• 제목/요약/키워드: thermal degradation diagnosis

검색결과 29건 처리시간 0.027초

열열화된 PVC 케이블의 부분방전 진단 (Partial Discharge Diagnosis of Thermal Degradated PVC Cable)

  • 송기태;이성일
    • 한국전기전자재료학회논문지
    • /
    • 제24권3호
    • /
    • pp.208-214
    • /
    • 2011
  • In this thesis, the partial discharge according to applied voltage and variations of cross-sectional area and length of the conductor related to general condition for using cable was measured in order to study degradation diagnosis for 2-Core cable of the PVC insulator used in industrial fields for other safety installations. Also the thermal degradation conditions under various installation circumstances of cables were studied by assuming degradation conditions with each different degradation rate (50%, 67%, 100%) such as variation in degradated temperature, thermal exposure time, normal state, partially degradated state and overall degradated state for thermal degradation diagnosis. The quantity of electric discharge (V-Q) according to applied voltage was measured for measurement of inception voltage and extinction voltage. The quantity of electric discharge and the number of electric discharge (Q-N) were measured with applied voltage kept constantly. In addition, pictures were taken using SEM (scanning electron microscope) to compare the surface of external insulator to degradated state of internal insulator according to thermal degradation temperature and also compare the surface of external insulator to degradated surface state of internal insulator according exposure time of cables to thermal stress.

배전 선로의 열화 진단을 위한 복합 카메라 보정기법 (A Composite Camera Calibration Technique for Thermal Deterioration Diagnosis of Power Distribution Line)

  • 정하형;박진하;유준
    • 제어로봇시스템학회논문지
    • /
    • 제22권6호
    • /
    • pp.463-469
    • /
    • 2016
  • This paper presents a composite camera calibration method to determine thermal degradation of power distribution equipment by combining an infrared (IR) camera and a color camera. A calibration jig was first constructed to match the properties of the two cameras. Our calibration and visualization techniques allow for the display of two images, one from the color camera and the other from the IR camera with different field of views (FOVs), on the screen at the same time. To confirm its validity, several case studies have been developed to analyze thermal deterioration limits of indoor and outdoor power distribution facilities.

철도차량 견인전동기의 가속열화수명평가 기술현황 (A technology State of Accelerating Degradation and Life Estimation on the Traction Motor for Railway Rolling Stock)

  • 왕종배;김기준;최영찬
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 제2회 학술대회 논문집 일렉트렛트 및 응용기술전문연구회
    • /
    • pp.25-28
    • /
    • 2000
  • In this paper, the technology for accelerating degradation & life estimation on the traction motor was introduced with the stator form-winding sample coils of the 200 Class insulation system The accelerative degradation was performed in 10 cycles, which were composed of thermal stress, fast rising surge voltage, vibration, water immersion and overvoltage applying. After aging of 10 cycles, condition diagnosis test such as insulation resistance & polarization index, capacitance & dielectric loss and partial discharge properties were investigated in the temperature range of $20{\sim}160^{\circ}C$. Relationship between degradation conditions and diagnosis results were analyzed to find an dominative degradation factor at the end-life point

  • PDF

전기철도용 견인전동기의 복합가속열화 상태진단에 관한 연구 (A Study on the Complex Accelerating Degradation and Condition Diagnosis of Traction Motor for Electric Railway)

  • 왕종배
    • 한국전기전자재료학회논문지
    • /
    • 제15권1호
    • /
    • pp.93-101
    • /
    • 2002
  • In this study, the stator form-winding sample coils based on silicone resin and polyimide were made for fault prediction and reliability estimation on the C-Class(200$\^{C}$ ) insulation system of traction motors. The complex accelerative degradation was periodically performed during 10 cycles, which was composed of thermal stress, fast rising surge voltage, vibration, water immersion and overvoltage applying. After aging of 10 cycles, the condition diagnosis test such as insulation resistance '||'&'||' polarization index, capacitance '||'&'||' dielectric loss and partial discharge properties were investigated in the temperature range of 20 ∼ 160$\^{C}$. Relationship among condition diagnosis tests was analyzed to find a dominative degradation factor and an insulation state at end-life point.

견인전동기의 복합가속열화 상태진단에 의한 고장예측 및 신뢰성 평가 (Fault Prediction & Reliability Estimation of the Traction Motor by the Complex Accelerating Degradation and Condition Diagnosis)

  • 왕종배;김명룡
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 하계학술대회 논문집
    • /
    • pp.763-766
    • /
    • 2000
  • In this paper, stator form-winding sample coils based on silicone resin and polyimide were made for fault prediction and reliability estimation on the 200 Class insulation system of traction motors. The complex accelerative degradation was performed by periods during 10 cycles, which was composed of thermal stress, fast rising surge voltage, vibration, water immersion and overvoltage applying. After aging of 10 cycles, condition diagnosis test such as insulation resistance & polarization index, capacitance & dielectric loss and partial discharge properties were investigated in the temperature range of 20∼160$^{\circ}C$. Relationship among condition diagnosis test was analyzed to find an dominative degradation factor and an insulation state at end-life point.

  • PDF

적외선방사카메라를 이용한 변압기 온도분포 모니터링 (Temperature Distribution Monitoring of Transformer Using IRR-Camera)

  • 이우선;정찬문;서용진
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 하계학술대회 논문집
    • /
    • pp.459-462
    • /
    • 2002
  • The conventional thermal insulator and power transformer testing is widely used in surface aging measurement of outside insulator because those testing can carry out very short time in Lab testing. Also thermal testing is able to offer the standard judgement of relative degradation level of outside HV machine. There it is very useful method compare to previous conventional thermal testing method and effective Lab testing method. But surface discharges(SD) have very complex characteristics of discharge pattern so it is required estimation research to development of precise analysis method. In recent, the study of IRR-camera is carrying out discover of temperature of power equipment through condition diagnosis and system development of degradation diagnosis. In this study, thermal testing of Power transformer is measured with partial temperature distribution in real time.

  • PDF

변압기 온도 변화특성 모니터링 (Temperature Distribution Monitoring of Transformer)

  • 이우선;정찬문;손동민;서용진;임장섭
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 제4회 영호남학술대회 논문집
    • /
    • pp.69-72
    • /
    • 2002
  • The conventional thermal insulator and power transformer testing is widely used in surface aging measurement of outside insulator because those testing can carry out very short time in Lab testing. Also thermal testing is able to offer the standard judgement of relative degradation level of outside HV machine. There it is very useful method compare to previous conventional thermal testing method and effective Lab testing method. But surface discharges(SD) have very complex characteristics of discharge pattern so it is required estimation research to development of precise analysis method. In recent, the study of IRR-camera is carrying out discover of temperature of power equipment through condition diagnosis and system development of degradation diagnosis. In this study, thermal testing of power transformer is measured with partial temperature distribution in real time.

  • PDF

열화상 카메라용 반사경 설계 (Design of a Reflector for Infrared Camera)

  • 배영철
    • 한국전자통신학회논문지
    • /
    • 제9권1호
    • /
    • pp.97-104
    • /
    • 2014
  • 최근에 열화상 카메라(적외선 카메라)는 수 변전 설비의 열화 상태를 진단하는데 많이 사용하고 있다. 그러나 자장이 높은 곳에서는 열화상 카메라의 전자부가 높은 자장으로 인하여 제대로 동작하지 못하는 문제점이 발생한다. 본 논문에서는 수 변전 설비 중 열화상 카메라의 동작에 영향을 주는 높은 자장을 발생시키는 정류기를 포함한 설비에서 적외선 카메라의 손상이 없이 열화진단을 수행할 수 있도록 반사경 설계 기법을 제안한다.

APPLICATION OF MONITORING, DIAGNOSIS, AND PROGNOSIS IN THERMAL PERFORMANCE ANALYSIS FOR NUCLEAR POWER PLANTS

  • Kim, Hyeonmin;Na, Man Gyun;Heo, Gyunyoung
    • Nuclear Engineering and Technology
    • /
    • 제46권6호
    • /
    • pp.737-752
    • /
    • 2014
  • As condition-based maintenance (CBM) has risen as a new trend, there has been an active movement to apply information technology for effective implementation of CBM in power plants. This motivation is widespread in operations and maintenance, including monitoring, diagnosis, prognosis, and decision-making on asset management. Thermal efficiency analysis in nuclear power plants (NPPs) is a longstanding concern being updated with new methodologies in an advanced IT environment. It is also a prominent way to differentiate competitiveness in terms of operations and maintenance costs. Although thermal performance tests implemented using industrial codes and standards can provide officially trustworthy results, they are essentially resource-consuming and maybe even a hind-sighted technique rather than a foresighted one, considering their periodicity. Therefore, if more accurate performance monitoring can be achieved using advanced data analysis techniques, we can expect more optimized operations and maintenance. This paper proposes a framework and describes associated methodologies for in-situ thermal performance analysis, which differs from conventional performance monitoring. The methodologies are effective for monitoring, diagnosis, and prognosis in pursuit of CBM. Our enabling techniques cover the intelligent removal of random and systematic errors, deviation detection between a best condition and a currently measured condition, degradation diagnosis using a structured knowledge base, and prognosis for decision-making about maintenance tasks. We also discuss how our new methods can be incorporated with existing performance tests. We provide guidance and directions for developers and end-users interested in in-situ thermal performance management, particularly in NPPs with large steam turbines.

철도차량 견인전동기의 상태진단 및 상시감시 기술 (Condition Diagnosis & On-line Monitoring Technology on the Traction Motor for Railway Rolling Stock)

  • 왕종배;변윤섭;백종현
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 제2회 학술대회 논문집 일렉트렛트 및 응용기술전문연구회
    • /
    • pp.36-39
    • /
    • 2000
  • This paper presents the technology of condition diagnosis & life estimation on insulation system of the traction motor. In the non-destructive methods for diagnosis of coil insulation state, residual dielectric strength is estimated by the D-map which consist of the partial discharge quantity Q and average degradation degree $\Delta$. In the operating history of machine, the N-Y life estimation method is based on the stop-starting numbers and operating times with considering each degradation factor by the thermal, electrical and heat-cycle stress. With the on-line conditioning monitoring on the currents of traction motors, detecting the abnormal operating state due to bearing faults, stator or armature faults, eccentricity related faults and broken rotor bars can be performed.

  • PDF