Many electric poles in the softground have been collapsed due to external load. In this study, 10 types of tests were performed with variation of location, numbers and depths of anchor blocks as well as depth of poles to find horizontal earth pressure through full scale pull-out tests. The horizontal earth pressure increased with embedded depth of electric pole, and earth pressure of lower passive zone decreased. The deeper of anchor block, earth pressure of passive zone becomes less. 4 anchor blocks decreased earth pressure at G.L.-0.9[m]. It is considered that 4 anchor blocks installed along 80[cm] vertically are main reason. Overall, when more anchor blocks are constructed, excavation area is large, and constructivity such as backfill is bad, therefore one anchor block would be preferred.
연약지반에 시공하는 많은 콘크리트전주가 외부하중으로 전도파괴가 발생하는데 본 연구에서는 실물인장실험을 실시하고 근가위치, 근가깊이, 근가개수, 전주근입깊이를 달리하면서 전주에 작용하는 수평토압을 분석하였다. 실물실험은 10가지 종류로 나누어 실험한 결과 수평토압은 전주 근입깊이가 클수록 커지고 하부수동영역이 길어지는 것으로 나타났다. 근가 설치위치가 깊을수록 하부수동영역 토압이 감소된다. 근가의 수를 4개 설치한 것이 G.L-0.9[m] 위치에서의 토압을 크게 줄였는데 이는 수직으로 80[cm]정도에 걸쳐 설치된 근가의 영향으로 판단되나 전체적으로 볼 때 근가의 수는 큰 차이가 없으며 근가를 다수 설치하면 굴착면적이 커져 되메우기 등 시공성이 떨어지는 단점이 있으므로 근가를 1개만 설치하여도 좋은 것으로 판단된다.