• Title/Summary/Keyword: dielectric recovery shock wave

Search Result 5, Processing Time 0.019 seconds

Evaluation Method II of the Small Current Breaking Performance of SF$_6$-Blown High-Voltage Gas Circuit Breakers (초고압 $SF_6$가스차단기의 소전류 차단성능 해석기술 II)

  • 송기동;이병윤;박경엽;박정후
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.50 no.8
    • /
    • pp.384-391
    • /
    • 2001
  • The insulation strength between contacts after current interruption to the transient recovery voltage i.e., the dielectric recovery strength should be estimated for the evaluation of the small capacitive current interruption capability. Many authors have used theoretical and semi-experimental approaches to evaluate the transient breakdown voltage after the current interruption. Moreover, an empirical equation, which is obtained from a series of tests, has been used to estimated the dielectric recovery strength. Un this paper, the theoretical method which is generated from the streamer theory has been applied to real circuit breakers in order to evaluated the interruption capability. The results of analysis have been compared with the test results and the reliability has been investigated.

  • PDF

Comparison of Evaluation Methods of the Small Current Breaking Performance for $SF_{6}$ Gas Circuit Breakers

  • Song, Ki-Dong;Lee, Byeong-Yoon;Park, Kyong-Yop;Park, Jung-Hoo
    • KIEE International Transaction on Electrical Machinery and Energy Conversion Systems
    • /
    • v.11B no.4
    • /
    • pp.129-136
    • /
    • 2001
  • In order to evaluate the dielectric recovery strength for GCBs, two equations have been usually utilized. One is the empirical formula obtained from a series of tests and the other is the theoretical formula obtained from the streamer theory. In this paper, both methods were applied to predict the small capacitive current interruption capability of model circuit breakers and were investigated in terms of the reliability by comparing the simulation results with test ones.

  • PDF

Experimental Study on the Recovery of Useful Minerals Using High Voltage Discharge Shock Pulse (고전압 방전 충격펄스를 이용한 유용광물 회수에 관한 실험적 연구)

  • Cho, Sangho;Jeong, Sangsun
    • Explosives and Blasting
    • /
    • v.40 no.1
    • /
    • pp.17-28
    • /
    • 2022
  • Electrical pulse disintegration(ED) is known as an efficient technology for recovering valuable resources by inducing dielectric breakdown in solids to separate mineral interfaces in ores among the crushing technologies by high voltage discharge. In this study, ED crushing experiment and mechanical crushing experiment of sulfide minerals were performed, and SEM analysis and Microfocus X-Ray CT of the crushed product were performed in order to analyze the disintegration characteristics of zinc minerals exist in the sulfide minerals by the shock wave generated in the solid by high voltage discharge.

Evaluation Method I of the Small Current Breaking Performance for SF(sub)6-Blown High-Voltage Gas Circuit Breakers (초고압 $SF_6$ 가스차단기의 소전류 차단성능 해석기술 I)

  • 송기동;이병운;박경엽;박정후
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.50 no.7
    • /
    • pp.331-337
    • /
    • 2001
  • With the increasing reliability of analysis schemes and the dramatically increased calculating speed, the computer simulation has become and indispensable process to predict the interruption capacity of circuit breakers. Generally, circuit breakers have to possess both the small current and large current interruption abilities and the circuit breaker designers need to evaluate its capacities to save the time and the expense. The analysis of small current and the large current interruption performances have been considered separately because the phenomena occurring in a interrupter are quite different. To analyze the dielectric recovery after large current interruption many physical phenomena such as heat transfer, convection and arc radiation, the nozzle ablation, the ionization of high temperature SF(sub)6 gas, the electric and themagnetic forces and so forth mush be considered. However, in the analysis of small current interruption performance only the cold gas flow analysis needs to be carried out because the capacitive current is to small that the influence from the current can be neglected. In this paper, an empirical equation which is obtained from a series of tests to estimate the dielectric recovery strength has been applied to a real circuit breaker. The results of analysis have been compared with the test results and the reliability has been investigated.

  • PDF

Investigation of Small Current Interruption Performance for New Type of Interrupting Chamber in SF$_{6}$ Gas Circuit Breaker (신차단방식 SF$_{6}$ 가스 차단기의 소전류 차단성능 연구)

  • Song, Won-Pyo;Kweon, Ki-Yeoung;Lee, Jae-Sung;Song, Ki-Dong;Kim, Maeng-Hyun;Ko, Hee-Seok
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.54 no.11
    • /
    • pp.519-526
    • /
    • 2005
  • This paper presents computer simulation results for developing new type of SF$_{6}$ Circuit Breaker in terms of cold gas flow after small current interruption. This cold gas flows down a nozzle into the chamber of a circuit breaker. There are many difficult problems in analyzing the gas flow due to complex geometry, moving boundary, shock wave and so on. When predicting the dielectric capability of a gas circuit breaker after interruption, the gas pressure and density distributions due to the cold gas must be considered in addition to the electrical field imposed across the gas. A self-coded computational fluid dynamics (CFD) program is used for the simulation of cold gas flow in order to evaluate the electrical field characteristic across open contacts and transient characteristics of insulations after small current interruption.