DOI QR코드

DOI QR Code

Series Gap Type 피뢰기의 뇌임펄스 동작책무 및 온도의존성에 관한 연구

A Study of Lightning Impulse Operating Duty and Temperature Dependence of Series Gap Type Arrester

  • 조한구 (한국전기연구원 나노융합소재연구센터) ;
  • 유대훈 (한국전기연구원 나노융합소재연구센터)
  • 발행 : 2009.08.01

초록

This paper describes lightning impulse operating duty performance and temperature dependence of series gap type for transmission line arresters. The ageing parameters of lightning arresters are impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by lightning impulse current. In the discharge withstand test, total energy applied to the ZnO arrester each time is 4/10 ${\mu}s$, 30 kA. and in the operating duty test, the arrester has passed the test if thermal stability is achieved, if the residual voltage measured before and after the test is not changed by more than 5 %, and after the test reveals no evidence of puncture, flashover or cracking of the ZnO block. As a results, the residual voltage was in the range of 17.2${\sim}$20.3 kV and ZnO block bear up against at 2 shot of series impulse current of 30 kA. Also it was so excellent that the mechanical destruction does not occur at the 2 groups of 5 impulses current of 2/20 ${\mu}s$ 10 kA. According to the tests, it is thought that the ZnO arrester shows good stability with impulse current test. and it was found that the ambient temperature is increased resistive leakage current was increased in the range 47.3${\sim}$167.4 ${\mu}A$.

키워드

참고문헌

  1. L. M. Levinson and H. R. Philipp, 'Zinc oxide varistors-a review', Am. Ceram. Soc. Bull., Vol. 65, p. 639, 1986
  2. T. K. Gupta, 'Application of zinc oxide varistors', J. Am. Ceram. Soc., Vol. 73, p. 1817, 1990 https://doi.org/10.1111/j.1151-2916.1990.tb05232.x
  3. K. Lahti, B. Richter, K. Kannus, and K. Nousiainen, 'Internal Degradation of Polymer Housed Metal Oxide Surge Arresters in Very Humid Ambient Conditions', IEEE High Voltage Engineering Symposium, 1999
  4. K. Lahti, K. Kannus, and K. Nousiainen, 'A comparison between the DC leakage currents of polymer housed metal oxide surge arresters in very humid ambient conditions and in water immersion tests', IEEE Trans. on Power Delivery, Vol. 14, No. 1, p. 163, 1999 https://doi.org/10.1109/61.736709
  5. J. He, S. Chen, R. Zeng, J. Hu, and C. Deng, 'Development and application effect of polymeric surge ZnO arresters for 500 kV compact transmission line', IEEE Transactions on Power Delivery, Vol. 21, No. 1, p. 113, 2006 https://doi.org/10.1109/TPWRD.2005.860234
  6. S. Shirakawa, S. Yamada, S. Tanaka, I. Ejiri, S. Watahiki, and S. Kondo, 'Improved zinc oxide surge arresters using high voltage gradient 300 V/mm, 400 V/mm ZnO elements', IEEE Trans. PWRD, Vol. 15, No. 2, p. 569, 2000 https://doi.org/10.1109/61.852986
  7. J. Kuang, Jeffey A. Bennett, Ram C. Bommakanti, and Steven A. Boggs, 'Temperature Distribution in a ZnO Arrester Subjected to Multiple Current Impulses', Conference Record of the IEEE International Symposium on Electrical Insulation, 1996
  8. IEC 60099-4 'Metal Oxide Surge Arresters Without Gaps for a.c. System', 2001