Effects of Position of Auxiliary Probe on Ground Resistance Measurement Using Fall-of-Potential Method

  • Gil, Hyoung-Jun;Kim, Dong-Woo;Kim, Dong-Ook;Lee, Ki-Yeon;Kim, Hyang-Kon
    • International Journal of Safety
    • /
    • v.7 no.2
    • /
    • pp.1-6
    • /
    • 2008
  • In this paper, the effects of the position and the angle of the potential probes on the measurements of the ground resistance using the fall-of-potential method are described and the testing techniques for minimizing the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position and angle of auxiliary probes. In order to analyze the relative error in the measured value of the ground resistance due to the position of the potential probe, the ground resistance was measured for the case in which the distance of the current probe was fixed at 50[m] and the distance of the potential probe was located from 10[m] to 50[m]. Also, the potential probe was located in turn at $30[^{\circ}]$, $45[^{\circ}]$, $60[^{\circ}]$, $90[^{\circ}]$, and $180[^{\circ}]$. As a consequence, relative error decreased with increasing distance of the potential probe and decreasing angle between the current probe and potential probe. The results could help to determine the position of the potential probe during the ground resistance measurement.

Relative Error Analysis for Measuring Value of Ground Resistance according to Position Variation of Potential Probe) (전위보조전극의 위치변화에 따른 접지저항 측정값의 상대오차분석)

  • Gil, Hyoung-Jun;Kim, Dong-Woo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.2
    • /
    • pp.96-102
    • /
    • 2009
  • In this paper, the effects of the position and the angle of the potential probes on the measurements of the ground resistance with the fall-of-potential method are described and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position and angle of auxiliary probes. In order to analyze the relative error for measuring value of ground resistance due to the position of the potential probe, ground resistance were measured in case that the distance of current probe was fixed at 50[m] and the distance of potential probe was located from l0[m] to 50[m]. Also, the potential probe was located at 30[$^{\circ}$], 45[$^{\circ}$], 60[$^{\circ}$], 90[$^{\circ}$] and 180[$^{\circ}$]. As a consequence, relative error decreased with increasing the distance of potential probe and decreasing the angle between current probe and potential probe. The results could be help to determine the position of potential probe when the ground resistance was measured at grounding system.

Characteristics for Ground Impedance of Counterpoise according to Position of Auxiliary Probe and Frequency (보조전극의 배치 및 주파수에 따른 매설지선의 접지임피던스 특성)

  • Gil, Hyoung-Jun;Kim, Dong-Woo
    • Journal of the Korean Society of Safety
    • /
    • v.27 no.4
    • /
    • pp.33-37
    • /
    • 2012
  • This paper describes the characteristics for ground impedance of counterpoise according to position of auxiliary probe and frequency using the fall-of-potential method and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position of auxiliary probes. In order to analyze the effects of ground impedance due to the distance of the current probe and frequency, ground impedances were measured in case that the distance of current probe was located from 10[m] to 100[m] and the measuring frequency was ranged in 55 [Hz], 128[Hz], 342[Hz], and 513[Hz]. The results could be help to determine the position of auxiliary probe when the ground impedance was measured at grounding system.

Effect of the Current Probe Position on Ground Resistance Measurement Using Fall-of-Potential Method (전위강하법에 의한 접지저항 측정에 미치는 전류보조전극의 위치의 영향)

  • Lee, B.H.;Eom, J.H.;Kim, S.W.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07c
    • /
    • pp.1874-1876
    • /
    • 2000
  • In this paper, the effects of the positions of the current probe on the measurements of the ground resistanc, and potential gradients with fall-of-potential method are described, and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position of the measuring auxiliary probes. The ground resistance is calculated by applying the 61.8% lute using fall-of-potential method.

  • PDF

Potential Distribution near Concrete Pole According to the position of Ground Rod (접지봉 설치에 따른 전주 주변의 전위분포)

  • Lee, B.H.;Jung, H.U.;Choi, C.H.;Cho, S.C.;Baek, Y.H.;Lee, K.S.;Ahn, C.H.
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2006.05a
    • /
    • pp.342-346
    • /
    • 2006
  • This paper describes ground surface potential rises and touch voltage. The more soil resistivity of upper layer is lower, the more ground surface potential rise is increased. Ground surface potential rise is increased as the buried depth of ground rod in lowered. Ground surface potential rises were measured in the test site and compared with results by CDEGS program. Touch voltages according to the separation distance of ground rod were measured in four directions. Touch voltages were remarkably changed by separation distance and contact position.

  • PDF

Effects of the Position of Potential Probe on Ground Resistance Measurements Using the Fall-of-Potential Method (전위강하법에 의한 접지저항측정에 미치는 전위보조전극 위치의 영향)

  • 이복희;어주홍;김성원
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.15 no.2
    • /
    • pp.97-104
    • /
    • 2001
  • The effects of the position of potential probe on the measurements of the ground resistance in the fa11-of-potential method are described. The ground resistance is theoretically calculated by applying the 61.8[%] rule, and then the potential probe is located on the straight line between the grounding electrode to be measured and the current probe. However, sometimes the grounding electrode to be measured and the measuring potential and current probes in on-site test might not be arranged on the straight line with adequate distance because there are building, roadblock construction and other establishments. Provided that the grounding electrode to be measured and the measuring potential probes are out of position on the straight line, the measurement of the ground resistance classically falls into an error and the measured ground resistance should be corrected. In this work, measurements were focused on the grounding electrode system made by the ground rods of 2.4 m long. The measuring error was increased with increasing the angle which is made by the 3-points of the grounding electrode to be measured, the potential anti current probes, and it was a negative. That is, all of the measured ground resistances ware less than the true ground resistance.

  • PDF

Method for Collision Avoidance Motion Coordination of Multiple Mobile Robots Using Central Observation (다중 이동 로봇의 중앙 감시에 의한 충돌 회피 동작조정 방법)

  • Ko Nak Yong;Seo Dong-Jin
    • The Transactions of the Korean Institute of Electrical Engineers D
    • /
    • v.52 no.4
    • /
    • pp.223-232
    • /
    • 2003
  • This paper presents a new method driving multiple robots to their goal position without collision. Each robot adjusts its motion based on the information on the goal location, velocity, and position of the robot and the velocity and position of the .other robots. To consider the movement of the robots in a work area, we adopt the concept of avoidability measure. The avoidability measure figures the degree of how easily a robot can avoid other robots considering the following factors: the distance from the robot to the other robots, velocity of the robot and the other robots. To implement the concept in moving robot avoidance, relative distance between the robots is derived. Our method combines the relative distance with an artificial potential field method. The proposed method is simulated for several cases. The results show that the proposed method steers robots to open space anticipating the approach of other robots. In contrast, the usual potential field method sometimes fails preventing collision or causes hasty motion, because it initiates avoidance motion later than the proposed method. The proposed method can be used to move robots in a robot soccer team to their appropriate position without collision as fast as possible.

An Analysis of the Protective Potential Distribution against Corrosion for Hull ICCP with Computer simulation (컴퓨터 Simulation을 통한 선체 음극방식(ICCP)의 방식전위분포해석)

  • Im, Gwan-Jin;Kim, Ki-Joon;Lee, Myung-Hoon;Moon, Kyung-Man
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2005.06a
    • /
    • pp.395-400
    • /
    • 2005
  • The ship hull part is always exposed to severe corrosive environments. Therefore, it should be protected in appropriate ways to reduce corrosion problems. So there are two effective methods in order to protect the corrosion of ship hull. One is the paint coating as a barrier between steel and electrolyte (seawater) and the other is the cathodic protection(CP) supplying protection current. In the conventional design process of the cathodic protection system the required current densities of protected materials have been used. However, the anode position of field or laboratory experiment for obtaining the required current density for CP is significantly different from anode position for real structures. Therefore, the recent CP design must consider the optimum anode position for potential distribution equally over the ship hull. The CP design companies in the advanced countries can obtain the potential distribution results on the cathodic materials by using the computer analysis module. This study would show how to approach the potential analysis in the field of corrosion engineering. The computer program can predict the under protection area on the structure when the boundary condition and analysis procedure are reasonable. In this analysis the polarization curve is converted to the boundary condition in material data.

  • PDF

USING AN ABSTRACTION OF AMINO ACID TYPES TO IMPROVE THE QUALITY OF STATISTICAL POTENTIALS FOR PROTEIN STRUCTURE PREDICTION

  • Lee, Jin-Woo
    • Journal of the Korean Society for Industrial and Applied Mathematics
    • /
    • v.15 no.3
    • /
    • pp.191-199
    • /
    • 2011
  • In this paper, we adopt a position specific scoring matrix as an abstraction of amino acid type to derive two new statistical potentials for protein structure prediction, and investigated its effect on the quality of the potentials compared to that derived using residue specific amino acid identity. For stringent test of the potential quality, we carried out folding simulations of 91 residue A chain of protein 2gpi, and found unexpectedly that the abstract amino acid type improved the quality of the one-body type statistical potential, but not for the two-body type statistical potential which describes long range interactions. This observation could be effectively used when one develops more accurate potentials for structure prediction, which are usually involved in merging various one-body and many-body potentials.

A comparative study between stress concentration factor of the infinite plate with elliptic hole and presuure coefficient of the potential flow around elliptic cylinder (추원공을 가진 무한평판의 응력집중계수와 추원주를 가진 Potential Flow 의 응력계수와 비교연구)

  • ;;Yoon, Kab Young
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.5 no.4
    • /
    • pp.354-361
    • /
    • 1981
  • This study aims to compare stress concentratior factors in a loaded elastic body of the infinite plate with pressure coefficients of a fluid in the potential flow. First in view of hydrodynamics, when a single elliptic cylinder in the form of a bluff body stands in the potential flow, the pressure distribution(doefficient, C$\_$p/around the elliptic cylicder which is changed according to the position(angular displacements)is theoretically analyzed and calulated; secondly, in view of theory of elasticity, when an eliptic hole which is made on a flat plate gets tension, the stress distribution(factor) around the elliptic hole which is changed according to the position(angular displacements )is theoretically(K$\_$t/) and experimentally (K$\_$e/) measured; and finally. The results are compard and examined.