Abstract
This paper presents a variable gain current control algorithm for the stabilized grid connection between the grid and a doubly fed induction(DFIG) as a wind power generator. The performance of a RSC current controller depends highly on accurate machine parameters, and especially requires a fast and robust response regardless of the disturbances such as voltage sag. However, parameter variations of a DFIG occur at the point of grid connection, which affects the current controller gains based on DFIG parameters after a DFIG is connected to the grid. Thus, performance degrades when actual machine parameters depart from values used in the control system. In the proposed algorithm, current controller gains of the rotor side converter(RSC) are changed after a DFIG is connected to the grid. The simulation results and experimental results for a 750kW are shown to illustrate the feasibility of the proposed algorithm.
본 논문은 이중여자 풍력발전기를 안정적으로 계통에 투입하는 알고리즘을 제안하였다. 발전기가 계통과 연계되는 순간 발전기의 내부 파라미터 값의 변동이 발생하며, 이는 계통 투입 전 발전기 파라미터에 근거한 RSC(Rotor Side Converter)측 전류제어기 이득 값에 영향을 준다. 이러한 영향으로 인하여 계통 투입 시 전류제어가 불안정하게 되거나, 전류제어 응답성이 낮게 된다. 따라서 계통투입 전 발전기 파라미터를 이용한 전류제어기 이득 값은 투입 후 바뀌어야 한다. 특히 회전자 전류제어기 성능은 순간 저전압 발생등 예상하지 않은 외란에 대하여 빠른 응답성을 필요로 한다. 따라서 본 논문에서는 계통투입 전 후의 RSC측 전류제어기의 이득 값을 달리하여 안정적인 계통 투입이 가능하도록 하는 알고리즘을 시뮬레이션과 실험으로 증명하였다.