Magazine, vol. 42, no. 4, pp. 78-86, Apr. 2004.
  3. Korea Meteorological Administration, "ANNUAL LIGHTNING REPORT 2010", pp 1, 2011.
  4. Jongmin Choi, Taehyun Jeon, "A method gor enhancing data transmission performance in the power-line communication channel with low-voltage surge protective devices", JIEIE.2012.26.2, pp 82-85.
  5. Hee-Ro Kwak, Chung-Yong Ki, "Lightning Protection for Information-oriented and Computerized Society", uijae, pp 105-131, 2000.
  6. Bok-Hee Lee, Ju-Hong Eom, "An Effective Installation Method of Lightning Protective Devices for Information and Communication Facilities", JIEIE, Vol.16, No 5, pp90-96, 2002. https://doi.org/10.5207/JIEIE.2002.16.5.090
  7. Sung-Chul Cho, Ju-Hong Eom and Tae-Hyung Lee, Hoo-Sek Han, "V-I Characteristic of ZnO Varistor and GDT", KIIEE Annual Spring Conference 2006, pp 356-359.