Study on the Frosting Phenomenon of the Fin and Tube Heat Exchanger with a Louvered Fin

루버형 휜을 가진 휜관형 열교환기의 착상현상 연구

  • Received : 2008.03.17
  • Accepted : 2008.11.21
  • Published : 2008.11.30

Abstract

The present study investigated the pressure drop and the total frost mass of the louvered fin type heat exchanger, which is widely used at the air-conditioning system. The pressure drop due to the frosting phenomenon and the total frost mass were investigated by changing the wet bulb temperature condition of the inlet air. Hence the brain of 55wt% was used as a cooling solution instead of a common refrigerant. The temperature difference between the brine and the tube outside wall at the outlet of heat exchanger was $10^{\circ}C$, at maximum, higher than that at the inlet of heat exchanger. As the wet bulb temperatures were increased, the pressure drop was linearly increased due to the increment of frost mass. And the increment of heat exchange rate was smaller than that of inlet air enthalpy due to the increment of frost mass. The pressure drop of air side was rapidly increased due to the progress of frosting phenomena. The run time that the pressure drop occurred rapidly was decreased by the growth of frost.

Keywords