DOI QR코드

DOI QR Code

Transient Grounding Impedance Behaviors of Deeply-driven Ground Rods According to the Injection Point of Impulse Currents

임펄스전류의 인가위치에 따른 심매실 봉상 접지전극의 과도접지임피던스 특선

  • 이수봉 (인하대학교 대학원 전기공학과) ;
  • 이봉 (인하대학교 대학원 전기공학과) ;
  • 이승주 (인하대학교 대학원 전기공학과) ;
  • 전병욱 (인하대학교 대학원 전기공학과) ;
  • 이복희 (인하대공대 전자전기공학부)
  • Published : 2008.10.31

Abstract

This paper presents the transient and conventional grounding impedance behaviors of deeply-driven ground rods associated with the injection point of impulse currents. The transient grounding impedance strongly depends on the length of deeply-driven ground rod and the rise time and injection point of impulse currents, and the intrinsic inductance of ground rod has a significant affect on the transient grounding impedance of grounding system in fast rise time ranges. The reduction of inductance is decisive to improve the impulse impedance behaviors of deeply-driven ground rods. It is effective that grounding conductor is connected to the top of the ground rod as short as possible.

본 논문은 임펄스전류의 인가위치에 따른 심매설 봉상 접지전극의 과도접지임피던스와 규약접지임피던스 특성에 관하여 기술하였다. 과도접지임피던스는 심매설 접지전극의 길이 및 임펄스전류의 상승시간과 인가위치에 강하게 의존하며, 접지전극의 자체 인덕턴스는 짧은 시간 영역에서 점지시스템의 과도접지임피던스에 크게 영향을 미치는 것으로 나타났다. 심매설 봉상 접지전극의 자체 인덕턴스의 저감은 과도접지임피던스 특성의 개선에 결정적인 역할을 한다. 접지도선의 길이는 최대한 짧게 하여 접지전극의 상단에 접속하는 것이 효과적이다.

Keywords

References

  1. J. H. Bogensperger, J. Frei and S. Pack, "Resistance of Grounding Systems Stationary and Transient Behavior", Proc. 9th international Symposium on High Voltage Engineering, pp.6715-1-4, 1995.9
  2. S. Karaki, et al, "Transient Impedance of GIS Grounding Grid", IEEE Trans., Vol.PD-10, No.2, pp.723-738, 1995
  3. Bok-Hee Lee,Dong-Cheol Jeong, Su-Bong Lee and Keun-Chul Chang, "Effective Impulse Impedances of Deeply Driven Grounding Electrodes", KIEE International Trans on EA, vol. 4-C, no. 5, pp. 207-214, 2004
  4. IEEE Std 81.2-1991, "IEEE Guide for Measurement of Impedance and Safety Characteristics of Large, Extended or Interconnected Grounding Systems", IEEE Inc., pp.1731, 1991
  5. KS C IEC 62305-3, 피뢰시스템-제3부: 구조물의 물리적 손상 및 인명위험, pp.148-159, 2007
  6. KS C IEC 62305-1, 피뢰시스템-제1부: 일반원칙, pp.3-15, 2007
  7. B. R. Gupta and B. Thapar, "Impulse Impedance of Grounding Grids", IEEE Trans. Vol.PAS-99, No.6, pp.214-218, 1980
  8. M. Ramamoorty, M. M. Babu Narayanan, S. Parameswaran and D. Mukhedkar, "Transient Performance of Grounding Grids", IEEE Trans. Vol.PD-4, pp.2053-2058, No.4, 1989
  9. 이복희 外, "조합형 써지전압.전류발생기의 제작과 특성", '96 대한전기학회 하계학술대회 논문지, Vol.C, pp1876-1878, 1996.7

Cited by

  1. Transient Grounding Impedance Characteristics of a Concrete Rod-type Grounding Electrode used for Electric Distribution Systems vol.24, pp.2, 2010, https://doi.org/10.5207/JIEIE.2010.24.2.009
  2. A Fundamental Study on the Impulse Responses of Ground Rod Attendant upon Soil Discharges vol.28, pp.4, 2014, https://doi.org/10.5207/JIEIE.2014.28.4.062
  3. Effects of Soil Discharges on the Impulsive Ground Impedance of Ground Rod with Needles vol.28, pp.5, 2014, https://doi.org/10.5207/JIEIE.2014.28.5.098