Abstract
Recently, a number of equipments related with electricity, electronics, and communication in the same building are needed to the grounding system for safety from unexpected accidents. When the faulted electric current flows into a certain grounding system, the potential rise in that system takes place and it might induce the potential rise to other grounding system. This potential interference was strongly affected by the surface potential, which was deeply related with the electrode shape. In this paper, the fundamental formula was deduced on the basis of surface potential of two grounding electrodes. Which corresponds to source of the potential interference and other grounding electrode, respectively. Therefore, the degree of potential interference in this mesh grounding electrode system was verified by the simple model simulation. In addition, in order to identify the difference between the grounding resistance in the realistic construction site and the expected value from the corresponding simulation, the experiment was performed with model on a reduced scale about the realistic grounding system. It consists of stainless steel hemisphere electrodes in a water tank. From this work, the grounding resistance in the mesh grounding electrode showed the good coincidence results between those. Consequently, it is confirmed that the grounding resistance in the mesh electrode is possible to be estimated by performing the experiment using the water tank model.
최근들어 빌딩내에 있는 많은 전기 전자 통신설비들은 기기 보호 및 안전을 위하여 반드시 접지를 필요로 하며, 고장 전류가 같은 빌딩내에 있는 어떤 접지 시스템으로 흐를 때, 이 전류에 의한 전위상승에 영향을 받아 다른 접지시스템의 전위 상승을 유도할 수 있다. 이러한 전위간섭은 접지극의 표면전위에 의해 영향을 받으며, 전각의 형상과 깊은 관련이 있다. 본 논문에서의 기본적 공식은 전위간섭을 받는 접지극과 전위간섭의 원천이 되는 두 접지극의 표면 전위에 기초하여 추론되었으며, 다중 접지극에 있어서의 전위간섭의 정도는 미리 간단한 모델을 이용하여 시뮬레이션을 실시하였다. 이는 대지위에 설치되는 건조물의 접지저항을 추정하기 위한 것이며, 실제의 현장에서 측정한 접지 저항값과 추정값과의 일치성을 입증하기 위하여 반구형 수조에서 모의 접지시스템의 축적 모델로 실험을 행한 결과, 확실한 메쉬접지극의 접지저항을 얻을 수 있었다. 따라서 수조 모델 실험을 통하여 메쉬접지각의 접지저항을 추정할 수 있음을 보여주고 있다.