• 제목/요약/키워드: ziegler parameter

검색결과 42건 처리시간 0.026초

PID 제어기의 On-Line 퍼지 자동동조 (On-Line Fuzzy Auto Tuning for PID Controller)

  • 황형수;최정내;이원혁
    • 대한전기학회논문지:시스템및제어부문D
    • /
    • 제49권2호
    • /
    • pp.55-61
    • /
    • 2000
  • In this paper, we proposed a new PID tuning algorithm by the fuzzy set theory to improve the performance of the PID controller. The new tuning algorithm for the PID controller has the initial value of parameter Kc, $\tau$I, $\tau$D by the Ziegler-Nichols formula using the ultimate gain and ultimate period from a relay tuning experiment. We get error and error change of plant output correspond to the initial value and new proportion gain(Kc) and integral time($\tau$I) from fuzzy tunner. This fuzzy tuning algorithm for PID controller considerably reduced overshoot and rise time compare to any other PID controller tuning algorithms. In real parametric uncertainty systems, the PID controller with Fuzzy auto-tuning give appreciable improvement in the performance. The significant properties of this algorithm is shown by simulation In this paper, we proposed a new PID algorithm by the fuzzy set theory to improve the performance of the PID controller.

  • PDF

Automatic PID Controller Parameter Analyzer

  • Pannil, Pittaya;Julsereewong, Prasit;Ukakimaparn, Prapart;Tirasesth, Kitti
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 1999년도 제14차 학술회의논문집
    • /
    • pp.288-291
    • /
    • 1999
  • The PID (Proportional-Integral-Derivative) controller is widely used in the industries for more than fifty years with the well known Ziegler-Nichols tuning method and others varieties. However, most of the PID controller being used in the real practice still require trial and error adjustment for each process after the tuning method is done, which is consuming of time and needs the operator experiences to obtain the best results for the controller parameter. In order to reduce the inconvenience in the controller tuning, this paper presents a design of an automatic PID controller parameter analyzer being used as a support instrument in the industrial process control. This analyzer is designed based on the tuning formula of Dahlin to synthesize the PID controller parameter. Using this analyzer, the time to be spent in the trial and error procedures and its complexity can be neglected. Experimental results using PID controller parameter synthesized from this analyzer to the liquid level control plant model and the fluid flow control plant model show that the responses of the controlled systems can be efficiently controlled without any difficulty in mathemathical computation.

  • PDF

온라인 자기동조 퍼지 PID 제어기 개발 (The development of an on-line self-tuning fuzzy PID controller)

  • 임형순;한진욱;김성중
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 1997년도 한국자동제어학술회의논문집; 한국전력공사 서울연수원; 17-18 Oct. 1997
    • /
    • pp.704-707
    • /
    • 1997
  • In this paper, we present a fuzzy logic based tuner for continuous on-line tuning of PID controllers. The essential idea of the scheme is to parameterize a Ziegler-Nichols-like tuning formula by a singler parameter .alpha., then to use an on line fuzzy logic to self-tune the parameter. The adaptive scaling makes the controller robust against large variations in parametric and dynamics uncertainties in the plant model. New self-tuning controller has the ability to decide when to use PI or PID control by extracting process dynamics from relay experiments. These scheme lead to improved performance of the transient and steady state behavior of the closed loop system, including processes with nonminimum phase processes.

  • PDF

Fuzzy 자동동조에 의한 불확실성 공정의 견실제어 (Robust Control of Uncertainty Systems by Fuzzy Auto-Tuning)

  • 류영국;최정내;김진권;모영승;황형수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 B
    • /
    • pp.504-506
    • /
    • 1999
  • In this paper, we propose a method which control parametric uncertainty systems using PID controller by fuzzy auto tuning. We get the error and the error change rate of plant output correspond to the initial value of parameter using the Ziegler-Nickols tuning and determine the new proportional gain$(K_p)$ and the integral time $(T_i)$ from fuzzy tuner by the error and error change rate of plant output as a membership function of fuzzy theory. The Fuzzy Auto-tuning algorithm for PID controller operate to adapt variable parameter of plant in parametric uncertainty systems. It is shown this method considerably improve the transient response at computer simulation.

  • PDF

전기유압식 모터용 위치제어 시스템의 설계 (Design of a Position Control System for Electro-hydraulic Motors)

  • 박진길;진강규;노영오;한봉주;정주윤;박재식
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제16권3호
    • /
    • pp.30-41
    • /
    • 1992
  • For the state feedback controller which measures only partial state variables, a state observer can be used to give the estimates of unmeasurable states. In this paper, the delayed state feedback method instead of the state observer for desingning a tracking controller of electro-hydraulic control system is presented. The controller design is based on augmenting the original system by one additional integral and proportional element which compensates for the effect of the integral control and on feeding back the measurable state variables and their delayed values. The performance of the proposed position control system is compared with both that of the full state feedback control system and that of the digital PID control system tuned by the Ziegler-Nichols method and by the parameter readjustment through the computer simulation. And then robustness against unmeasurable constant disturbace and parameter variations during operations is also checked.

  • PDF

단순한 자동동조 PID제어기의 설계에 관한 연구 (A Study on the Design of Simple Auto-tunig PID Controller)

  • 설남오;신만식;이창구
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1995년도 하계학술대회 논문집 B
    • /
    • pp.795-797
    • /
    • 1995
  • In this paper, we present a simple auto-tuning PID controller using genetic algorithms. The basic idea of the scheme is to parameterize a Ziegler-Nichols-like tuning formula by a single parameter ${\alpha}$, then to use GA to select optimal tuning parameter. Also, simple rule mechanisms make the controller adapt against large variations in parametric and dynamics uncertainties in the plant. These scheme lead to improved performance of the transient and steady state behavior of the closed loop system, including processes with long delay-time and nonminimum phase systems.

  • PDF

조정파라미터 공간에서의 제어계 동작점과 안정성에 관한 연구 (STUDY ON THE OPERATING CONDITION AND STABILITY OF CONTROL SYSTEM IN THE SPACE OF ADJUSTING PARAMETERS)

  • 최순만
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제24권4호
    • /
    • pp.470-477
    • /
    • 2000
  • The states of control loops in existing actual systems are changed according to time varying conditions of controllest process and other system components. Adjusting control parameters properly at site which is performed generally by Ziegler & Nichols mthod is important for safe and efficient operation, but the method may require much time to adjust and not easy to inexperienced engineers. This study is aimed to propose more handy method to adjust control parameters by plotting operating conditions on the space of adjusting parameters. One loop of model control system without perturbation condition has been adopted and its stability limit was plotted on the coordinates of Gain and Integral time which was acquired after analyzing Nyquist diagrams and time domain responses. The result showed that the sets of adjusting parameters according to critical stability and proper stability could be acquired reasonably through both responses and the curves on parameter space revealed available patterns for the purpose of easy maintenance of control characteristics.

  • PDF

Automatic tune parameter for digital PID controller based on FPGA

  • Tipsuwanporn, V.;Jitnaknan, P.;Gulpanich, S.;Numsomran, A.;Runghimmawan, T.
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 2003년도 ICCAS
    • /
    • pp.1012-1015
    • /
    • 2003
  • Recently technologies have created new principle and theory but the PID control system remains its popularity as the PID controller contains simple structure, including maintenance and parameter adjustment being so simple. The adjust parameter of PID to achieve best response of process which be using time and may be error if user are not expert. Nowadays this problem was solved by develop PID controller which can analysis and auto tune parameter are appropriate with process which used principle of Ziegler ? Nichols but it are expensive and designed for each task. Thus, this paper proposes auto tune PID based on FPGA by use principle of Dahlin which maximum overshoot not over 5 percentages and do not fine tuning again. It have performance in control process are neighboring controller in industrial and simple to use. Especially, It can use various process and low price. The auto tune digital PID processor embedded on chip FPGA XC2S50-5tq-144. The digital PID processor was designed by fundamental PID equation which architectures including multiplier, adder, subtracter and some other logic gate. It was verified by control model of temperature control system.

  • PDF

원자력발전소 PID 공정제어기에 대한 튜닝 최적화 방법 (A Method of Tuning Optimization for PID Controller in Nuclear Power Plants)

  • 성찬호;민문기
    • 한국압력기기공학회 논문집
    • /
    • 제10권1호
    • /
    • pp.1-6
    • /
    • 2014
  • PID(Proportional, Integral, Derivative) controller is one of the most used process controllers in nuclear power plants. The optimized parameter setting of process controller contributes to the stable operation and efficiency in the operating nuclear power plants. PID parameter setting is tuned when new process control system is established or process control system is changed. It is a burdensome work for I&C(Instrument and Control) engineers to tune the PID controller because it requires a lot of experience and knowledge. When the plant is in operation, inadequate PID parameter setting can be the cause of the unstable process of the plant. Therefore the results of PID parameter setting should be compared, simulated, verified and finally optimized. The practical PID tuning methods used in process controller are tuning operation calculation(Ziegler-Nicholes, Minimum TIAE, Lambda, IMC), exclusive tuning program based on computer and Matlab application. This paper introduces the various tuning methods and suggests an optimized PID tuning process in the operating nuclear power plants.

Neural Network Tuning of the 2-DOF PID Controller With a Combined 2-DOF Parameter For a Gas Turbine Generating Plant

  • Kim, Dong-Hwa
    • International Journal of Fuzzy Logic and Intelligent Systems
    • /
    • 제1권1호
    • /
    • pp.95-103
    • /
    • 2001
  • The purpose of Introducing a combined cycle with gas turbine in power plants is to reduce losses of energy, by effectively using exhaust gases from the gas turbine to produce additional electricity or process. The efficiency of a combined power plant with the gas turbine increases, exceeding 50%, while the efficiency of traditional steam turbine plants is approximately 35% to 40%. Up to the present time, the PID controller has been used to operate this system. However, it is very difficult to achieve an optimal PID gain without any experience, since the gain of the PID controller has to be manually tuned by trial and error procedures. This paper focuses on the neural network tuning of the 2-DOF PID controller with a combined 2-DOF parameter (NN-Tuning 2-DOF PID controller), for optimal control of the Gun-san gas turbine generating plant in Seoul, Korea. In order to attain optimal control, transfer function and operating data from start-up, running, and stop procedures of the Gun-san gas turbine have been acquired and a designed controller has been applied to this system. The results of the NN-Tuning 2-DOF PID are compared with the PID controller and the conventional 2-DOF PID controller tuned by the Ziegler-Nichols method through experimentation. The experimental results of the NN-Tuning 2-DOF PID controller represent a more satisfactory response than those of the previously-mentioned two controllers.

  • PDF