The Temperature Distribution and Thermal Stress Analysis of Pole Mold transformer

주상용 몰드변압기의 온도분포와 열응력 해석

  • 조한구 (한국전기연구원 전력기술연구단) ;
  • 이운용 (한국전기연구원 전력기술연구단) ;
  • 한세원 (한국전기연구원 전력기술연구단) ;
  • 김석수 (한국전기연구원 전력기술연구단)
  • Published : 2001.04.01

Abstract

In this paper, the temperature distribution and thermal stress analysis of 50kVA pole cast resin transformer for power distribution are investigated by FEM program. The one body molding model (Model 1) and air duct model (Model 2) are designed and their temperature distribution are analysed. The temperature rise value is about 105.5 deg in the model 1 and 65.28 de in the model 2. The temperature change of secondary winding is more than primary winding according to load ratio. The concentration part of Von Mises Stress occurs at interface between glass fiber and epoxy.

Keywords

References

  1. Takaoka Review v.43 no.4 Application Technology of Molded Products in the Field Takashi Hasegawa
  2. IEEE Trans. Power Delv. v.7 no.2 An Investigation of The Temperature Distribution in Cast Resin Transformer Windings Linden W. Pierce
  3. IEEE Trans. Power Delv. v.9 no.2 Predicting Hottest Spot Temperatures in Ventilated Dry Type Transformer Windings Linden W. Pierce
  4. 전기전자재료학회지 v.6 no.2 자동수렴성을 갖는 반도체 유한요소 해석프로그램 개발 최경
  5. 전기전자재료학회지 v.3 no.2 에폭시 수지의 경화형태와 전기절연특성과의 연관성 김태성(외 2인)
  6. Electric Machines and Power Systems v.20 Prevision of The Thermal Behavior of Dry Type Cast Resin Transformers A. Fernandes-Costa(et. al.)
  7. Dry Type Power Transformers IEC 726
  8. 재료역학 오세일
  9. 전기전자재료학회지 v.8 no.2 유리섬유/에폭시 복합절연재료의 계면접착력 개선에 관한 연구 이종호(외 2인)