GISPD Analysis Using UHF Dual-Band Method

UHF이중대역법을 이용한 GISPD분석

  • 김광화 (전력설비진단연구 그룹, 한국전기연구원) ;
  • 이상화 (전력설비진단연구 그룹, 한국전기연구원) ;
  • 최재구 (전력설비진단연구 그룹, 한국전기연구원)
  • Published : 2004.07.14

Abstract

It is widely known that the ultra high frequency (UHF) method that detects the electromagnetic wave of the PD pulses in the gas insulated space is one of the most competitive methods for its high sensitivity. From the above point of view, this paper describes the characteristics of GIS PD signals measured with ultra wide band (UWB) GIS PD detecting system in which PD signals are detected into the dual UHF band. The UWB PD detection system consists of the UWB UHF coupler, the UWB low noise amplifier (LNA) and the oscilloscope. The dual bands for PD signals are 0.5-2GHz(full band) and 1-2GHz(high band). As results, it was found that the partial discharges of each defect have their own characteristic pattern and the ratio of High band to Full band increases with gas pressure.

Keywords