Cooling Performance of a Ground Source Heat Pump System

지열히트펌프시스템의 냉방운전에 따른 성능연구

  • Lee, Jae-Keun (Department of Mechanical Engineering, Pusan National University) ;
  • Jeong, Young-Man (Department of Mechanical Engineering, Pusan National University) ;
  • Koo, Kyoung-Min (Department of Mechanical Engineering, Pusan National University) ;
  • Hwang, Yu-Jin (Department of Mechanical Engineering, Pusan National University) ;
  • Jang, Se-Yong (Department of Mechanical Engineering, Pusan National University) ;
  • Kim, In-Kyu (Digital Appliance Laboratory, LG Electronics) ;
  • Jin, Sim-Won (Digital Appliance Laboratory, LG Electronics) ;
  • Lee, Dong-Hyuk (Digital Appliance Laboratory, LG Electronics)
  • Published : 2007.11.30

Abstract

This present study is to evaluate the cooling performance of a water-to-refrigerant ground source heat pump system(GSHP) under actually operating condition. 1 unit is selected among 10 units of the GSHP in the building to analyze the performance. The average cooling COP of the GSHP at the part load of 64% is 8.2, overall system COP is 6.19. In the GSHP system, the cooling temperature of the condenser is lower compared to the air source heat pump system. Conclusively, the cooling performance of the GSHP is higher than the air source heat pump system by 80%.