• 제목/요약/키워드: cooling source

검색결과 633건 처리시간 0.027초

데이터센터 냉방시스템 고효율화를 위한 국내 수열에너지 보급 제도 개선에 관한 연구 (A Study on the Improvement of the Water Source Energy Distribution Regulation for High Efficient Data Center Cooling System in Korea)

  • 조용;최종민
    • 한국지열·수열에너지학회논문집
    • /
    • 제17권3호
    • /
    • pp.21-29
    • /
    • 2021
  • In this study, the current regulation of the water source energy, one of the renewable energy, was analyzed, and the improvement plan for the high efficient data center cooling system was suggested. In the improvement plan, the design and construction guidelines of the water source energy system permit to adopt the cooling and heating system with or without heat pump. In addition, it should also include the system operated in the cooling mode only all year-round. The domestic test standards to consider the water source operating conditions should be developed. Especially, it is highly recommended that the test standards to include the system with forced cooling and free cooling modes related with the enhanced data center cooling system adopting the water source energy.

건축물 용도별 내부 발열부하에 따른 수열원, 지열원 및 하이브리드 히트펌프 시스템의 에너지 성능 비교 분석 (Comparative Analysis of Energy Performance of Hydrothermal, Geothermal Source and Hybrid Heat Pump System According to Internal Heat Load for Office, School and Smart Farm)

  • 박시훈;민준기
    • 한국지열·수열에너지학회논문집
    • /
    • 제18권3호
    • /
    • pp.19-30
    • /
    • 2022
  • In this study, comparative analysis of energy performance in Taebaek city, a test area, by applying hydrothermal, geothermal source and hybrid heat pump system to office, school and smart farms with different internal heat loads. The conclusion is as follows. In the load characteristics by use of buildings, it was found that office had a large cooling load compared to heating load, school had a large heating load compared to cooling load, and smart farm had only cooling load year-round. Performance analysis of the heat pump system in office shows that the cooling COP of the hydrothermal source is 5.12% and the heating COP is 3.22% lower based on the geothermal source, the cooling COP of the hybrid is 0.41% higher, and the heating COP is the difference in performance appeared sparsely. The performance analysis of the heat pump system in school showed that the cooling COP of the hydrothermal source was 10.44% and the heating COP 3.22% lower based on the geothermal source, and the performance difference between the hybrid cooling and heating COP was insignificant. Heat pump system performance analysis in smart farm only occurred with cooling load. Based on geothermal sources, the cooling COP of the hydrothermal source was 46% and the cooling COP of the hybrid was 19.65%, respectively.

지열히트펌프시스템의 냉방운전에 따른 성능연구 (Cooling Performance of a Ground Source Heat Pump System)

  • 이재근;정영만;구경민;황유진;장세용;김인규;진심원;이동혁
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.441-446
    • /
    • 2007
  • This present study is to evaluate the cooling performance of a water-to-refrigerant ground source heat pump system(GSHP) under actually operating condition. 1 unit is selected among 10 units of the GSHP in the building to analyze the performance. The average cooling COP of the GSHP at the part load of 64% is 8.2, overall system COP is 6.19. In the GSHP system, the cooling temperature of the condenser is lower compared to the air source heat pump system. Conclusively, the cooling performance of the GSHP is higher than the air source heat pump system by 80%.

  • PDF

대형 Community 건물의 연료전지 구동 복합열원 하이브리드 히트펌프 냉.난방 시스템 성능 해석 (The Study on the Performance of the Fuel Cell Driven Compound Source Hybrid Heat Pump Heating and Cooling System to Large Community Building)

  • 변재기;정동화;최영돈
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.82-87
    • /
    • 2007
  • In the present study, the simulation on the annual performance evaluation of a renewable energy systems with fuel cell driven compound source hybrid heat pump systems is applied to the heating and cooling of large community building. The large community building has the economical advantage to apply heat pump cooling and heating systems the long period operation. If air and ground source hybrid heat pump systems are combined, COP of the system can be increased largely. Fuel cell driven compound source hybrid heat pump system can reduced the fuel cost as well as thermal storage tank sharply.

  • PDF

물-물 수온차 히트펌프 시스템의 원수온도에 따른 성능 특성 분석 (Analysis on Cooling and Heating Performance of Water-to-Water Heat Pump System for Water Source Temperature)

  • 박태진;조용;박진훈
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2010년도 춘계학술대회 초록집
    • /
    • pp.169.2-169.2
    • /
    • 2010
  • The research assesses the performance of the water-to-water heat pump system installed in Cheongju water treatment plant for cooling and heating ventilation. In summer season monthly averaged COP is ranged from 3.85 to 4.56 according to the water source temperature, and the performance is increased as the raw water temperature is dropped. While, heating performance is increased for the high temperature water source, and the monthly averaged COP is changed from 2.92 to 3.82. The correlation of the water source temperature and the heat pump performance shows a linear tendency by the simple regression of average data. In heating, the COP of heat pump system linearly rises according to the water source temperature. In comparison, the COP in cooling linearly reduces as the raw water temperature is raised. The goodness of fit at the simple regression shows the coefficient of determination 82% in cooling, 46% in heating. The electric cost of water-to-water heat pump is reduced by 40% compared to that of air source heat pump.

  • PDF

수절환 및 냉매절환방식에 따른 지열히트펌프의 냉방특성에 관한 연구 (A Study on Cooling Characteristics of Ground Source Heat Pump with Variation of Water Switching and Refrigerant Switching Methods)

  • 차동안;권오경;박차식
    • 설비공학논문집
    • /
    • 제24권8호
    • /
    • pp.605-611
    • /
    • 2012
  • The objective of this study is to investigate the influence of the cooling performance for a water-to-water 10 RT ground source heat pump by using the water switching and refrigerant switching method. The test of water-to-water ground source heat pump was measured by varying the compressor speed, load side inlet temperature, and ground heat source side temperature. The cooling capacity and refrigerant mass flow rate of the heat pump increased with increasing ground heat source temperature. But COP of the heat pump decreased with increasing ground heat source temperature. As a result, the water switching method with counter flow, compared to a refrigerant switching method, improves the cooling capacity and COP by approximately 6~9% in average, respectively.

수열원 냉난방 동시형 히트펌프 시스템의 실외 열교환기 유량제어를 통한 성능개선에 관한 연구 (A Study on the Performance Improvement of a Simultaneous Heating and Cooling Water Source Heat Pump System by Controlling of the Refrigerant Flow Rate in an Outdoor Unit)

  • 배흥희;이동혁;이상헌;김병순;안영철
    • 설비공학논문집
    • /
    • 제25권3호
    • /
    • pp.131-136
    • /
    • 2013
  • The present study has conducted cycle design and control technology of a water source VRF heat pump system. Previously, study of a simultaneous heating and cooling in an air source VRF heat pump system has been conducted. However, performance data and design methods for simultaneous heating and cooling in a water source VRF heat pump system are limited in the literature, due to various system parameters and operating conditions. In this study, the operating characteristics and performances of a simultaneous heating and cooling heat pump system are carried out, in simultaneous operation modes. Control logics of an EEV are developed for flow rate control to the outdoor unit, and are verified. When the control logics are applied, the simultaneous cooling and heating performances are sufficiently achieved, and system COPs are increased by up to 23.4%.

공동주택에서 지열 냉난방 시스템 적용시 경제성 분석 (Economic Analsys of Cooling-Heating System Using Ground Source Heat in Multi Family Apartment)

  • 박용부;박종배;임해식;백성권
    • 한국지반환경공학회 논문집
    • /
    • 제8권3호
    • /
    • pp.11-18
    • /
    • 2007
  • 본 연구에서는 파급효과가 큰 공동주택에서 지열 냉난방 시스템의 경제성을 아파트 분양평형, 운전시간, 냉난방 및 급탕 설치형태별로 구분하여 초기 공사비 증가, 운전비 절감액, 초기 투자비 회수기간등을 산정하였다. 냉난방 및 급탕 운전시간이 많을수록 초기 공사비 증가액에 비해 운전비용 절감액이 커 초기 투자비 회수기간이 단축되었다. 전용면적이 클수록 투자회수 기간이 길었으며 냉난방 및 급탕 설치형태에서는 냉난방을 지열원, 급탕을 폐열회수한 경우가 초기 투자 회수기간이 가장 짧았다. 기존 시스템(패키지 에어콘, LNG 난방 및 급탕)에 비해 냉난방, 급탕을 모두 지열로 이용하는 경우, 냉난방은 지열, 급탕은 폐열을 이용하는 경우, 냉난방은 지열, 급탕은 LNG인 경우에 공사비가 $m^2$당 각각 약 72,000원, 66,900원, 62,300원 정도 증가하였다.

  • PDF

중앙냉난방시스템의 EMS 복합제어 효과 분석에 관한 시뮬레이션 연구 (A Simulation Study on Effect Analysis of EMS Combined Control of Central Cooling and Heating System )

  • 송재엽;안병천
    • 한국지열·수열에너지학회논문집
    • /
    • 제18권4호
    • /
    • pp.33-44
    • /
    • 2022
  • In this study, we analyze the existing heating and cooling operation method for an office-type complex building with a central heating and cooling system, and examine the effects of applying various EMS that can be applied according to the load size to save energy in the building. For this purpose, simulation analysis was performed. As a control method, reset control of chilled water, hot water, cooling water and supply air temperatures, optimal start/stop of heat source, and number of heat source control were applied according to the load size, and energy consumption was analyzed accordingly. In addition, when all of these control methods were applied, the overlapping energy saving effect was finally confirmed. As a result, it was possible to confirm the energy saving effect when EMS for reset control and heat source control were applied compared to the existing control method of the heating and cooling system, and the effect for the case of using all these control methods in combination was also confirmed.

다수의 히트펌프로 구성된 냉난방시스템에서 하절기 히트펌프의 최적운전에 관한 연구 (A Study on Optimal Operation of Summer Season Cooling System with Numbers of Heat Pumps)

  • 신관우
    • 전기학회논문지P
    • /
    • 제55권1호
    • /
    • pp.35-40
    • /
    • 2006
  • Heat-pump system has a special feature that provides heating operation in winter season and cooling operation in summer season with a single system. It also has a merit that absorbs and makes use of wastewater heat, terrestrial heat, and heat energy from the air. Because heat-pump system uses midnight electric power, it decreases power peak load and is very economical as a result. By using the property that energy source is converted to low temperature when losing the heat, high temperature energy source is used to provide heating water and low temperature energy source is used to provide cooling water simultaneously in summer season. This study made up a heat-pump system with 4 air heat sources and a water heat source and implemented the optimal operation algorithm that works with numbers of heat pumps to operate them efficiently. With the heat-pump system, we applied it to cooling and heating operation in summer season operation mode in a real building.