• Title/Summary/Keyword: cast-resin transformer

Search Result 43, Processing Time 0.023 seconds

The Temperature Distribution Analysis of Mold transformer (100kVA 주상용 몰드 변압기의 온도분포 해석)

  • Cho, Han-Goo;Lee, Un-Yong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.05b
    • /
    • pp.125-129
    • /
    • 2004
  • The mold transformers have been widely used in underground substations in large building and have some advantages in comparison to oil-transformer, that is low fire risk, excellent environmental compatibility, compact size and high reliability. In addition, the application of mold transformer for outdoor is possible due to development of epoxy resin. The mold transformer generally has cooling duct between low voltage coil and high voltage coil. A mold transformer made by one body molding method has been developed for small size and low loss, but it needs some cooling method because heat radiation between each winding is difficult. The life of transformer is significantly dependent on the thermal behavior in windings. Many transformer designers have calculated temperature distribution and hot spot point by FEM(finite element method) to analyze winding temperature rise. In this paper, the temperature distribution and thermal stress analysis of 100kVA pole cast resin transformer for power distribution are investigated by FEM program.

  • PDF

The analysis of the single transformer by using F.E.M (F.E.M.을 이용한 단상 변압기의 전자력 해석)

  • Lee, Hyun-Jin;Huh, Chang-Su;Jeong, Jung-Il;Cho, Han-Goo;Park, Yeong-Doo
    • Proceedings of the KIEE Conference
    • /
    • 2001.07b
    • /
    • pp.855-858
    • /
    • 2001
  • The single transformer appeared the electro-magnetic force must be constructed to support it. it must construct the single transformer to supporting the electro-magnetic force appeared by the cut-off current. the problem is that the electro-magnetic occurs the modification of the single transformer and an serious accident. In the case of the molding-transformer, the part of the molding cast used in the construction occurs the crack, because of the strong force. therefore, in this paper, the molding material used in the molding-transformer is settled by comparing the results from commercial soft ware of F.E.M and a out-equipment circuit.

  • PDF

The Temperature Distribution and Thermal Stress Analysis of Mold transformer (주상용 몰드변압기의 온도분포와 열응력 해석)

  • 조한구;이운용;한세원
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.387-390
    • /
    • 2000
  • The life of transformer is significantly dependent on the thermal behavior in windings. To analyse winding temperature rise, many transformer designer have calculated temperature distribution and hot spot point by finite element method(FEM). Recently, numerical analyses of transformer are studied for optimum design, that is electric field analysis, magnetic field, potential vibration, thermal distribution and thermal stress. Therefore design time and design cost are decreased by numerical analysis. In this paper, the temperature distribution and thermal stress analysis of 50kVA pole cast resin transformer for power distribution are investigated by FEM program. The temperature change according to load rates of transformer also have been investigated. We have carried out temperature rise test and test results are compared with simulation data.

  • PDF

Design and Fabrication of Rogowski-type Partial Discharge Sensor for Insulation Diagnosis of Cast-Resin Transformers (몰드 변압기의 절연 진단을 위한 로고우스키형 부분방전 센서의 설계 및 제작)

  • Lee, Gyeong-Yeol;Kim, Sung-Wook;Kil, Gyung-Suk
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.35 no.6
    • /
    • pp.594-602
    • /
    • 2022
  • Cast-resin transformers are widely installed in various electrical power systems because of their low operating cost and low influence on external environmental factors. However, when they have an internal defect during the manufacturing process or operation, a partial discharge (PD) occurs, and eventually destroys the insulation. In this paper, a Rogowski-type PD sensor was studied to replace commercial PD sensors used for the insulation diagnosis of power apparatus. The proposed PD sensor was manufactured with four different types of PCB-based winding structures, and it was analyzed in terms of the detection characteristics for standard calibration pulses and the changes of the output voltage according to the distance. The output increased linearly in accordance with the applied discharge amount. It was confirmed that the hexagon structure sensor had the highest sensitivity, because the winding cross-sectional area of the sensor was larger than others. In addition, as the distance from the defect increased, the output voltage of the sensors decreased by 7.32% on average. It was also confirmed that the attenuation rate according to the distance decreased as the input discharge amount increased. For the application of this new type sensor, PD electrode system was designed to simulate the void defect. Waveforms and PRPD patterns measured by the proposed PD sensors at DIV and 120% of DIV were the same as the results measured by MPD 600 based on IEC 60270. The proposed PD sensors can be installed on the inner wall of the transformer tank by coating its surfaces with a non-conductive material; therefore, it is possible to detect internal defects more effectively at a closer distance from the defect than the conventional sensors.

Identification of Void Diameters for Cast-Resin Transformers (몰드변압기의 보이드 결함 크기 판별)

  • Jeong, Gi-woo;Kim, Wook-sung
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • 2022.10a
    • /
    • pp.570-573
    • /
    • 2022
  • This paper presents the identification of void diameters for a cast-resin transformer using an artificial neural network (ANN) model. A PD signal was measured by the Rogowski coil sensor which has the planar and thin structures fabricated on a printed circuit board (PCB), and the PD electrode system was fabricated to simulate a PD defect by a void. In addition, void samples with different diameters were fabricated by injecting air in a cylindrical aluminum frame using a syringe during the epoxy curing process. To identify the diameter of void defects, PD characteristics such as the discharge magnitude, pulse count, and phase angle were extracted and back propagation algorithm (BPA) was designed using virtual instrument (VI) based on the Labview program. From the experimental results, the BPA algorithm proposed in this paper has over 90% accurate rate to identify the diameter of void defects and is expected to use reference data of maintenance and replacement of insulation for cast-resin transformers in the on-site PD measurement.

  • PDF

A Surge Voltage Distribution Analysis of 2MVA Cast Resin Transformer Winding with FEM Simulation (FEM 시뮬레이션을 이용한 2MVA 몰드변압기 권선간 써지전압 분배 해석 기법 연구)

  • Jang, Hyeong-Taek;Shin, Pan-Seok
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.5
    • /
    • pp.15-21
    • /
    • 2011
  • This paper presents an analyzing method of the capacitance of the power transformer for initial voltage distribution and insulation design. When a high incoming surge voltage is accidently occurred in windings of transformer, it does not distribute equally in the windings. This phenomenon makes electric field concentration and the insulating material could be break. Initial voltage distribute mostly depends on capacitances between winding to winding or winding to core in the transformer. If the C network can be structuralized into the equivalent circuit model and be calculated each capacitance element value by circuit analysis and FEM(Finite Element Method) simulation program, the transformer designer could know the place where the structure is to be modified or the insulation to be reinforced. This method quickly provides the data of the voltage distribution in each winding to the designer.

Degradation Properties of Epoxy Resin Used in Indoor (옥내용 에폭시 수지의 열화 특성)

  • 남기동;정중일;연복희;허창수;박영두
    • Proceedings of the Korean Institute of Navigation and Port Research Conference
    • /
    • 2000.11a
    • /
    • pp.57-60
    • /
    • 2000
  • In this paper, study on the properties of the thermal degradated epoxy resin which is used in indoor insulation apparatus is performed to investigate the problems of the decreasing insulation characteristics and crack in the indoor insulation apparatus. As a parameter of variation, SEM, contact angle, surface resistivity, relative dielectric constant and weight loss are measured. As the results of the above measurements, the contact angle and surface resistivity of the epoxy resin has increased to 200$^{\circ}C$ in but at the above 200$^{\circ}C$ the values have decreased. The relative dielectric constants the thermal treated samples have increased on with the temperature increase. We find the volatile components of the epoxy resin compound has disappeared during thermal degradation by SEM. The insulation properties of the epoxy resin have increased by the 200$^{\circ}C$ but decreased in the above 200$^{\circ}C$.

  • PDF

Degradation Properties of Epoxy Resin Used in Indoor (옥내용 에폭시 수지의 열화 특성)

  • 남기동;정중일;연복희;허창수;박영두
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.57-60
    • /
    • 2000
  • In this paper, study on the properties of the thermal degradated epoxy resin which is used in indoor insulation apparatus is performed to investigate the problems of the decreasing insulation characteristics and crack in the indoor insulation apparatus. As a parameter of variation, SEM, contact angle, surface resistivity, relative dielectric constant and weight loss are measured. As the results of the above measurements, the contact angle and surface resistivity of the epoxy resin has increased to 200$^{\circ}C$ in but at the above 200$^{\circ}C$ the values have decreased. The relative dielectric constants the thermal treated samples have increased on with the temperature increase. We find the volatile components of the epoxy resin compound has disappeared during thermal degradation by SEM. The insulation properties of the epoxy resin have increased by the 200$^{\circ}C$ but decreased in the above 200$^{\circ}C$.

  • PDF

Distribution Characteristics of AE Signals in Insulation Deterioration and AE Noise in Cast Resin transformer (절연물의 열화에 의한 AE신호와 변압기 외함의 AE노이즈 분포)

  • Lee, Sang-Woo;Kim, In-Sik;Kim, Lee-Kook;Park, Won-Zoo;Lee, Kwang-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1865-1867
    • /
    • 2002
  • In this paper, frequency spectra of AE signals detected from respective the insulation deterioration were analysed to under ac high-voltage application using epoxy resin sample and insulation oil. Also, frequency spectra of AE signals generated from the load currents in the actual operating transformer of 500[kVA] under distribution system of 22.9[kVJ] were also analysed to distinguish the AE signals due to void discharges from the magnetic circuit noises in transformer. As the experimental results, we could distinguish the AE signals whether those signals were caused due to the void discharges or due to the magnetic circuit noises by analyzing the frequency spectrum of AE signals.

  • PDF

The Temperature Distribution and Thermal Stress Analysis of Pole Mold transformer (주상용 몰드변압기의 온도분포와 열응력 해석)

  • 조한구;이운용;한세원;김석수
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.14 no.4
    • /
    • pp.297-301
    • /
    • 2001
  • In this paper, the temperature distribution and thermal stress analysis of 50kVA pole cast resin transformer for power distribution are investigated by FEM program. The one body molding model (Model 1) and air duct model (Model 2) are designed and their temperature distribution are analysed. The temperature rise value is about 105.5 deg in the model 1 and 65.28 de in the model 2. The temperature change of secondary winding is more than primary winding according to load ratio. The concentration part of Von Mises Stress occurs at interface between glass fiber and epoxy.

  • PDF