A Study on the Improvement of the Evacuation in Ward of the General Hospital

종합병원 병동부 피난환경 개선에 관한 연구

  • Published : 2006.10.31

Abstract

The purpose of this study is to suggest architectural planning guideline for the improvement of the evacuation environment in a ward. To suggest of guideline, the problem of irrational domestic criteria is searched according to compare National fire code (NFPA101, Life safety code) with Korea building law. This study includes stairs, corridors and exit door etc. but excludes fire facilities. To verify effectiveness of suggested guideline, egress simulation is run that based on databases according to literature survey. The results of this study could be summarized as follow: Suggested guidelines are subdivision(fire partition), evacuation by elevator, secure useful waiting space of elevator hall and smokeproof enclosures, the corridor is divided by fire or smoke barriers corridor from hazardous room, only wheeled items are arranged in corridors of a ward story. The result of computer simulation for suggested guidelines verify that egress time can be decreased 20% or above.

Keywords

References

  1. 김응식 외, 병원 피난에 관한 연구 : Part I, 제19권 제2호, 한국화재소방학회 논문지, 2005
  2. 문창호, 미국 노인복지시설의 건축적 특성과 경향에 대한 연구, 대한건축학회논문집, 18권 5호(통권 163호), 2002
  3. 박두원 외, 고층건물에서의 피난 엘리베이터의 효율성에 관한 연구, 한국화재소방학회 춘계학술논문발표회 논문집, 2006
  4. 이정수 외, 종합병원 병동부의 이용자 피난행태를 고려한 건축계획 및 운영관리 지침에 관한 연구, 대한건축학회논문집, 21권 10호(통권 204 호), 2005
  5. 임지현 외, 사례를 통해 본 병원 건축의 방재계획에 관한 연구, 한국화재소방학회 하계학술논문발표회 논문집, 2004
  6. 한국화재보험협회, 인명안전코드, 제8판, 한컴닷컴, 2001
  7. Peter A. Thompson 외, Testing and application of the computer model 'SIMULEX', Fire Safety Journal (Vol. 24, No. 2), U.K., 1995
  8. NFPA, Life Safety Code Handbook 2000 edition, NFPA, USA, 2000