• Title/Summary/Keyword: Potential Rise

Search Result 670, Processing Time 0.02 seconds

Distribution of Potential Rise as a Function of Shape of Grounding Electrodes

  • Gil, Hyoung-Jun;Choi, Chung-Seog;Kim, Hyang-Kon
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.4
    • /
    • pp.73-79
    • /
    • 2007
  • In order to analyze the potential rise of grounding systems installed in buildings, a hemispherical grounding simulation system was studied. Potential rise was measured and analyzed regarding the shape and distance of the grounding electrodes by using this system. The system was composed of a hemispherical water tank, AC power supply, a movable potentiometer, and test grounding electrodes. The potential rise was measured in real time by the horizontal moving probe of be potentiometer. The test grounding electrodes were fabricated through reducing the grounding electrode installed in real buildings such as the ground rod, grounding grid and so on. The potential rise was displayed in a two-dimensional profile and was analyzed regarding the shapes of the ground electrodes. The potential rise of the grounding grid combined with a ground rod was the lowest of every grounding electrode tested. The proposed results can be applicable to evaluating ground potential rise in grounding systems, and the analytical data can be used to stabilize the electrical installations and prevent electrical disasters.

Research on Buried Depth Dependent Characteristics of Potential Rise for Structure (구조물 전위상승의 매설깊이 의존특성에 관한 연구)

  • Gil, Hyoung-Jun;Kim, Hyang-Kon;Kim, Dong-Ook;Choi, Chung-Seog
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.56 no.2
    • /
    • pp.104-108
    • /
    • 2007
  • This paper deals with an approach to the reduction of potential rise according to the buried depth of structure. In order to analyze the surface potential rise of structure, an electrolytic tank which simulates the semi-infinite earth has been used. The potential rise has been measured and analyzed for types of structure using an electrolytic tank experimental apparatus in real time. The structure models were designed through reducing real buildings and fabricated with four types on a scale of one-one hundred sixty. When a test current flowed through structure models, potential gradient was the highest value in case of the outline frame type(structure model A). The distributions of surface potential rise are dependent on the resistivity and absorption percentage in concrete attached to structure model.

A study on Rail Potential Test adaptation for Performance test of DC Railway system (직류 전기철도 성능시험을 위한 레일전위시험 적용연구)

  • Jung, Ho-Sung;Jang, Dong-Uk;Han, Moon-Seob;Park, Hyun-June
    • Proceedings of the KIEE Conference
    • /
    • 2007.10c
    • /
    • pp.238-240
    • /
    • 2007
  • This paper present adaptation method of rail potential test to verify DC railway system's performance and safety. For protection of person and utility caused by rail potential rise, international standard to limit rail potential rise is made and rail potential is tested at the time of plan and construction of DC railway system in foreign country. So, we need rail potential test at the opening time and prepare a continuous monitoring technique of rail potential and a limitation method of rail potential rise. For these, we describe cause of rail potential rise, international standard about rail potential, protection principle, an example of calculation and measurement, and adaptation method for performance test.

  • PDF

A Rise in Electric Potential of Telecommunication Line for Electric Power System by Lightning Surges (뇌서지에 의한 전력통신선로의 전위상승)

  • Lee, Bok-Hee;Chang, Sug-Hun
    • Proceedings of the KIEE Conference
    • /
    • 1997.07e
    • /
    • pp.1718-1720
    • /
    • 1997
  • This paper deals with n rise in electric potential of telecommunication line for electric power system by lightning surges. When $1.2/50{\mu}s$ and $8/20{\mu}s$ impulse voltage and current were applied on telecommunication cable, the voltage waveforms at the end terminal and equipment were measured. The telecommunication lines, which consist of 60 conductors and 3.5km in length, have some surge protectors such as preposition lightning arrester and TVSS. In each case, the rise in electric potential was measured for differential mode and common mode, respectively. Also, the rise in ground potential and the induced voltages were measured and analyzed. As a result, a significant rise in ground potential was observed for lightning surge. It can cause failure or malfunction of telecommunication systems.

  • PDF

Research on Comparison of Individual and Connecting Grounding Electrode for Potential Rise Distribution (개별 접지전극과 연접된 접지전극의 전위상승 분포 비교 연구)

  • Gil, Hyoung-Jun;Choi, Chung-Seog;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.2
    • /
    • pp.57-62
    • /
    • 2008
  • This paper deals with a comparison of individual and connecting grounding electrode for potential rise. When a test current flowed through grounding electrode, potential rise was measured and analyzed for grounding method using a electrolytic tank in real time. In order to analyze the potential rise of grounding systems, a hemispherical water tank experimental apparatus was studied. Potential rise was measured and analyzed regarding the grounding method and distance by using this apparatus. The apparatus was composed of a hemispherical water tank, AC power supply, a movable potentiometer, and test grounding electrodes. The potential rise was measured by the horizontal moving probe of the potentiometer. The grounding electrodes were designed and fabricated with ground rods on a scale of one-eightieth. Potential rises of individual grounding electrode were higher than those of connecting grounding electrode. The distributions of surface potential are dependent on the distance from grounding electrode.

Calculation methods for the rail potential rise and the stray current in the ungrounded DC traction system (비접지 급전시스템에서의 레일전위상승과 누설전류 계산)

  • Chung, Sang-Gi;Park, Hyun-Joon;Kwon, Sam-Young;Bai, Chang-Han
    • Proceedings of the KSR Conference
    • /
    • 2006.11b
    • /
    • pp.631-635
    • /
    • 2006
  • DC traction power system is operated ungrounded to minimize the stray current. This causes rail potential increase and makes hazardous condition to the person in touch with running rails. To prevent the hazardous condition, maximum allowable limits on rail potential rise are set by regulations in advanced foreign countries. In this paper, the simplified calculation methods for the rail potential rise and the stray currents are discussed.

  • PDF

Potential Ruse as a function of the Buried Depth for Structure (구조체의 매설깊이에 따른 전위상승)

  • Gil, Hyoung-Jun;Kim, Dong-Ook;Kim, Dong-Woo;Lee, Ki-Yeon;Kim, Hyang-Kon
    • Proceedings of the KIEE Conference
    • /
    • 2006.07e
    • /
    • pp.27-28
    • /
    • 2006
  • This paper deals with an approach to the reduction of potential rise according to the buried depth of structure. In order to analyze the surface potential rise of structure, an electrolytic tank which simulates the semi-infinite earth has been used. The potential rise has been measured and analyzed for types of structure using an electrolytic tank experimental apparatus in real time. The structure models were designed through reducing real buildings and fabricated with two types on a scale of one-one hundred sixty When a test current flowed through structure models, the potential rise of outline frame type(structure model A) was more high than that of electric cage type(structure model B). The distributions of surface potential rise are dependent on the buried depth of structure model.

  • PDF

Analyses of Earth Surface Potentials Depending on Soil Structures (대지구조에 따른 대지표면전위의 분석)

  • Lee, Bok-Hee;Baek, Young-Hwan;Jung, Hyun-Wook
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.10
    • /
    • pp.1796-1801
    • /
    • 2007
  • This paper presents electric potential rise on the surface of the earth due to ground currents. It is the aim of this paper to propose fundamental data relevant to the earth surface potentials depending on the soil structures. The earth potential rise, touch and step voltages in the immediate vicinity of the ground rod of a distribution pole were measured and analyzed. The results described in this paper are based on laboratory measurements which were intended to simulate conditions existing in actual installations. As a result, the earth surface potential rise, touch and step voltages strongly depend on the soil structure. The highest earth surface potential occurred in the vicinity of the top of ground rod. When the ground rod was installed in the distance range of $1{\sim}1.5\;m$ from distribution pole, the highest touch voltages appeared near the place of 1 m on the straight line connecting the distribution pole to ground rod.

Evaluation of Potential Interferences between Grounding Electrodes using an Electrolytic Tank (수조실험장치를 이용한 접지전극 상호간의 전위간섭 평가)

  • Lee, Bok-Hee;Lee, Su-Bong;Lee, Tae-Hyung;Gil, Hyoung-Jun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.4
    • /
    • pp.29-36
    • /
    • 2006
  • This paper deals with the potential interferences between grounding electrodes in various grounding electrodes. The ground potential rise and potential interference coefficients were measured by using and electrolytic tank and calculated by CDEGS program as functions of the configuration and size of grounding electrodes and the distance between grounding electrodes. The ground potential rise and potential interference coefficient strongly depend on the distance between grounding electrodes, the shape and size of grounding electrodes. The potential rise interferences between grounding grid and grounding grid is lower than those between grounding grid and ground rod.

The Potential Interference of the Grounding Grids (격자형 접지전극의 전위간섭)

  • Lee, Bok-Hee;Lee, Tae-Hyung;Lee, Su-Bong;Jung, Hyun-Uk;Gil, Hyoung-Jun
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.261-263
    • /
    • 2005
  • This paper presents the potential interferences between various grounding electrodes. The ground potential rise and potential interference coefficient between grounding grid and ground rod were calculated. The potential rise and potential interference coefficient strongly depend on the distance between grounding electrodes.

  • PDF