Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference (한국전기전자재료학회:학술대회논문집)
- 2007.11a
- /
- Pages.472-473
- /
- 2007
Arcing horn design specification and electrical characteristics special quality estimation of distribution line
배전선로의 내뢰흔 설계사양 및 전기적 특성 평가
- Kim, Seok-Sou (KERI) ;
- Choi, Ik-Sun (KERI) ;
- Park, Tae-Gon (Changwon Uni.)
- Published : 2007.11.01
Abstract
This study evaluated electrical characteristics of the manufactured arcing horn whose rated voltage and nominal discharge current were 18kV and 2.5kA, respectively. In this study, residual voltage and lightning impulse flashover voltage were examined. The arcing horn showed excellent electrical characteristics that residual voltage and lightning impulse flashover voltage were 55kV below and 121kV at 115mm, respectively. Therefore the manufactured arcing Horn is considered that it would show good performance for protecting electrical wires and line post insulators from lightning impulse, if it were applied to real fields.