• Title/Summary/Keyword: power distribution line

Search Result 812, Processing Time 0.036 seconds

Realization of the Transmitter of Communication Modem for Control Systems using Power-Distribution Circuit (전력선 버스를 이용한 제어 시스템의 통신모뎀 송신기 구현에 관한 연구)

  • Chung, Chang-Kyung;Park, Young-Chull;Sohn, Dong-Sup
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.3
    • /
    • pp.330-335
    • /
    • 1999
  • Recently, there a lot of activities on the researches that implement many kinds of control system using power lines. To implement that, it is desirable to use hybrid PSK model because it takes advantage of PSK and DPSK which has a low-bit-error rate. In this parer, we implement the transmitter of this model. Because the power line is not designed for the data communication, we separated the signal generator circuit and the signal loading circuit so that minimized noises from outside. Also, to make it easy on the experiments, most of process are performed by software. As a result, transmitting a high frequency signal on the power line made no effects on the electrical devices.

  • PDF

The Design Efforts of PowerLine Communication System in Distribution Line (배전 계통의 자동화용 고압 전력선 통신 시스템)

  • Park, Byung-Seok;Song, Seok-Young;Lim, Young-Hoon
    • Proceedings of the KIEE Conference
    • /
    • 2003.07d
    • /
    • pp.2708-2710
    • /
    • 2003
  • 본 논문에서는 배전 계통의 고압선로를 이용한 전력선 통신 시스템을 설계하고 기초시험을 수행한 연구를 소개한다. 설계, 개발된 시스템은 450kHz이하의 저주파 대역을 이용하여, 수kbps의 전송 성능을 가진다. 아울러 수십 km정도의 길이를 갖는 배전 선로를 따라 고루 분산된 제어 노드들을 효과적으로 연결하기위하여 약 십km정도의 전송거리를 가지며, 중간 노드에서 중계시 수십km까지 가능하다. 이를 위하여 고압 커플러, 임피던스 정합장치, 고출력 앰프 등을 제작하고 그 성능 특성을 보였다.

  • PDF

A Study on Leakage of Critical Information via the Power Analysis of Power Lines (전원선의 전력분석을 이용한 주요정보 유출 가능성에 관한 연구)

  • Han, Kyong-Ho;Lee, Seong-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.11
    • /
    • pp.1571-1574
    • /
    • 2014
  • In this paper, we propose a unidirectional transmission of critical information obtained by keyboard hacking or kernel and keyboard driver hacking even though the computer is not connected to the external network. We show the hacking can be attempted in the proposed method to show the way preventing such attempts in advance. Firewalls and other various methods are used to prevent the hacking from the external network but the hacking is also attempted in various ways to detour the firewall. One of the most effective way preventing from the hacking attack is physically disconnect the internal intranet systems from the external internet and most of the government systems, military systems and big corporate systems are using this way as on one of the protection method. In this paper, we show the feasibility of transmission of security codes, etc via the short message to the external network on the assumption that a hacking program such as Trojan Horse is installed on the computer systems separated from the external network. Previous studies showed that the letters on the monitor can be hijacked by electromagnetic analysis on the computer to obtain the information even though the system is not connected ti the network. Other studies showed that the security code hint can obtained by analyzing the power consumption distribution of CPU. In this paper, the power consumption distribution of externally accessible power line is analyzed to obtain the information and the information can be transmitted to the external network. Software controlling the CPU and GPU usage is designed to control the power supply of computer. The sensors such as the Rogowski coils can be used on the external power line to collect the data of power consumption change rates. To transmit the user password by short message, due to the capacitive components and the obstacle from other power supply, A very slow protocol are used.

A Novel Clock Distribution Scheme for High Performance System and A Structural Analysis of Coplanar and Microstrip Transmission Line (고성능 시스템을 위한 클록 분배 방식 및 Coplanar 및 Microstrip 전송라인의 구조적 분석)

  • Park, Jung-Keun;Moon, Gyu;Wee, Jae-Kyung
    • Journal of the Institute of Electronics Engineers of Korea SD
    • /
    • v.41 no.4
    • /
    • pp.1-8
    • /
    • 2004
  • A novol clock distribution scheme is proposed for high-speed and low-power digital system to minimize clock skew and reduce dynamic power consumption. This scheme has ideal zero-skew characteristic by using folded clock lines (FCL) and phase blending circuit. For analyzing suitable line structures to FCLs, microstrip line and coplanar line are placed with folded clock lines. Simulation results show that the maximum clock-skew between two receivers located 10mm apart is less than lops at 1㎓ and the maximum clock-skew between two receivers located 20mm apart is less than 60ps at 1㎓. Also the results show that the minimum skews of clock signals regardless of process, voltage, and temperature variation are invariant.

Distribution Network Reconfiguration Using Feeder Modeling (피더모델링을 이용한 배전계통 재구성)

  • Kim, Se-Ho;An, Jin-Oh;Lee, Soo-Mook
    • Proceedings of the KIEE Conference
    • /
    • 1998.07c
    • /
    • pp.1156-1158
    • /
    • 1998
  • This paper Presents two distribution-feeder models to simplify complicated distribution system calculations. These equivalent models are developed to simulate the total series voltage drop at the end of the given feeder and the total line loss of the given feeder accurately. In addition, the proposed models are bidirectional. This means that power infeed can be at either end and the model is accurate. Also, it is shown that the proposed models are suitable for network reconfiguration.

  • PDF

The Additional Functions and Data Transmission Flow Diagram for Effective Operation of Distribution Automation System (배전자동화시스템의 효율적인 운용을 위한 구가기능 및 정보전송체계)

  • Lee, Jung-Ho;Ha, Bok-Nam;Cho, Nam-Hun
    • Proceedings of the KIEE Conference
    • /
    • 1998.11a
    • /
    • pp.211-213
    • /
    • 1998
  • This paper introduces the additional remote monitoring and remote setting functions needed to operate the distribution automation system effectively. we compare the additional functions with the old functions. The remote setting of minimum trip value of fault indicator is an example of additional function. It saves time and line-man's power. Also this paper describes the data transmission flow diagram for operation of distribution automation system using wireless communication method.

  • PDF

A Study on the Safety Checking and Testing method of the underground power transmission line (OF Cable) (지중송전선로 안전관리 방안 (OF케이블))

  • Choi, Jong-Soo;Park, Kang-Seo;Jeon, Jun-Man
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.10a
    • /
    • pp.429-434
    • /
    • 2009
  • In this paper it was written about the safety management plan for underground power transmission cable, and it guarantees the reliable electric power supply and facility management to prevent an electric disasters according to that. Recently fires which happens on OF Cable lead to a breakdown of power system and cause a power outage of wide area and serious social problems. So it needs an improvement of inspection ability on OF cable as well as a strict inspection system to prevent that problems in advance and it will bring us the development of electric safety management and the reliable electric power supply.

  • PDF

A Four Leg Shunt Active Power Filter Predictive Fuzzy Logic Controller for Low-Voltage Unbalanced-Load Distribution Networks

  • Fahmy, A.M.;Abdelslam, Ahmed K.;Lotfy, Ahmed A.;Hamad, Mostafa;Kotb, Abdelsamee
    • Journal of Power Electronics
    • /
    • v.18 no.2
    • /
    • pp.573-587
    • /
    • 2018
  • Recently evolved power electronics' based domestic/residential appliances have begun to behave as single phase non-linear loads. Performing as voltage/current harmonic sources, those loads when connected to a three phase distribution network contaminate the line current with harmonics in addition to creating a neutral wire current increase. In this paper, an enhanced performance three phase four leg shunt active power filter (SAPF) controller is presented as a solution for this problem. The presented control strategy incorporates a hybrid predictive fuzzy-logic based technique. The predictive part is responsible for the SAPF compensating current generation while the DC-link voltage control is performed by a fuzzy logic technique. Simulations at various loading conditions are carried out to validate the effectiveness of the proposed technique. In addition, an experimental test rig is implemented for practical validation of the of the enhanced performance of the proposed technique.

Transient State Analysis in Case of Lightning Arrester Deterioration due to Lightning Surge (뇌서지로 인한 피뢰기 열화시 과도상태 분석)

  • Lim, Sung-Yong;Kim, Kyu-Ho;Rhee, Sang-Bong;Kim, Soo-Bae
    • Proceedings of the KIEE Conference
    • /
    • 2015.07a
    • /
    • pp.276-277
    • /
    • 2015
  • As the effect of global warming continues, surge rates in Korea are also getting increased. Although there are devices to protect distribution line from the surge like lightning arrester, insulation of the lightning arrester can be destroyed if frequent surge occurs in distribution line. This paper assumed that the lightning surge hits the lightning arrester and make this device's insulation destroyed. This paper also simulated these processes utilizing EMTP/ATPDraw and verified voltage behavior when faults such as line to ground fault due to frequent lightning surge occur in lightning arrester.

  • PDF

Filter Test for Partial Discharge Detection of Underground Distribution Cables (지중배전케이블의 PD 검출용 필터 시험 연구)

  • Lee, Yong-Sung;Kim, Jung-Yoon;Lee, Kwan-Woo;Choi, Yong-Sung;Park, Dae-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.07a
    • /
    • pp.215-216
    • /
    • 2005
  • To decrease and remove of much noises that is detected in PD (partial discharge) measuring test. we forced on detection of those. We made W-LC filter for measuring PD. which adapted that to field test. We tested after design laboratory circumstances like field line. and then the phase change properties of detected signal in UHF sensor were measured by Lemke Probe and oscilloscope (TDS-3054. Tektronix). Eventually we checked decrement of noises from experimental result. Also from experimental result at the joint box of 22.9[kV] distribution line. we obtained reasonable data which enable noises to decrease. Hereafter those results will be adapted at ultra-high voltage for trouble prevention and on-line cable watch. diagnosis of those.

  • PDF