Study on Heat Transfer Characteristics of Discrete Fin-and-tube Heat Exchangers

독립 핀-튜브 열교환기의 열전달 성능특성에 관한 연구

  • Lee, Ho-Seong (Graduate School of Mechanical Engineering, Korea University) ;
  • Kim, Yong-Han (Samsung Electronics DA R&D Center) ;
  • Choi, Jong-Min (Department of Mechanical Engineering, Hanbat National University) ;
  • Kim, Yong-Chan (Department of Mechanical Engineering, Korea University)
  • Published : 2005.11.25

Abstract

The objective of this study Is to investigate the heat transfer performance of plate discrete fin-and-tube heat exchangers with large fin pitch. In this study, twenty-two heat exchangers were tested with a variation of fin pitch, number of tube row, longitudinal tube pitch and fin alignment. Discrete fin type exchangers improved heat transfer performance more than 10% compared to tile continuous fin type heat exchangers. The air-side heat transfer coefficient decreased with a reduction of the fin pitch and an increase of the number of tube row, The staggered fin alignment improved heat transfer performance more than 6% compared to the inline fin alignment. The effect of longitudinal tube pitch was insignificant on the j-factor and experiments found opposite effects on the j-factor with respect to fin alignment. Heat transfer correlations were developed from the measured data for flat plate discrete fin-and-tube heat exchangers with large fin pitch. The correlations yielded good predictions of the measured data with mean deviations of 1,4% and 0.3% for tire inline and staggered tube alignment, respectively.

Keywords