• Title/Summary/Keyword: gas insulation

Search Result 539, Processing Time 0.031 seconds

A numerical study on the fatigue evaluation of mark-III LNG primary barrier (수치해석을 이용한 Mark-III LNG 1차 방벽에 대한 피로 평가)

  • Kwon, Sun-Beom;Kim, Myung-Sung;Lee, Jae-Myung
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.41 no.4
    • /
    • pp.337-344
    • /
    • 2017
  • The demand of liquified natural gas is increasing due to environmental issues. This reason has resulted in increasing the capacity of liquified natural gas cargo tank. The Mark-III type primary barrier directly contacts liquified natural gas. Also, the primary barrier is under various loading conditions such as weight of liquified natural gas and sloshing loads. During a ship operation, various loads can cause fatigue failure. Therefore, the fatigue life prediction should be evaluated to prevent leakage of liquified natural gas. In the present study, the fatigue analysis of insulation system including primary barrier is performed using a finite element model. The fatigue life of primary barrier is carried out using a numerical study. The value of principle stress and the location of maximum principle stress range are calculated, and the fatigue life is evaluated. In addition, the effects on the insulation panel status and the arrangement of knot or corrugation are analyzed by comparing the fatigue life of various models. The insulation system which has best structural performance of primary barrier was selected to ensure structural integrity in fatigue assessment. These results can be used as a design guideline and a fundamental study for the fatigue assessment of primary barrier.

Breakdown Characteristics of $SF_6$ Gas under Particle Contaminated Conditions (금속입자 오손시 $SF_6$가스의 절연파괴특성)

  • Kim, Min-Kyu;Moon, In-Wook;Kim, Ik-Soo;Lee, Hyeong-Ho
    • Proceedings of the KIEE Conference
    • /
    • 1995.11a
    • /
    • pp.465-468
    • /
    • 1995
  • The gas-insulated switchgear(GIS) has made high-reliability, high-safety, compact substations possible by using $SF_6$ gas. They are likely to be further developed toward higher voltages and targer capacities, along with greater compactness and lower cost. Although $SF_6$ gas has excellent insulation performance, breakdown voltages are reduced by the conducting particles. Thus, extensive studies have been made on the breakdown characteristics of $SF_6$ gas in particle contaminated conditions. Experiments were carried out for fired particle and free particle in a coaxial electrode system with DC and AC voltages. This paper represents the experimental results of the processes involved in electrical breakdown in compressed $SF_6$ gas, where breakdown is initiated by conducting particles.

  • PDF

Insulation Performance and BOR of Pressurized Large-capacity Liquid Hydrogen Storage Tank (가압식 대용량 액체수소 저장탱크의 단열 성능과 BOR)

  • HEUNG SEOK SEO;YEONGBUM LEE;DONGHYUK KIM;CHANGWON PARK
    • Transactions of the Korean hydrogen and new energy society
    • /
    • v.34 no.6
    • /
    • pp.650-656
    • /
    • 2023
  • In order to efficiently control boil-off rate of a liquefied hydrogen tank, the important thing is to maintain an appropriate vacuum level. however, compared to small and medium-sized storage tank, it is very difficult to create and maintain vacuum in large-capacity storage tanks. In this study, we aim to determine the target level of future large-capacity storage tank technology development and secure basic data on performance test methods by analyzing the corelation between evaporation gas and thermal conductivity of liquefied hydrogen storage tanks.

A Study on Optimal Insulation Design of the Distribution Level HTS FCL (배전급 고온초전도 한류기 절연설계 최적화 연구)

  • Seok, B.Y.;Kang, H.;Lee, C.;Nam, K.;Ko, T.K.
    • Proceedings of the KIEE Conference
    • /
    • 2006.07b
    • /
    • pp.723-724
    • /
    • 2006
  • In this study, superconducting coil arrangements and cryostat concept design were conducted for the development of 13.2kV/630A bifilar winding type high temperature superconducting(HTS) fault current limiter(FCL) with YBCO coated conductor(CC) wire. The coil consists of several layers with unique non-inductive solenoid winding method. Six types of HTS coil arrangements were investigated for the optimal insulation design of HTS FCL. And, conceptual design of cryostat was conducted for the decrement of thermal invasion and the prevention of low voltage insulation breakdown in the LHe which is used as pressurization gas in sub-cooling condition of liquid nitrogen(LN2). As the results, it was found that the modified suspended type cryostat with horizontal coil arrangement is beneficial to the insulation design of 13.2kV level bifilar winding type HTS FCL.

  • PDF

Efficiency Estimation of Toxicity Free Eire Resistance Cable

  • Yoon, Hun-Ju;Hon, Jin-Woong
    • Transactions on Electrical and Electronic Materials
    • /
    • v.3 no.3
    • /
    • pp.34-38
    • /
    • 2002
  • In this paper, efficiency estimation of toxicity fee fire resistance cable experiments was measured smoke density of toxicity free fire resistance polyolefin insulation material and electric field dependence of tree shape in low density polyethylene (LDPE). One of the most serious causes of failure in high-voltage cables, can be an electrical discharge across an internal gab or void in the insulating material. Treeing due to partial discharge is one of the main causes of breakdown in the insulating materials and reduction of the insulation life. Therefore the necessity for establishing a method to diagnose the aging of insulation materials and to predict the breakdown of insulation and research of the fire resistance character has become important. First, we have studied on electric field dependence of tree shape in LDPE about treeing phenomena occurring on the high electrical field. Second, the measurement method is the attenuation quantity of irradiation by smoke accumulating with in a closed chamber due to non-flaming heat decomposition and flaming combustion. A main cause of fire-growth and generating toxic gas when, it bums, should be dealt with great care in life. safety design. The fire gases were occurred carbon monoxide and decomposition than in polyolefin due to incomplete combustion of PVC, which has high content of carbon in chemical compound.

Impulse breakdown Characteristics in SF6/N2, Gas Mixtures with a Temperature Variation (온도변화에 따른 SF6/N2 혼합가스의 임펄스 절연파괴특성)

  • Li, Feng;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.12
    • /
    • pp.79-86
    • /
    • 2008
  • This paper presents the experimental results of impulse breakdown characteristics in $SF_6/N_2$ gas mixtures under a highly non-uniform electric field with a change in temperature. The test temperature ranges from -25[$^{\circ}C$] to 25[$^{\circ}C$]. The processes of impulse preliminary breakdown developments were analyzed by the measurements of current pulse and luminous signals. As a result, the temperature dependance of breakdown voltage for the negative polarity was much stronger than that for the positive polarity. When increasing the temperature, The leader stepping time for the negative polarity was shown to be longer than that for the positive polarity. The results presented in this paper can be used as a useful information in designing the gas insulation lines with prominent ability for lightning surge.

Patterns and Characteristics of Corrugated Stainless Steel Tubing for a Yellow Insulation Ring Type by Artificially Deteriorated (인위적으로 열화된 황색절연링형 금속플렉시블호스의 패턴 및 특성)

  • Lee, Jang-Woo;Choi, Chung-Seog
    • Fire Science and Engineering
    • /
    • v.32 no.6
    • /
    • pp.1-6
    • /
    • 2018
  • This study is to analyze the characteristics of the yellow insulation ring type of the CSST used for tubing when it is artificially deteriorated and damaged by burning. The CSST for tubing consists of a tube, protective coating, nut, yellow insulation ring, packing, and socket. In addition, it is thought that a yellow insulation ring and rubber packing were used to connect the tube and socket in order to improve the airtightness and insulation performance. The result of the verification of the data acquired from the tests in the 95% confidence interval shows that the Anderson-Darling (AD) and P value were analyzed to be 0.945 and 0.015, respectively. This confirms that the test data of the CSST for tubing is reliable. The analysis of the arithmetic mean of the insulation resistance of a CSST showed that the CSST damaged by burning by a torch, and the one damaged by electrical burning, was $16.7k{\Omega}$ (the greatest relatively) and $208{\Omega}$ (the lowest), respectively, while it was $1.72k{\Omega}$ in the case of a normal product. Therefore, the analysis result of the insulation resistance of the CSST collected from the scene of a fire can be utilized to examine the cause of damage by burning. In addition, it was found that when the maximum current of 97 A was applied to the CSST for about 5 s using a Primary Current Injection Test System (PCITS) the protective film and insulation ring of the CSST has no difference from that of a normal product. However, a part of the metal tube was melted.

The Electric Fields Characteristics of Partial Discharges in $SF_6$ ($SF_6$ 가스중 부분방전시 전계 특징)

  • 김해준;박경태;박광서;이현동;김충년;이광식
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2001.11a
    • /
    • pp.145-149
    • /
    • 2001
  • The most of faults in gas insulation of power facilities are caused by partial discharge. Therefore we simulated partial discharge and measured the radiated electromagnetic wave emitted from partial discharge in SF$_{6}$ gas by biconical antenna. This paper describes time delay and electric fields pulse characteristics of radiated electromagnetic waves with distance(1[m], 3[m], 5[m]) between antenna and discharge source.e.

  • PDF

A Study on the integrity assessment of the high voltage transformer with Dissolved Gas Analysis (특고압 변압기 건전성 평가에 관한 연구)

  • Lee, Il-Moo;You, Sang-Bong;Joung, Hea-Sung
    • Proceedings of the KIEE Conference
    • /
    • 2015.07a
    • /
    • pp.1463-1464
    • /
    • 2015
  • This paper describes for the diagnosis insulating oil for transformers integrity assessment. The high-capacity oil transformer has several insulators are entered for the purpose of insulation, such as insulating oil, insulating paper and press board. Irradiated with a gas component dissolved in the insulating oil can analyze the status of the transformer, and can prevent a sudden accident in advance.

  • PDF

The Electric Field Analysis with Conducting Particle between Coaxial Cylindrical Electrodes in $SF_6$ Gas ($SF_6$ 가스 동축원통전극에서 금속이물 존재시의 전계해석)

  • 조국희;곽희로
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 1999.11a
    • /
    • pp.168-171
    • /
    • 1999
  • This paper describes the influence of conducting particle within the coaxial cylindrical electrodes gap under alternating voltage condition investigated using charge simulation method. If the conducting particles precent in the gas insulated system, they can cause decrement of breakdown voltage. Thus, three dimensions computations of electric fields and electrostatic forces have been carried out according to particle location. The results show a good agreement with those of outside country, which can offer a practical reference on the insulation design of domestic GIS.

  • PDF