• Title/Summary/Keyword: fault current interrupter

Search Result 36, Processing Time 0.033 seconds

A Study on Development of Arc Fault Circuit Interrupter Used in House Distribution Line (옥내 배전선로용 아크차단기 개발에 관한 연구)

  • Kwak, Dong-Kurl;Choi, Jung-Kyu;Park, Young-Jic;Kim, Jin-Hwan;Son, Jae-Hyun
    • Proceedings of the KIPE Conference
    • /
    • 2013.07a
    • /
    • pp.546-547
    • /
    • 2013
  • This paper proposes an arc fault circuit interrupter (AFCI) using the distorted voltage wave in electric arc faults. It perceives a voltage instantaneously at the time of voltage drop. and occurrence. It is an AFCI of the new concept which operates with high reliability. The primary reason of electric fire is arc and spark. It prevents an electric fire or an electric leakage accident with quick responsiveness. Earth Leakage Circuit Breaker(ELB), Molded_case Circuit Breaker (MCCB) or Residual Current Protective Device(RCD) can not cut off electric arc or spark to be a major factor of electrical fire. This theory will be able to intercept an arc or a spark. which occurrence with periodic. Consequently It raises a reliability and validates a practicality of RCD.

  • PDF

Development of Arc Fault Circuit Interrupter Using the Distorted Voltage Wave in Electric Arc Faults (아크사고 발생 시 전압 왜형파를 이용한 아크차단기 개발)

  • Kwak, Dong-Kurl
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.6
    • /
    • pp.876-880
    • /
    • 2013
  • The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The principal factor of the fire is electric arc or spark accompanied with such electric faults. Earth Leakage Circuit Breaker (ELB) and Molded_case Circuit Breaker (MCCB), that is, Residual Current Protective Devices (RCDs) used on low voltage distribution lines cut off earth leakage and overload, but the RCD can not cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied in low voltage distribution panel are prescribed to rated breaking time about 30[ms] (KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To improve such problems, this paper studies on an arc fault circuit interrupter (AFCI) using the distorted voltage wave in electric arc faults. The proposed voltage sensing type AFCI is an electrical fire prevention apparatus of new conception that operates a circuit breaker with sensing the instantaneous voltage drop of line voltage at electrical faults occurrence. The proposed AFCI is composed of control circuit topology using some semiconductor switching devices. Some experimental tests of the proposed AFCI confirm practicality and the validity of the analytical results.

Development of Medium Voltage $SF_6$ Interrupter for RMU ($SF_6$ 가스를 이용한 배전급 RMU용 소호부 개발)

  • Lee, B.W.;Sohn, J.M.;Seo, J.M.;Choe, J.W.
    • Proceedings of the KIEE Conference
    • /
    • 2001.05a
    • /
    • pp.301-304
    • /
    • 2001
  • This paper considers the research of the hybrid interrupter which adopts both rotating arc and thermal expansion technology. The operating principle of this device defends on rapid arc rotation due to the magnetic field created by the fault current through a coil which is mounted on contacts and also relies on the principle of thermal expansion created by arc energy in extinguishing chamber and finally causes pressure rise in expansion volume. In this research, the principle of the interrupting techniques are given and experimental results of hybrid interrupter which is developed by new technology is introduced.

  • PDF

Operational Characteristics of Flux-lock Type SFCL using Series Resonance

  • Lim, Sung-Hun;Han, Byoung-Sung;Choi, Hyo-Sang
    • Transactions on Electrical and Electronic Materials
    • /
    • v.6 no.4
    • /
    • pp.159-163
    • /
    • 2005
  • We analyzed the fault current limiting characteristics of a flux-lock type $high-T_c$ super­conducting fault current limiter (HTSC-FCL) using series resonance between capacitor for series resonance and magnetic field coil which was installed in coil 3. The capacitor for the series resonance in the flux-lock type HTSC-FCL was inserted in series with the magnetic field coil to apply enough magnetic field into HTSC element, which resulted in higher resistance of HTSC element. However, the impedance of the flux lock type HTSC-FCL has started to decrease since the current of coil 3 exceeded one of coil 2 after a fault accident. The decrease in the impedance of the FCL causes the line current to increase and, if continues, the capacitor for the series resonance to be destructed. To avoid this operation, the flux-lock type HTSC-FCL requires an additional device such as fault current interrupter or control circuit for magnetic field. From the experimental results, we investigated the parameter range where the operation as mentioned above for the designed flux-lock type HTSC-FCL using series resonance occurred.

Development of Control Algorithm and Detection of the Small Leakage Current (미소 누전전류 검출 및 차단제어기 설계)

  • 반기종;김낙교
    • The Transactions of the Korean Institute of Electrical Engineers D
    • /
    • v.53 no.3
    • /
    • pp.161-165
    • /
    • 2004
  • In this paper, we have designed the ground faults detection and interrupting controller at normal condition of AC 120v to 240v rating voltage. Ground faults in electrical network have the characteristics of low current, 60㎐ frequency to 2㎑frequency. The load condition are no load and 20A load. The trip level of the controller is 6㎃ with ground faults. The Controller algorithm is implemented using pic16c71 microprocessor.

Investigation of Network Application of the Hybrid SFCLs (복합형 초전도 한류기의 한류특성에 따른 계통 적용성 검토)

  • Choe, Won-Joon;Sim, Jung-Wook;Park, Kwon-Bae;Kim, Young-Gun;Oh, Il-Sung;Hyun, Ok-Bae
    • Proceedings of the KIEE Conference
    • /
    • 2008.10c
    • /
    • pp.223-225
    • /
    • 2008
  • In order to apply SFCLs into electric power systems, the urgent issues to be settled are as follows, such as initial installation price, operation and maintenance cost due to ac loss of superconductor and the life of cryostat, and high voltage and high current problems. We designed novel hybrid SFCLs which combine superconductor and conventional electric equipments including a vacuum interrupter, an electro-magnetic contactor and a current limiting reactor. The main purpose of the hybrid SFCL is to drastically reduce total usage of superconductor by adopting current commutation method by use of the superconductor and the fast switch. According to protective coordination and performance, we investigated two concepts of Hybrid SFCLs. First is a half cycle fault current limitation type and second is a non-half cycle fault current limitation type. We concluded that the non-half cycle fault current limitation type is batter than the other.

  • PDF

Investigation on $SF_6$ Hybrid Interrupter using Thermal Expansion and Arc Rotation Principle (자력팽창 및 아크 회전에 의한 배전급 $SF_6$ 복합소호부 개발 연구)

  • Lee, B.W.;Sohn, J.M.;Kang, J.S.;Choe, W.J.;Kim, Y.K.;Seo, J.M.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07b
    • /
    • pp.919-921
    • /
    • 2000
  • This paper considers the research of the hybrid interrupter which adopts both rotating arc and thermal expansion technology. The operating principle of this device depends on rapid arc rotation due to the magnetic field created by the fault current through a coil which is mounted on contacts and also relies on the principle of thermal expansion created by arc energy in extinguishing chamber and finally causes pressure rise in expansion volume. In this research, the principle of the interrupting techniques are given and experimental results of hybrid interrupter which is developed by new technology is introduced.

  • PDF

Arc Fault Circuit Interrupter Design using Microprocessor (마이크로프로세서를 이용한 아크결함 차단기 설계)

  • Yoon, Kwang-Ho;Ban, Gi-Jong;Lee, Hyo-Jik;Park, Byung-Suk;Nam, Moon-Hyon
    • Journal of the Institute of Electronics Engineers of Korea SC
    • /
    • v.44 no.1
    • /
    • pp.12-18
    • /
    • 2007
  • As an arc fault interrupter, the AFCI mentioned in this paper has been designed to detect and interrupt arc faults due to wire deterioration, insulation, wire damage, loose connection, and excessive mechanical damage. Since AFCI is digital and uses mechanical and electric stress, the length of interruption against overload and over-current is much shorter than the current bi-metal method. Therefore, the risk of electrical fires has been reduced.

Hybrid Superconducting Fault Current Limiters for Distribution Electric Networks (하이브리드 방식을 적용한 배전급 초전도 한류기 개발)

  • Lee, B.W.;Park, K.B.;Sim, J.;Oh, I.S.;Lim, S.W.;Kim, H.R.;Hyun, O.B.
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.102-103
    • /
    • 2007
  • In order to apply resistive superconducting fault current limiters into electric power systems, the urgent issues to be settled are as follows, such as initial installation price of SFCL, operation and maintenance cost due to ac loss of superconductor and the life of cryostat, and high voltage and high current problems. The ac loss and high cost of superconductor and cryostat system are main bottlenecks for real application. Furthermore in order to increase voltage and current ratings of SFCL, a lot of superconductor components should be connected in series and parallel which resulted in extreme high cost. Thus, in order to make practical SFCL, we designed novel hybrid SFCL which combines superconductor and conventional electric equipment including vacuum interrupter, power fuse and current limiting reactor. The main purpose of hybrid SFCL is to drastically reduce total usage of superconductor by adopting current commutation method by use of superconductor and high fast switch. Consequently, it was possible to get the satisfactory test results using this method, and further works for practical applications are in the process.

  • PDF