Horizontal Stress Analysis of Electric Pole using Earth Pressure Cell from Mock-Up Tension Test

전주의 실물인장실험시 토압계를 이용한 수평토압분석

  • 안태봉 (우송대학교 철도건설환경공학과)
  • Received : 2010.03.25
  • Accepted : 2010.04.22
  • Published : 2010.08.31

Abstract

Many electric poles in the softground have been collapsed due to external load. In this study, 10 types of tests were performed with variation of location, numbers and depths of anchor blocks as well as depth of poles to find horizontal earth pressure through full scale pull-out tests. The horizontal earth pressure increased with embedded depth of electric pole, and earth pressure of lower passive zone decreased. The deeper of anchor block, earth pressure of passive zone becomes less. 4 anchor blocks decreased earth pressure at G.L.-0.9[m]. It is considered that 4 anchor blocks installed along 80[cm] vertically are main reason. Overall, when more anchor blocks are constructed, excavation area is large, and constructivity such as backfill is bad, therefore one anchor block would be preferred.

연약지반에 시공하는 많은 콘크리트전주가 외부하중으로 전도파괴가 발생하는데 본 연구에서는 실물인장실험을 실시하고 근가위치, 근가깊이, 근가개수, 전주근입깊이를 달리하면서 전주에 작용하는 수평토압을 분석하였다. 실물실험은 10가지 종류로 나누어 실험한 결과 수평토압은 전주 근입깊이가 클수록 커지고 하부수동영역이 길어지는 것으로 나타났다. 근가 설치위치가 깊을수록 하부수동영역 토압이 감소된다. 근가의 수를 4개 설치한 것이 G.L-0.9[m] 위치에서의 토압을 크게 줄였는데 이는 수직으로 80[cm]정도에 걸쳐 설치된 근가의 영향으로 판단되나 전체적으로 볼 때 근가의 수는 큰 차이가 없으며 근가를 다수 설치하면 굴착면적이 커져 되메우기 등 시공성이 떨어지는 단점이 있으므로 근가를 1개만 설치하여도 좋은 것으로 판단된다.

Keywords

References

  1. 손명윤 임종석, 점성토에 설치된 콘크리트 전주지반의 수평방향지지력, 대한토목학회 학술발표회, 2004.
  2. White, D. J., Thompson, M. J., Suleiman,, M..T and Schaefer, V. R.. “Behavior of Slender Piles Subject to Free-Field Lateral Soil Movement”, Journal of Geotechnical and Geoenvironmental Engineering, Vol. 134, No. 4, pp. 428-436, April 2008. https://doi.org/10.1061/(ASCE)1090-0241(2008)134:4(428)
  3. Rajashree, S. S., Sitharam,T. G., “Nonlinear Finite-Element Modeling of Batter Piles under Lateral Load”, Journal of Geotechnical and Geoenvironmental Engineering, Vol. 127, No. 7, pp. 604-612, 2001. https://doi.org/10.1061/(ASCE)1090-0241(2001)127:7(604)
  4. Chen, S. L. and Chen, L. Z. “Note on the Interaction Factor for Two Laterally Loaded Piles”, Journal of Geotechnical and Geoenvironmental Engineering, Vol. 134, No. 11, pp. 1685-1690, 2008. https://doi.org/10.1061/(ASCE)1090-0241(2008)134:11(1685)
  5. 안태봉, 배전용 콘크리트전주 기초지반의 횡방향변위 분석, 한국조명전기설비학회 논문집, Vol. 23, No.5 pp. 42-49, 2009. https://doi.org/10.5207/JIEIE.2009.23.5.042
  6. 안태봉, 연약지반에 시공된 전주의 실물인장실험을 통한 수평변위분석, 한국조명전기설비학회 논문집, Vol. 23, No.12 pp. 115-126, 2009. https://doi.org/10.5207/JIEIE.2009.23.12.115
  7. 한국전력공사, 지반상태별 콘크리트전주 기초의 안전성 확보방안 최종보고서, 2004.