Arcing horn design specification and electrical characteristics special quality estimation of distribution line (배전선로의 내뢰흔 설계사양 및 전기적 특성 평가)

  • Kim, Seok-Sou;Choi, Ik-Sun;Park, Tae-Gon
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.11a
    • /
    • pp.472-473
    • /
    • 2007
  • This study evaluated electrical characteristics of the manufactured arcing horn whose rated voltage and nominal discharge current were 18kV and 2.5kA, respectively. In this study, residual voltage and lightning impulse flashover voltage were examined. The arcing horn showed excellent electrical characteristics that residual voltage and lightning impulse flashover voltage were 55kV below and 121kV at 115mm, respectively. Therefore the manufactured arcing Horn is considered that it would show good performance for protecting electrical wires and line post insulators from lightning impulse, if it were applied to real fields.

  • PDF

Change of Electrical Characteristics of ZnO Arrester Blocks by Lightning Impulse Current (뇌충격전류에 의한 산화아연형 피뢰기 소자의 전기적 특성변화)

  • Gil, Gyeong-Seok;Han, Ju-Seop;Park, Yeong-Ho
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.48 no.7
    • /
    • pp.550-555
    • /
    • 1999
  • This paper deals with the effect of lightning impulse current on electrical characteristics of ZnO blocks used in distribution lightning arrester. The electrical characteristics of ZnO blocks are degraded by overtime impulse current, and the degraded ZnO block is brought to a thermal runaway and finally destroyed. It is therefore important to estimate the change of electrical characteristics of ZnO blocks. In this study, an impulse current generator which can produce 8/20$[\mus]$, 3[㎄] and 4/10$[\mus]$, 5[㎄] waveform is designed and fabricated to simulate the lightning impulse current of power systems. Total energy applied to the ZnO blocks at each time is 739[J] in 8/20$[\mus]$, and 523[J] in 4/10$[\mus]$, impulse current, respectively. From the experimental results, the 3rd harmonic of the leakage current increases continuously with the number of applied impulse current, but no significant changes in residual voltage and in reference voltage are observed until the ZnO block is destroyed. Also, it is confirmed that the main factor on degradation of ZnO blocks is rather the total energy applied to ZnO blocks than the peak value of the impulse current.

  • PDF

Development of ZnO Varistor for Distribution Surge Arrester (18kV, 5kA) (배전급 피뢰기(18kV, 5kA)용 ZnO 바리스터 소자 개발)

  • 박춘현;윤관준;조이곤;정세영;서형권
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.212-216
    • /
    • 2000
  • ZnO varistors for distribution surge arrester (18kV, 5kA) were developed and tested microstructure and electrical characteristics. Microstructure of ZnO varistor was consisted of ZnO grain, spinel phase and Bi-rich phase. Average grain size of ZnO varistor was $\mu\textrm{m}$ Reference voltage and lightning impulse residual voltage of ZnO varistor exhibited a good haracteristics above 5.5kV and below 11.56kV, respectively. Consequently, discharge capacity which is the most important characteristics of ZnO varistor for surge arrester exhibited excellent properties above 70kA at twice high-current impulse test. Moreover, variation rate of reference voltage and lightning impulse residual voltage showed below 5% and 2% after high-current impulse test, respectively. Leakage current and watt loss of ZnO varistor will not increase during accelerated aging test at stress condition, such as 3.213kV/$115^{\circ}C$/1000h.

  • PDF

Characteristics of Lightning Impulse Current of Zno Block for Transmission Line Arrester with External Gap (송전선로에 사용되는 갭형 피뢰기 소자의 뇌임펄스 전류특성)

  • Cho, Han-Goo;Yoo, Dae-Hoon
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.04b
    • /
    • pp.61-62
    • /
    • 2009
  • This paper describes the characteristics of lightning impulse current of ZnO block for transmission line arrester with external gap. The ageing parameters of lightning arresters ate impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by impulse current. Total energy applied to the ZnO arrester each time is $4/10{\mu}s$, 30kA and $2/20{\mu}s$, 10kA impulse current. Before and After the test, the residual voltage variation of varistors passed was below 5%. According to the test, it is thought that the ZnO arrester shows good stability with impulse current test.

  • PDF

Characteristics of Lightning Impulse Current of ZnO Block for Transmission Line Arrester with External Gap (송전선로에 사용되는 갭형 피뢰기 소자의 뇌임펄스 전류특성)

  • Cho, Han-Goo;Yoo, Dae-Hoon
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.06a
    • /
    • pp.458-459
    • /
    • 2007
  • This paper describes the characteristics of lightning impulse current of ZnO block for transmission line arrester with external gap. The ageing parameters of lightning arresters are impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by impulse current. Total energy applied to the ZnO arrester each time is $4/10{\mu}s$, 30kA and $2/20{\mu}s$, 10kA impulse current. Before and After the test, the residual voltage variation of varistors passed was below 5%. According to the test, it is thought that the ZnO arrester shows good stability with impulse current test.

  • PDF

Change of the Characteristics of ZnO Arrester Blocks by Lightning Impulse Current (산화아연형 피뢰기 소자의 뇌충격전류에 의한 특성 변화)

  • Han, Joo-Sup;Song, Jae-Yong;Kil, Gyung-Suk
    • Proceedings of the KIEE Conference
    • /
    • 1998.11c
    • /
    • pp.907-909
    • /
    • 1998
  • This paper describes the effect of impulse current on degradation of ZnO blocks. In this study, an impulse current generator which can produce 8/20 [${\mu}s$], 3 [kA] and 4/10 [${\mu}s$], 5 [kA] waveform is designed and fabricated to simulate the lightning impulse current. The residual voltage, reference voltage, and leakage current flowing to the ZnO blocks are observed. The experimental results show that the leakage current increases continuously with the number of applied impulse current, but no significant changes in residual voltage and in operating voltage are observed until the ZnO block is destroyed. Also, it is confirmed that the main factor on degradation of ZnO blocks is rather the total energy applied to ZnO blocks than the peak value of the impulse current.

  • PDF

A Study of Lightning Impulse Operating Duty and Temperature Dependence of Series Gap Type Arrester (Series Gap Type 피뢰기의 뇌임펄스 동작책무 및 온도의존성에 관한 연구)

  • Cho, Han-Goo;Yoo, Dae-Hoon
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.22 no.8
    • /
    • pp.659-664
    • /
    • 2009
  • This paper describes lightning impulse operating duty performance and temperature dependence of series gap type for transmission line arresters. The ageing parameters of lightning arresters are impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by lightning impulse current. In the discharge withstand test, total energy applied to the ZnO arrester each time is 4/10 ${\mu}s$, 30 kA. and in the operating duty test, the arrester has passed the test if thermal stability is achieved, if the residual voltage measured before and after the test is not changed by more than 5 %, and after the test reveals no evidence of puncture, flashover or cracking of the ZnO block. As a results, the residual voltage was in the range of 17.2${\sim}$20.3 kV and ZnO block bear up against at 2 shot of series impulse current of 30 kA. Also it was so excellent that the mechanical destruction does not occur at the 2 groups of 5 impulses current of 2/20 ${\mu}s$ 10 kA. According to the tests, it is thought that the ZnO arrester shows good stability with impulse current test. and it was found that the ambient temperature is increased resistive leakage current was increased in the range 47.3${\sim}$167.4 ${\mu}A$.

The Electrical Characteristics of ZnO varistor for d.c. Arrester (직류 피뢰기용 ZnO 소자의 전기적 특성)

  • Kim, Seok-Sou;Choi, Ike-Sun;Cho, Han-Gu
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07b
    • /
    • pp.1106-1110
    • /
    • 2003
  • The electrical characteristics of $A{\sim}C's$ ZnO varistors fabricated according to variable sintering condition, which sintering temperature is $l130^{\circ}C$ and speeds of pusher are A: 2mm/min, B: 4mm/min, C: 6 mm/min, respectively, were investigated. The varistor voltage of $A{\sim}C's$ ZnO varistors sintered at $1130^{\circ}C$ increased in order A < B $A{\sim}C's$ ZnO varistors exhibited below 2mA at rated voltage. Lightning impulse residual voltage of A's ZnO varistor suited standard characteristics, which is 3.85kV at 2.5kA, 4.4kV at 5kA and 5.16kV at 10kA. After multi lightning impulse residual voltage test of A's ZnO varistor exhibited good discharge characteristics which ZnO varistor reveals no evidence of puncture, flashover, cracking in visual examination. After high current impulse test of A's ZnO varistor exhibited good discharge characteristics, which variation rate of residual voltage is 0.4% before and after test, and revealed no evidence.

  • PDF

A Development of ZnO Varistor for Railroad Vehicle d.c. Arrester (전철탑재형 직류피뢰기용 ZnO 바리스터의 개발)

  • Cho, I-Gon;Park, Choon-Hyun;Jung, Se-Young;Song, Tae-Kwon;Kim, Suk-Soo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.552-556
    • /
    • 2002
  • The microstructure and electrical characteristics of A~C's ZnO varistors fabricated according to variable sintering condition, which sintering temperature is $1130^{\circ}C$ and speeds of pusher are A: 2mm/min, B: 4mm/min, C: 6mm/min, respectively, were investigated. In the microstructure, A~C's ZnO varist-ors fabricated variable sintering condition was consisted of ZnO grain(ZnO), spinel phase$(Zn_{2.33}Sb_{0.67}O_4)$ Bi-rich $phase(Bi_{2}O_{3})$, wholly. Varistor voltage of A~C's ZnO varistors sintered at $1130^{\circ}C$ increased in order A < B < C's ZnO varistors. C's ZnO varistor exhibited good characteristics that nonlinear exponent is 31.70. Leakage current of A~C's ZnO varistors exhibited below 2mA at rated voltage. Lightning impulse residual voltage of A's ZnO varistor suited standard characteristics, which is 3.85kV at 2.5kA, 4.4kV at 5kA and 5.16kV at 10kA. After multi lightning impulse residual voltage test of A's ZnO varistor exhibited good discharge characteristics which ZnO varistor reveals no evidence of puncture, flashover, cracking in visual examination. After high current impulse test of A's ZnO varistor exhibited good discharge characteristics, which variation rate of residual voltage is 0.4% before and after test, and revealed no evidence.

  • PDF

Performance Estimation of Protector for 154 kV Underground Cable (154kV 지중 케이블 보호장치의 성능평가)

  • Cho, H.G.;Lee, J.H.;Han, S.W.;Kim, S.S.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.05c
    • /
    • pp.127-131
    • /
    • 2002
  • The surge protector is crucial power apparatus to guarantee the safe operation of power transmission of underground cable which can effectively restrain the overvoltage and inductive lightning stroke in power system. The surge protector is crucial power apparatus to guarantee the safe operation of power transmission of underground cable which can effectively restrain the overvoltage and inductive lightning stroke in power system. This paper described the results of a study on the performance for surge protector for underground cable. And, the performance of surge protector was evaluated through such as measurement of the reference voltage, residual voltage and impulse current etc. In results of surge protector, reference and residual voltage of ZnO element is 4.75 kV, 9.86 kV respectively. Also, In the impulse current test, thermal properties are good, despite of that polymeric housing of surge protector has thick structure. Therefore the developed surge protector is thought to apply for underground cable.

  • PDF