• Title/Summary/Keyword: superheat

Search Result 198, Processing Time 0.021 seconds

Performance of Alternative Refrigerants in Low Temperature Chillers

  • Jung, Dong-Soo;Kim, Chong-Bo
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.6
    • /
    • pp.67-79
    • /
    • 1998
  • This paper is about the performance of alternative refrigerants for low temperature and transport refrigeration chillers. A breadboard refrigeration chiller was constructed with counterflow heat exchangers. R502, its transitional alternatives of R402A and R402B, and long-term alternatives of R404A and R507 were tested in an attempt to compare the performance of each refrigerant against R502. Measurements were conducted at two condensing temperatures of 43.3$^{\circ}C$ and 52.$0^{\circ}C$ and the evaporating temperature was varied over a range from -$25^{\circ}C$ to -5$^{\circ}C$. The evaporator superheat and condenser subcooling were maintained constant at about 5$^{\circ}C$ for all tests. Test results showed that all alternative fluids tested in this work can be used as 'drop-in fluids' to replace R502 without any major problem. It is also found that in the long run HFC alternatives are to be used due to their favorable environmental characteristics and better performance.

  • PDF

Fuzzy Control Algorithms for the Compressor and the Electronic Expansion Valve of a Multi-type Air-conditioning System using Multiple Input Variables (다입력변수를 사용한 멀티형 공조시스템 압축기와 전자팽창밸브의 퍼지 제어 알고리즘)

  • Han, Do-Young;Park, Kwan-Jun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.2
    • /
    • pp.163-171
    • /
    • 2006
  • In order to control multi-zone temperatures, a multi-type air-conditioning system may be used. In this study, control algorithms for the compressor and the electronic expansion valve of a multi-type air-conditioning system were developed by using fuzzy logics. The compressor control algorithm was composed of a compressor pressure setpoint algorithm, a compressor pressure setpoint reset algorithm, and a compressor frequency setpoint algorithm. The electronic expansion valve control algorithm was composed of an indoor temperature control algorithm, and a superheat control algorithm. These algorithms were applied to a multi-type air-conditioning system. Test showed good results for the control of a multi-type air-conditioning system.

Experimental Study for Investigating the Optimum Operating Conditions of a Seawater Ice Machine (해수제빙장치의 최적 운전 조건 탐색을 위한 실험적 연구)

  • Li, H.;Joo, W.J.;Jeong, S.K.
    • Journal of Power System Engineering
    • /
    • v.14 no.5
    • /
    • pp.76-82
    • /
    • 2010
  • This paper investigates the optimum operating conditions to construct total automatic control system with high energy efficiency of a newly developed seawater ice machine. The machine has an electronic expansion valve(EEV) and a variable speed rotating drum with an evaporator installed inside. The coefficient of performance(COP) was used as an index to evaluate energy efficiency of the machine. At first, the opening angle of EEV was adjusted to obtain COP of the machine at a constant speed of the drum. Then, we checked seawater ice product versus opening angles of the EEV. Finally, effect of drum's rotating speed in response to product of seawater ice and seawater ice temperature were considered.

A Study on Quantitative Performance Index for Phase-Change Cooling Systems (상변화 냉각시스템의 정량적 성능지수 연구)

  • Jang, Myeong-Eon;Song, Hye-Eun
    • Journal of the Korea Institute of Military Science and Technology
    • /
    • v.23 no.3
    • /
    • pp.237-245
    • /
    • 2020
  • In this paper, I introduce Phase-Change Cooling for thermal management of high power devices that can be applied to High Power Laser and Electric Propulsion Systems which are composed of multiple distributed superheat sources. Phase-Change Cooling can be good used to efficient cooling of their heat sources. Phase-Change Cooling has extremely high efficiency of two-phase heat transport by utilizing heat of vaporization, relatively low flow rates and reduced pumps power. And I suggest TPI(Thermal Performance Index) which is a quantitative performance index of Phase-Change Cooling for thermal management. I quantify the performance of Phase-Change Cooling by introducing TPI. I present the test results of TPI's changing refrigerant, heat sink and flow rate of the Phase-Change Cooling system through the experiments and analyze these results.

Spray Characteristics of Superheated Swirl Spray Vertically Introduced into Convective Cross-flow (대류유동으로 수직 분사된 과열 와류분무의 분무특성)

  • Lee, Hae-Cheon;Yoon, Woong-Sup
    • Proceedings of the Korean Society of Propulsion Engineers Conference
    • /
    • 2010.11a
    • /
    • pp.395-398
    • /
    • 2010
  • 감압비등에 의한 미립화는 더 미세한 직경의 액적을 얻을 수 있고, 분무각이 증가하며, 더 좋은 혼합특성을 갖는 다는 점에서 단순 압력식 미립화와 차이가 난다. 감압비등이란 과열된 액체를 포화 압력 이하의 대기 중으로 분사하여 급격한 비등에 의해 이루어지는 미립화이다. 본 연구는 금속 연료를 이용한 추진기관의 산화제인 물 공급기술에 감압비등과정을 이용한 와류분무를 적용시키기 위해 수행됐다. 분열길이와 같은 거시적 특성은 Charge-Couple Device(CCD) 카메라를 이용해 측정하였고, Sauter Mean Diameter(SMD)와 SMD분포와 같은 미시적 특성은 Global Sizing Velocimetry(GSV) 시스템을 이용해 측정했다. 실험은 압력과 온도, 대류 속도를 변화시키며 진행했다.

  • PDF

Effects of Tube Diameter on Nucleate Pool Boiling Heat Transfer (튜브 직경이 풀핵비등 열전달에 미치는 영향)

  • Kang, Myeong-Gie
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.24 no.7
    • /
    • pp.930-937
    • /
    • 2000
  • A series of data sets for the heat transfer coefficient versus wall superheat has been obtained experimentally using various combinations of tube diameters ($9.7{\sim}25.5mm$), surface roughness ($15.1{\sim}60.9nm$), and tube orientations (horizontal and vertical) to obtain effects of tube diameters on nucleate pool boiling heat transfer for the saturated water at atmospheric pressure. In addition, the results are compared with the well known Cornwell and Houston's correlation for horizontal tubes to identify the deviation of the present experimental data from the correlation and the applicability of it to vertical tubes. The experimental results show that the heat transfer coefficient decreases as the tube diameter increases for both horizontal and vertical tubes and they are in good agreement with the Cornwell and Houston's correlation within ${\pm}20%$ scatter range.

Bubble Nucleation and Behavior on Square Micro Heaters (사각 마이크로 히터위에서의 기포의 형성 및 거동)

  • Jung, Jung-Yeul;Kwak, Ho-Young
    • Proceedings of the KSME Conference
    • /
    • 2004.04a
    • /
    • pp.1464-1469
    • /
    • 2004
  • In this study, micro square heaters having dimensions of $65{\times}65{\mu}m^2$and $100{\times}100{\mu}m^2$ were fabricated and bubble nucleation experiments on the heaters were performed. Bubble nucleation temperature was also measured using a bridge circuit and the photographs of bubble nucleation and subsequent growth were taken by a camera with a flash unit. Measured bubble nucleation temperatures were found to be closer to the superheat limit of working fluid (FC-72). Also quasi-1D analyses for the square heaters were performed. The quasi-1D analysis yielded proper temperature distribution of the square heater at steady state, however failed to predict the temperature rise up to the steady state. Similar time dependent temperature can be obtained with proper value of thermal diffusivity. For the $100{\times}100{\mu}m^2$ square heater, nucleation of several bubbles was observed while only one bubble was observed to be nucleated on $65{\times}65{\mu}m^2$ heater.

  • PDF

Effects of Tube Inclination on Saturated Nucleate Pool Boiling Heat Transfer (튜브 경사각이 포화풀핵비등 열전달에 미치는 영향)

  • Kang, Myeong-Gie
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.32 no.5
    • /
    • pp.327-334
    • /
    • 2008
  • Effects of tube inclination on pool boiling heat transfer have been studied for the saturated water at atmospheric pressure. For the analysis, seven inclination angles varying from the horizontal to the vertical and two tube diameters(25.4 and 30.0 mm) are tested. According to the results, inclination angles result in much change on heat transfer. For the same wall superheat(about $5.3^{\circ}C$) the ratio between two heat fluxes for the $45^{\circ}$ inclined and the vertical has the value of more than five when the tube diameter is 25.4mm. As the inclination angle is increasing from the horizontal to the vertical direction heat transfer is gradually increasing because of the increase in liquid agitation. However the detailed tendency depends on the ratio between the tube length and the diameter.

Experimental Study on the freezing of Aqueous Binary Solution Saturated Packed bed in a Square Cavity (다공성 물질이 충전된 정방형 밀폐용기 내에서 수용성 혼합용액의 동결거동에 관한 실험적 연구)

  • Choi, J.Y.;Kim, B.C.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.4 no.3
    • /
    • pp.175-182
    • /
    • 1992
  • Freezing of the binary solution ($H_2O-NaCl$) saturating a packed bed of spheres is investigated experimentally. The system is cooled through its top surface, and the bottom is maintained at a temperature above the liquidus. Experiments are performed on the hypolutectic side, and the cold wall temperature is lower than the eutectic point. The effects of initial mixture concentration, superheat and glass bead diameter on temperature and concentration distributions are investigated. Supercooling was observed only at early times of the freezing process for experiments with 5% initial salt concentration. Flow visualization experiments and mushy-liquid interface position observations revealed natural convection in the liquid region. Remelting phenomena was not observed at both the solid-mushy and mushy-liquid interfaces.

  • PDF

Performance of an inverter refrigeration system with a change of expansion devices (인버터형 냉동시스템의 팽창장치 변경에 따른 성능특성)

  • 이용택;김용찬;박윤철;김민수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.6
    • /
    • pp.928-936
    • /
    • 1999
  • An experimental study was performed to investigate characteristics of an inverter driven water-to-water refrigeration system with a variation of compressor frequencies and expansion devices. The frequency of a compressor varied from 30Hz to 75Hz, and performance of the systems applying three different expansion devices such as capillary tube, thermostatic expansion valve(TXV), and electronic expansion valve(EEV) were measured. The load conditions were altered by varying the temperature of the secondary fluid entering condenser and evaporator with a constant flow rate. When the test conditions were deviated from the standard value(rated value), TXV and EEV showed better performance than capillary tube due to optimum control of mass flow rate and superheat. In the present study, it was observed that the variable area expansion device had better performance than constant area expansion device in an inverter refrigeration system due to active control of flow area with a change of compressor frequency and load conditions.

  • PDF