• 제목/요약/키워드: surge current test

검색결과 99건 처리시간 0.027초

피뢰기용 단로기의 특성 및 성능 평가 (Properties & Performance Evaluation of Disconnector for Surge Arrester)

  • 김석수;최익순;정낙헌;박태곤
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2005년도 하계학술대회 논문집 Vol.6
    • /
    • pp.546-547
    • /
    • 2005
  • This study aims to evaluate the properties and the performance of the newly designed disconnector for surge arrester. This disconnector was verified with the performance in long-duration current impulse test and high current impulse test. And time-current characteristic test was done at 20A, 200A and 800A(3points) for simulating the internal fault condition of the arrester. The results of this test was very good. Consequently, the newly designed disconnector was, evaluated that it is possible to be used for surge arrester in distribution line system.

  • PDF

임펄스전류에 의한 배전용 ZnO 피뢰기 소자의 열화특성 (Deterioration Characteristics of ZnO Surge Arrester Blocks for Power Distribution Systems Due to Impulse Currents)

  • 이복희;조성철;양순만
    • 조명전기설비학회논문지
    • /
    • 제27권3호
    • /
    • pp.79-86
    • /
    • 2013
  • In order to analyze the electrical performance of ZnO surge arresters stressed by the combined DC and AC voltages that are generated in DC/AC converter systems, the leakage current properties of ZnO surge arrester blocks deteriorated by impulse currents were investigated. The test specimens were deteriorated by the 8/$20{\mu}s$ impulse current of 2.5kA and the leakage currents flowing into the deteriorated zinc oxide(ZnO) arrester blocks subjected to the combined DC and power frequency AC voltages are measured. As a result, the leakage currents flowing through deteriorated ZnO surge arrester blocks were higher than those flowing through the fine ZnO surge arrester blocks and the larger the injection number of 8/$20{\mu}s$ impulse current of 2.5kA is, the greater the leakage current is. The leakage current-voltage curves(I-V curves) of the fine and deteriorated ZnO surge arrester blocks stressed by the combined DC and AC voltages show significant difference in the low conduction region. Also the cross-over phenomenon is observed at the voltage close to the knee of conduction on plots of I-V curves.

배전급 피뢰기(18kV, 5kA)용 산화아연바리스타의 성능향상에 관한 연구 (A Study on the Improvement of ZnO Varistor for Distribution Class Surge Arrester(18kV, 5kA))

  • 유덕선;윤한수;김석수;최연규;장성도
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 하계학술대회 논문집 Vol.4 No.2
    • /
    • pp.744-746
    • /
    • 2003
  • A ZnO varistor with reference voltage 250V/mm was fabricated through the control of particle size in slurry and the variation of sintering conditions. It was found that to measure the flatness of the V-I characteristic curve in the small-current region and the flatness of the V-I characteristic curve in a large-current region was improved nonlinearity of the fabricated ZnO varistor. According to the IEC 60099-4 was measured the accelerated aging test and high current test of the distribution class surge varistor which is excellent in respect to the property of ZnO varistor.

  • PDF

폴리머 피뢰기의 구조에 따른 온도와 누설전류 특성 (Temperature and Leakage Current Characteristics of Polymeric Surge Arrester with Housing)

  • 조한구;유대훈;이운용;김하나
    • 한국전기전자재료학회논문지
    • /
    • 제20권3호
    • /
    • pp.273-280
    • /
    • 2007
  • In this paper, the ZnO surge arrester performance of power distribution class has been studied under different manufacturing conditions such as housing materials(polymeric, porcelain), interface sealants and one-body molding type. In the recent years, the polymeric ZnO surge arresters have been developed and put into operations based on their excellent characteristics. For polymeric surge arresters, the inner gas volume is extremely small, especially in solid insulation polymeric arresters there are not any gas volume inside arresters in the structure due to polymeric materials are filled into the internal gas volume. The sealing integrity is related to safe operation of surge arrester, the prime failure reason of porcelain housed arresters is moisture ingress. In this paper, the sealing integrity of polymeric surge arresters is investigated with moisture multi-aging test and ingress test. The evaluation techniques are used to inspect the sealing integrity of polymeric arresters, including leakage current, surface temperature, reference voltage and dissipation factor.

직류+60[Hz] 교류 중첩전압에 대한 ZnO 피뢰기 소자의 전기적 특성 (Electrical Characteristics of ZnO Surge Arrester Elements Subjected to the Mixed DC and 60[Hz] AC Voltages)

  • 이복희;양순만
    • 조명전기설비학회논문지
    • /
    • 제26권4호
    • /
    • pp.41-47
    • /
    • 2012
  • This paper deals with the electrical characteristics related to power loss, equivalent resistance, and leakage currents flowing through new and deteriorated zinc oxide(ZnO) arrester elements subjected to the mixed DC and 60[Hz] AC voltages. The test specimens were deteriorated by 8/20[${\mu}s$] impulse current of 2.5[kA]. The leakage current-applied voltage($I-V$) characteristic curves of ZnO surge arrester elements were measured as a parameter of the ratio of the peak of 60[Hz] AC voltage to the peak of total voltage. As a consequence of test results, in case of the same applied voltage, the leakage currents flowing through the deteriorated ZnO arrester elements were higher than those flowing through the new ZnO surge arrester elements. The cross-over phenomenon in $I-V$ curves of ZnO surge arrester elements measured as a parameter of the mixed ratio of DC and AC voltages was observed at the low current domain. The effect of DC voltage on the leakage current flowing through ZnO surge arrester elements is pronounced at the same magnitude of test voltages. In addition, the larger the applied number of 8/20[${\mu}s$] impulse current of 2.5[kA] is, the greater the power loss is, in particular, the more severe the power loss increases at higher applied voltages.

Arrester용 Surge counter의 동작특성 (Operating characteristic of surge counter)

  • 김석수;최익순;변진호;이강섭;박태곤
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 춘계학술대회 논문집 방전 플라즈마 유기절연재료 초전도 자성체연구회
    • /
    • pp.30-33
    • /
    • 2004
  • A surge counter is installed under surge arrester, which is protecting the power system apparatuses against abnormal voltage and surges originated in power system line. A surge counter is the device of knowing the times of surge flowed in. There are two methods to get the electric power for mechanical movement and detect the surge. One is using ZnO varistor resister and the other is using the current transformer. In this paper, the characteristics of these methods are presented with using the test and evaluation of them. The process of evaluating the characteristics is essential to develop the domestic surge counter.

  • PDF

직류 전차 탑재형 피뢰기의 하우징 설계 및 성능평가 (Performance Evaluation and Housing Design for Direct Current Surge Arrester in Railway Rolling Stock)

  • 조한구;김석수;한세원;이운용
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 하계학술대회 논문집
    • /
    • pp.128-131
    • /
    • 2000
  • The main objective of this paper is to design and test a new type of polymer ZnO surge arrester for DC power system of railroad vehicles. The rated voltage is 1500V direct current. The main research works are focused on structure design by finite element method, rating voltage, temporary over voltage and studies of characteristics of polymeric surge arrester.

  • PDF

뇌임펄스전류에 의한 ZnO 피뢰기의 열화특성 (Degradation Properties of ZnO Surge Arresters Due to Lightning Impulse Currents)

  • 이수봉;이복희
    • 조명전기설비학회논문지
    • /
    • 제23권4호
    • /
    • pp.79-85
    • /
    • 2009
  • 이 논문은 피임펄스전류의 입사에 따른 ZnO 피뢰기의 열화 특성에 대하여 기술하였다. 뇌서지에 의한 ZnO 피뢰기의 열화특성을 분석하기 위해 시료 ZnO 피뢰기에 8/20[${\mu}s$], 2.5[kA]의 표준뇌임펄스전류를 인가하였다. 뇌임펄스전류를 인가한 것과 인가하지 않은 ZnO 피뢰기에 흐르는 상용주파수 AC 및 DC 누설전류를 측정하였다. 그 결과 임펄스전류의 인가횟수가 증가함에 따라 누설전류는 증가하였고 AC전압에서 누설전류의 비 대칭성은 뚜렷하게 나타났다. 뇌임펄스전류를 인가하지 않은 ZnO 피뢰기의 ZnO 입자는 균일한데 반해 뇌임펄스전류를 인가한 ZnO 피뢰기의 ZnO 입자는 불균일하게 변형되었다. 또한 뇌임펄스전류 인가에 따른 $Bi_2O_3$의 감소가 입계층의 결핍을 발생시키며 입계층의 결핍에 의한 전류의 집중이 ZnO 피뢰기 소자의 비선형 특성의 열화에 대한 중요한 요인으로 작용한 것으로 밝혀졌다.

Failure Prediction of Metal Oxide Varistor Using Nonlinear Surge Look-up Table Based on Experimental Data

  • Kim, Young Sun
    • Transactions on Electrical and Electronic Materials
    • /
    • 제16권6호
    • /
    • pp.317-322
    • /
    • 2015
  • The metal oxide varistor (MOV) is a major component of the surge protection devices (SPDs) currently in use. The device is judged to be faulty when fatigue caused by the continuous inflow of lightning accumulates and reaches the damage limit. In many cases, induced lightning resulting from lightning strikes flows in to the device several times per second in succession. Therefore, the frequency or the rate at which the SPD is actually exposed to stress, called a surge, is outside the range of human perception. For this reason, the protective device should be replaced if it actually approaches the end of its life even though it is not faulty at present, currently no basis exists for making the judgment of remaining lifetime. Up to now, the life of an MOV has been predicted solely based on the number of inflow surges, irrespective of the magnitude of the surge current or the amount of energy that has flowed through the device. In this study, nonlinear data that shows the damage to an MOV depending on the count of surge and the amount of input current were collected through a high-voltage test. Then, a failure prediction algorithm was proposed by preparing a look-up table using the results of the test. The proposed method was experimentally verified using an impulse surge generator

송전급 피뢰기의 구조와 성능평가 (Contruction and Performance Evaluation of the Surge Arrester for Transmission Class)

  • 김석수;최익순;조한구
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 하계학술대회 논문집 Vol.3 No.2
    • /
    • pp.890-893
    • /
    • 2002
  • Since 1970s, varistors using metal-oxide resistors have been applied to Gapless surge arresters for power system. In the paper, the structure of metal-oxide surge arresters without gaps for 362kV GIS which is developed the first in korea has been introduced. And the main evaluation items for the metal-oxide resistors which are reference voltage test, residual voltage test, long duration current impulse withstand test and operating duty test is tested and evaluated.

  • PDF