DOI QR코드

DOI QR Code

Partial Discharge Characteristics of the XLPE/EPDM Interface in Power Cable Joint

전력케이블 접속재 XLPE/EPDM 계면의 부분방전 특성

  • 조경순 (광운대학교 전자정보공과대학 전기공학과 중전기기 미래기술개발 연구센터) ;
  • 홍진웅 (광운대학교 전자정보공과대학 전기공학과 중전기기 미래기술개발 연구센터)
  • Published : 2007.09.01

Abstract

This paper describes the influence on partial discharge characteristics of defects at the model XLPE/EPDM interfaces of power cable joints. The defects of void and copper which could inadvertently be present at the joint interface. We measured ${\Phi}-n,\;{\Phi}-q$ patterns by a computer-aided partial discharge measuring system. Several parameters i, e, maximum discharge $q_{max}$ [pC], average discharge q [pC/cycle], and average angle of discharge ${\Theta}g$ [deg] were found to depend upon the defect type varying applied voltage. As the result of time evaluation, partial discharges are small different at copper defects, but is decreasing obviously about 20 minutes at void defect. It considered that difference of magnitude of total positive discharge of Q+ [pC] and total negative discharge of Q- [pC] is SPMD(swarming pulsive micro discharges).

Keywords

References

  1. 유근양, '지중 케이블 접속재 시공', 전기설비, 18권, 10호, 통권 제194호, p. 40, 2001
  2. Ehara, Y., Koizumi, N., Kishida, H., and Ito, T., 'Effects of humidity on the degradation of insulating materials exposed to partial discharge', Electrical Insulation and Dielectric Phenomena, IEEE annual Report, p. 538, 1994
  3. Wolter, K. D., Tanaka, J., and Johnson, J. F., 'A study of the gaseous degradation products of corona exposed polyethylene', IEEE Trans. on Electrical Insulation, Vol. 17, No. 3, p. 248, 1982 https://doi.org/10.1109/TEI.1982.298463
  4. Cavallini, A., Montanari, G. C., Contin, A., and Pulletti, F., 'A new approach to the diagnosis of solid insulation systems based on PD signal inference', IEEE Electrical Insulation Magazine, Vol. 19, No. 2, p. 23, 2003
  5. Uchida K., Hirata T., Tanaka I., and Takahashi T., 'Partial discharge and breakdown characteristics of various defects in XLPE cable joint', T. IEE Japan, Vol. 115-B, No. 10, p. 1185, 1995
  6. F. H. Kreuger, 'Partial Discharge Detection in High-Voltage Equipment', Butterworths, p. 52, 1989
  7. Kawakami, H., Kawakubo, N., Ehara, Y., Kishda, H., and Ito, T., 'Influence of swarming pulsive micro discharge on tree degradation', 2002 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, p. 979, 2002
  8. Tokunaga, S., Tsurusaki, T., Arief, Y. Z., Ohtsuka, S., Mizuno, T., and Hikita, M., 'Partial discharge characteristics till, breakdown for XLPE cable joint with an artificial defect', Proceedings 7th International Conference on Applications of Dielectric Materials, p. 1206, 2003
  9. Nadolny, Z., Braun, J. M., and Densley, R. J., 'Effect of Mechanical Pressure and Silicone Grease on Partial Discharge Characteristics for Model XLPE Transmission Cable Joint', IEE High Voltage engineering Symposium, p. 297, 1999
  10. B. Yazici, 'Statistical pattern analysis of partial discharge measurements for quality assessment of insulation systems in high-voltage electrical machinery', IEEE Trans. on. Industry Appl., Vol. 40, No. 2, p. 1579, 2004 https://doi.org/10.1109/TIA.2004.836174