Protection Coordination Associated with Connection Location of Residual Current Devices and Surge Protective Devices (RCD와 SPD의 접속 위치에 따른 보호협조)

  • Lee, Bok-Hee;Park, Hee-Yeoul;Shin, Gun-Jin;Bae, Gwan-Young;Ryu, Chun-Hyoung;Lee, Kang-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.3
    • /
    • pp.100-106
    • /
    • 2013
  • In this paper, in order to analyze lightning impulse response characteristics in combined installations of SPDs and RCDs, surge protection coordination between SPDs and RCDs are experimentally investigated by using the combination wave generator. Six different types of single-phase residual current operated circuit-breakers with integral overcurrent protection for household and similar uses(RCBOs) being present on the domestic market are tested according to KS C IEC 61009-1 standard. As a result, when a class I SPD is located on the source side of an RCBO, all kinds of specimens are able to provide the proper coordination between the SPD and RCBOs without nuisance tripping, unintended operation or damage due to test impulse currents. However, in the case that the class II SPD is located on the load side of RCBOs, a lot of L-N mode injected currents is split into the RCBO, and a few RCBOs are damaged. Coordination between SPDs and RCDs is not valid and a role of SPDs is of no use. When combining SPDs with RCDs, it is necessary to select SPDs and RCDs in consideration of the protection voltage level of metal oxide varistor embedded in RCDs.

Effects of the Injected Number and Amplitude of 8/20 [μs] Impulse Current on the Life of ZnO Varistors (8/20 [μs] 임펄스전류의 인가횟수와 크기가 ZnO바리스터의 수명에 미치는 영향)

  • Lee, Bok-Hee;Li, Feng
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.1
    • /
    • pp.118-124
    • /
    • 2007
  • This paper presents the effects of the injected number and amplitude of impulse current on the service life of ZnO varistors for low voltages. To analyze the effects of lightning impulse currents on the performance of ZnO varistors, the measurements of resistive leakage current and power dissipation at the power frequency ac voltage before and after the injections of the $8/20[{\mu}s]$ impulse currents were made. As a consequence, the duration and amplitude of resistive leakage current flowing through ZnO varistor were increased with increasing the number of injections of the $8/20[{\mu}s]$ impulse currents. It is desirable that the service life of ZnO varistors should be evaluated as a function of the number and amplitude of lightning impulse current.

High Frequency Impedance Calculation of Grounding Meshes Installed at Power Substations (전력용 변전소에 설치된 메쉬 접지망의 고주파 임피던스 계산)

  • Han, Poong;Choi, Chang-Hyek
    • Proceedings of the KIEE Conference
    • /
    • 1998.07e
    • /
    • pp.1578-1582
    • /
    • 1998
  • The ground potential rise generated by the switching surge or lightning stroke may be dangerous to personnel and cause damage to electronic control parts. For a first step to the transient performance analysis. high frequency impedances of grounding grids have been calculated and discussed. Grounding grids include 7 square grids from $10m{\times}10m$ to $80m{\times}80m$. The high frequency current was injected into the center and a corner of the grounding grid. The calculation results indicate that the impedance of the grounding grid is significantly influenced by frequency and the point of injection of the current. and the effective radius of a large grounding grid may be represented in $15{\sim}20m$.

  • PDF

Development of a Surge Protective Device for Computer Network to International Standards (국제규격 대응 컴퓨터 네트워크용 서지방호장치 개발)

  • Park Dae-won;Song Jae-yong;Han Joo-sup;Kil Gyung-suk
    • Journal of the Korea Institute of Information and Communication Engineering
    • /
    • v.9 no.6
    • /
    • pp.1253-1259
    • /
    • 2005
  • This paper dealt with the development of surge protection devices (SPDs) that can protect high speed computer network devices from overvoltages caused by switching operations or lightning surges. The designed SPD is a form of hybrid circuit which is composed of a gas tube having large current diverting capability, high response bi-directional avalanche diodes, and fast recovery diodes to reduce insertion loss on high frequency domain. Surge protection and signal transmission characteristics of the fabricated SPD was tested according to the international standards, IEC 61000-4-5 and IEC 61643-21. From the test results, the SPD is satisfied with the international standards and the high cut-off frequency was 204 MHz. Also, the SPD showed a good performance without an insertion loss on a field test of 100 Mbps class Local Area Network.

A Study on the Best Selection of Lightning Arrester for DC Electric Traction Vehicles (직류전동차 탑재용 피뢰기의 최적선정에 관한 연구)

  • Cha, Myung-Soo;Song, Jae-Yong;Kim, Il-Kwon;Kil, Gyung-Suk;Lee, Dae-Sung;Park, Jae-Kyu
    • Proceedings of the KIEE Conference
    • /
    • 2006.07c
    • /
    • pp.1519-1520
    • /
    • 2006
  • This paper describes a selection and application recommendations of ZnO arresters on DC electric traction vehicles. We measured and analyzed the system voltages applied to arresters and the surge currents flowing arresters on DC electric traction vehicles under operation to decide the Continuous Operating Voltage($U_C$), the Rated Voltage($U_R$), and the Nominal Discharge Current($I_n$). System voltages measured up to 1,800 V during anti-breaking in 1,500 V-system, and surge currents were recorded up to 3 times per running-service-route and their magnitudes were ranges of $150A{\sim}2kA$. From these results and the standard EN50163, we proposed the Continuous Operating Voltage($U_C$) the Rated Voltage($U_R$) for the $1,500V_{dc}$ electric traction vehicles.

  • PDF

The Decreasing of Surge Impedance of Grounding System by using Discharge (지중방전현상에 의한 접지시스템의 써지 임피던스의 저감)

  • 정재기;강지원;양병모;김홍필
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.12 no.4
    • /
    • pp.55-61
    • /
    • 1998
  • Generally, in the calculation of ground resistance in the grounding system, the method measuring ground potential rise which is caused by low frequency source injection is used. But both lightning and surge impulse re very harmful to electric equipment. In this connection, this paper presents the results of an experimental investigation of transient behavior of ground impedances when lightening current is injected to the electric rod the experimental results are agreement with the theoretical analysis. In addition, the states on the behavior of ground electrodes under impulse currents due to lighting strokes are presented. And the impulse impedance reductions caused by discharge in the soils are presented.

  • PDF

Lightning Protection System of Solar Power Generation Device (태양광발전장치의 낙뢰보호 시스템)

  • Yongho Yoon
    • The Journal of the Institute of Internet, Broadcasting and Communication
    • /
    • v.23 no.2
    • /
    • pp.157-162
    • /
    • 2023
  • Among the failures of photovoltaic power generation facilities, failures caused by surges account for 20% of the total failure rate, and energy emissions of tens to hundreds [A] during power generation and electrical damage to inverters and connection boards lead to electrical safety accidents. In particular, in the case of lightning, an abnormal voltage is induced in an electric circuit to destroy insulation, and the current flowing at this time causes a fire and acts as a factor that accelerates the deterioration of parts. Due to this action, the problem of electrical safety of solar power generation devices spreading from outside the city center to the inside of the city center such as houses, apartments, and government offices is emerging. Since lightning strikes cause both field-based and conducted electrical interference, this effect increases with increasing cable length or conductor loops. In addition, surge damages not only solar modules, inverters and monitoring devices, but also building facilities, which can eventually cause operational shutdown due to fire of the photovoltaic power generation system and consequent financial loss. Therefore, in this paper, a lightning protection system for solar power generation devices is studied for the purpose of reducing property damage and human casualties due to the increase in fire and electrical safety accidents caused by lightning strikes in photovoltaic power generation systems.

Discharge Luminous Phenomena Caused Between ZnO Surge Arrester Block and Electrodes (산화아연 피뢰기 소자와 전극사이에 발생하는 방전광 현상)

  • Lee, Bok-Hee;Park, Keon-Young;Kang, Sung-Man
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.3
    • /
    • pp.44-50
    • /
    • 2005
  • This paper deals with the characteristics and reduction methods of the plasma luminosity caused between the ZnO surge arrester block and metal electrodes. In this study, the impulse current generator that can generate $8/20[{\mu}s]$ impulse currents with a peak short-circuit of 10[kA] is designed and fabricated. Plasma luminosity phenomena for fine and used ZnO blocks were observed as a function of the contact states between the ZnO block and electrodes and the polarity of applied impulse voltages. As a result, discharge luminous events are produced near the contact edges between the ZnO block and metal electrodes. The discharge plasma luminosity between the ZnO surge arrester block and low potential electrode is more intensive than that between the ZnO surge arrester block and high potential electrode. Surface flashover of ZnO blocks are mainly caused by plasma generation near the edge of metal electrode. Also, plasma luminosity for the fine ZnO blocks is less than that for the used ZnO blocks. Plasma luminosity at the contact of the ZnO block and ring-type electrode is more intensive than that at the contact of ZnO block and disk electrode. It is desirable to use the disk electrode with the proper contact area to reduce the plasma luminosity caused at the contact point between the ZnO block and electrodes.

Field Test and Analysis for Proper Location of Protective Equipment in Underground Distribution System (지중배전계통 보호설비 적정위치 선정을 위한 실증시험과 해석)

  • Yun, Chang-Sub;Lee, Jong-Beom
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.5
    • /
    • pp.773-782
    • /
    • 2008
  • This paper describes the method for proper location of protective equipment in underground distribution cable through field test and analysis at testing lines. To prove the reliability for analysis simulated by EMTP/ATPDraw, the testing results obtained by the real test and the analysis for the same test lines were compared each other. The accuracy of analysis was proved by the comparison. Over voltages were measured and analyzed at each point of cable and switches in case of which lightning surge current was applied. The analysing method was applied to real distribution systems to select the proper location of protective equipment. It is evaluated that the location of protective equipment was properly selected.

Electrical Characteristics Test of Distribution Polymer Lightening Arresters (배전용 폴리머 피뢰기의 전기적 특성시험)

  • Kwon, Tae-Ho;Lee, Byung-Sung;Song, Il-Keun;Kim, Dong-Myung;Yoon, Tae-Sang;Jung, Sang-Bong
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.546-549
    • /
    • 2004
  • This paper describes the electrical characteristics of the polymer lightning arresters(L.As) used to protect distribution lines and power facilities from surge. For the relative comparison, the characteristics assessment was done for 2 states of L.As before and after water immersion treatment. The L.As for the comparative test were immersed with water of $95[^{\circ}C]$ considered a severe condition. After the immersion treatment, the assessment was carried out for material analyses in chemical structure(FTIR : fourier transform infrared spectrophotometer). Electrical performance measured insulation resistance measurement, leakage current measurement, critical operation voltage measurement etc.. In addition to, the results were compared with those for the L.As deteriorated in the field. Thus, the accelerative deterioration degree of polymer materials by immersion treatment was evaluated, by which the structural defects of the polymer L.As could be inferred.