• Title/Summary/Keyword: circuit breaker deterioration

Search Result 9, Processing Time 0.02 seconds

A Study on the Physical Characteristics of the Low-voltage Circuit Breaker Based on the Accelerated Degradation Test (가속 열화 시험에 따른 저압용 차단기의 물리적 특성에 관한 연구)

  • Sin dong, Kang;Jae-Ho, Kim
    • Journal of the Korean Society of Safety
    • /
    • v.37 no.6
    • /
    • pp.1-8
    • /
    • 2022
  • This study analyzed the characteristics of insulation resistance and operating time based on an accelerated degradation test of a low-voltage circuit breaker. The experimental sample used a molded case circuit breaker (MCCB) and an earth leakage circuit breaker (ELCB). After measuring the insulation resistance of the circuit breakers, the leakage current was affected by an external rather than an internal structure. Furthermore, the insulation resistance of the circuit breakers with accelerated degradation was measured using a Megger insulation tester. In the accelerated degradation test, aging times of five, ten, 15, and 20 years were applied according to a temperature derived using the Arrhenius equation. Circuit breakers with an equivalent life of ten, 15, and 20 years had increased insulation resistance compared to those with less degradation time. In particular, the circuit breaker with an equivalent life of ten years had the highest insulation resistance. Component analysis of the circuit breaker manufactured through an accelerated degradation test confirmed that the timing of the increase in insulation resistance and the time of additive loss were the same. Finally, after analyzing the operating time of the circuit breakers with degradation, it was confirmed that the MCCB did not change, but the ELCB breaker failed.

A Study on the Evaluation of Reliability of the Vacuum Circuit Breaker for the Electrical Fire (전기화재에 따른 진공차단기의 건전성 평가)

  • Choi, Hong-Kyoo;Park, Joon-Yeol
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.7
    • /
    • pp.24-28
    • /
    • 2013
  • Fire-hited electrical equipment has possibility of deterioration. So its replacement is essential in terms of safety. However, the economic burden is increased. Therefore, the replacement or re-use of it is to be determined by tests. But the research of Integrity Assessment on Fire-hited electrical equipments is very rare. In this paper, we tested to determine the replacement or re-use of Fire-hited vacuum circuit breaker. And provided the data for the integrity assessment through the analysis of its deterioration.

Insulation Deterioration of AC/DC Section Insulators for Electric Railroad Catenary. (전기철도 교/직 절연구분장치의 절연열화 현상)

  • 최규형
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.52 no.1
    • /
    • pp.16-22
    • /
    • 2003
  • While passing through the AC/DC section insulators installed at electric railroad catenary, some electric trains undergo mis-operation of main circuit breaker after AC/DC change-over operation. This paper provides insulation resistance measurements of AC/DC section insulators, which confirm the insulation levels of section insulators are below the standard of insulators. The insulation deterioration and pantograph arrangement on the electric train can produce voltage impression on section insulator which induces mis-operation of main circuit breaker To mitigate the insulation deterioration of the section insulator installed at underground railroads, the section insulators have been cleaned periodically, but section insulator structure should be modified to make the section insulator performance perfect. Based on the above analysis, effective modification method of AC/DC section insulator is provided.

Development of the Controlled Switching Device for a Cirrcuit Breaker

  • Kim, Ik-Mo;Kim, Myung-Chan;Choi, Young-Chan;Ryu, Sung-Sic;Kim, Dong-Hyun
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 2004.08a
    • /
    • pp.558-560
    • /
    • 2004
  • Studies on the controlled switching method have been done to prevent the power system surges which cause the insulation deterioration and electro magnetic compatibility (EMC) problems during closing and opening of a circuit breaker. The controlled switching method controls the closing and tripping time in coincidence with the voltage or current to suppress switching surge. It is used to switch condenser bank, no load transformer, and shunt reactor. In this study, basic concept of the controlled switching is introduced, and also the test is performed to find parameters of the controlled switching in a 24kV vacuum circuit. And then, the control device hardware using TMS320C31 DSP has been designed and manufactured. It has been found that the application of IT technology to a circuit breaker is very effective to depress the switching surge.

  • PDF

Thermal Runaway Prevention of MOV and Safety Improvement of Power Line System and Internal Electronic Device Circuit Using a Phosphorous Switching Module (인청동 스위칭 모듈을 이용한 전력계통 및 전자기기 내부회로의 MOV 열폭주 방지와 안전성 개선)

  • Kim, Ju-Chul;Choi, Gyung-Ray;Lee, Sang-Joong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.9
    • /
    • pp.75-79
    • /
    • 2011
  • The MOV(Metal Oxide Varistor), a voltage limiting element, has been installed in the SPD(Surge Protective Device) or inside the internal circuit of an electronic appliance for protection of the electric power system and electronic device against electrical surge. Such an MOV is exposed, however, to the risk of the thermal runaway resulting from excessive voltage and deterioration. In this paper, a reciprocal action has been tested and analyzed using a phosphorus bronze switching module and the low-temperature solder. And a short current break characteristic test linked with the circuit breaker has been performed to limit the inrush current when the MOV breaks down. It has been proven that the phosphorus bronze switching module installed inside the internal circuit can improve the safety of the power line system and the electronic device.

Identification of Tracking Conduct Wiring Using Neural Networks (인공신경망을 이용한 전기배선의 트랙킹 식별에 관한 연구)

  • 최태원;이오걸;김이곤
    • Journal of the Korean Institute of Intelligent Systems
    • /
    • v.8 no.2
    • /
    • pp.1-8
    • /
    • 1998
  • In this paper, a method which cna detect tracking caused by the insulation deterioration of conduct wiring, is proposed. To investigate it, we analyzed the harmonics of each load current waveform and those of tracking current waveform with FFT. The computer which take experiment data is learned by neural network algorithm, which has recently been used for the load recognition. The proposed metod in our study can be applied to the development of several measuring equipments such as hotline insulation tester, cna earch tester for the detection of tracking under hot-line state, Furthermore, it can substitutes molded case circuit breaker, fuse, and so on.

  • PDF

A Study on the Reduction Method and the Analysis of VCB Switching Surge for High Voltage Induction Motor (고압전동식용 진단차식기의 스위칭써지 해석 및 연구)

  • 이은웅;김종겸;김택수;이성철
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.43 no.5
    • /
    • pp.761-769
    • /
    • 1994
  • VCB (Vacuum Circuit Breaker), with the strong arc extinction capability in switching the source of an induction motor, occurs the severe switching surge voltage which can cause the breakdown or the deterioration of motor insulation. Therefore, a method which reduces surge voltage across motor windings is necessary. So, it is analyzed that fast-rise-time surges resulting from VCB switching operations give rise to severe voltage stress on turn insulation. Additionally, the switching surge simulation algorithms using EMTP are developed, and C, R values of surge suppressor minimizing the steep-fronted stress in winding insulation surges are calculated.

A Study for the Fire Analysis and Igniting Cause of Freezing Protection Heating Cables (동파방지열선 화재 흔적분석과 발화원인 연구)

  • Lee, Jung Il;Ha, Kag Cheon
    • Journal of the Korean Society of Safety
    • /
    • v.33 no.3
    • /
    • pp.15-20
    • /
    • 2018
  • There have been a number of major fatal fire accidents in Korea recently. The number of fires in 2017 were 44,178, which is not only increasing number of fires but also increasing in casualties. Particularly, the fire at Jecheon Sports Center, which suffered many casualties, is expected to have a huge impact. The cause of the fire has not been determined yet, but heat waves on the ceiling have also been pointed out. As such, the copper heating waves, which are used as a preventive measure against damage of pipes due to freezing of pipes, etc., always have a fire hazard. To determine the possibility of a flame-resistant heated fire, a positive electric cable product was used to artificially ignite and analyze the results. In case of a short circuit, the external covering of the positive electric cable is damaged, but not short circuit unless the heating material surrounding the wire is damaged. Due to the characteristics of heating cable for preventing copper waves, the chances of insulation becoming more severe due to moisture and temperature changes are higher than normal wires. If the internal heating system is carbonized by insulating deterioration without damage to the outer coating, it is likely to cause trekking, to form a winding loop in the heating materials, and to cause short circuit in the heated materials. For the positive temperature line, if the middle is shorted, the current continues to flow to the short circuit unless the breaker disconnects. Consequently, a heated fire that does not cut off the power immediately may leave multiple marks or cuts.

Electro-thermal analysis of contacts and connections in VCB under high electric current by finite element methods (유한요소법에 의한 VCB 접속부의 대전류에 대한 전열해석)

  • Kang, Woo-Jong;Huh, Hoon;Kang, Kyeong-Rok
    • Transactions of the Korean Society of Mechanical Engineers A
    • /
    • v.22 no.4
    • /
    • pp.715-722
    • /
    • 1998
  • A large electric system of a vacuum circuit breaker(VCB) has been studied for the electro-thermal analysis by finite element methods. Since the heat generation in VCB causes not only energy loss but deterioration of the VCB system with oxidization of parts, the overheating of the system must be prevented. For the analysis, a finite element formulation is derived for both electric analysis and thermal analysis that are coupled together. Two sets of formulations are uncoupled after finite dimensional approximation. First, the electric potential is obtained for the entire field and scaled to the given electric current. The electric field obtained is then used to calculate the heat generation in the VCB system including contacts and connections for the calculation of the temperature distribution in the entire domain. The finite element analysis is carried out to study the effect of shapes and locations of contacts and connections. From the results, the existing VCB has been modified to enhance its capacity with reduction of heat generation and temperature elevation.