• 제목/요약/키워드: Wilson plot method

검색결과 13건 처리시간 0.018초

Wilson plot법을 이용한 Plate & Shell 열교환기의 단상유동 열전달 특성에 관한 실험적 연구 (Experimental Study on Heat Transfer Characteristics for Single-phase Flow in Plate & Shell Heat Exchangers by Using Wilson Plot Method)

  • 서무교;김영수;이상경
    • 동력기계공학회지
    • /
    • 제3권4호
    • /
    • pp.22-27
    • /
    • 1999
  • Single phase heat transfer coefficients were measured for turbulent water flow in a plate & shell heat exchangers by using Wilson plot method. An experiment for counterflow heat exchange between the plate and shell was performed. The shell side heat transfer resistance was varied and the overall heat transfer coefficients were measured. The single-phase heat transfer coefficients in a plate side were obtained by Wilson plot method. Single-phase heat transfer correlations based on projected heat transfer area have been proposed for a plate & shell heat exchanger.

  • PDF

Wilson Plot을 이용한 만액식 증발기의 열전달계수 측정 (Measurement of Heat Transfer Coefficient in a Flooded Evaporator through Wilson Plot Method)

  • 윤필현;강용태;정진희
    • 설비공학논문집
    • /
    • 제16권8호
    • /
    • pp.698-706
    • /
    • 2004
  • Heat transfer coefficients of enhanced tubes in a flooded evaporator are measured through Wilson Plot method. And the correlations are proposed to design a flooded evaporators. Overall heat transfer coefficients are composed of the heat transfer coefficients both inside and outside tubes. Usually the experiments have been conducted separately. But there have been many difficulties like setting up the equipments and measuring the wall temperature. Wilson Plot method makes it possible to measure the separated transfer coefficients at the same equipment through experimental skills. So the cost and time can be reduced. And the results are reliable enough to use for design. Heat transfer coefficients inside the tube were able to be correlated uniquely in spite of various outside conditions. Boiling heat transfer of R134a is more dependent on the saturation temperature and much higher than that of R123.

Plate and Shell 열교환기의 단상유동 열전달 및 압력강하 특성에 관한 실험적 연구 (Experimental Study on Heat Transfer and Pressure Drop Characteristics for Single-Phase Flow in Plate and Shell Heat Exchangers.)

  • 서무교;김영수
    • 설비공학논문집
    • /
    • 제12권4호
    • /
    • pp.422-429
    • /
    • 2000
  • Plate and shell heat exchanger(P&SHE) is widely applied as evaporators or condensers in the refrigeration and air conditioning systems for their high efficiency and compactness. In order to set up the database for the design of the P&SHE, heat transfer and pressure drop characteristics for single phase flow of water in a plate & shell heat exchanger are experimentally investigated in this study. Single phase heat transfer coefficients were measured for turbulent water flow in a plate and shell heat exchangers by Wilson plot method. The shell side heat transfer resistance was varied and the overall heat transfer coefficients were measured. The single-phase heat transfer coefficients in a plate side were obtained by Wilson plot method. Single-phase heat transfer correlations based on projected heat transfer area and friction factor correlations have been proposed for single phase flow in a plate and shell heat exchanger.

  • PDF

R22 대체냉매의 수평원관내 흐름비등 열전달 특성 (Flow Boiling Heat Transfer Characteristics of R22 Alternative Refrigerants in a Horizontal Smooth Tube)

  • 한재웅;김신종;정동수;김영일
    • 설비공학논문집
    • /
    • 제13권4호
    • /
    • pp.242-251
    • /
    • 2001
  • Flow boiling heat transfer coefficients (HTCs) of R22, R134a, R407C, and R410A were measured for a horizontal plain tube. The test section was made of a copper tube of 8.8mm inner diameter and 1000mm length respectively. The refrigerant was heated by passing hot water through an annulus surrounding the test section. All tests were performed at a fixed refrigerant saturation temperature of $5^{\circ}C$ with mass fluxes of 100~300 kg/$m^2$,/TEX>s. HTCs were measured by two methods: the direct wall temperature measurement method and the indirect Wilson plot method. Experimental results showed that the Wilson plot method was affected greatly by the external test conditions and yielded inconsistent results. For the mass flux of 100kg/$m^2$,/TEX>s, HTCs were almost constant regardless of the quality for a given refrigerant HTCs of R134a and R407C were similar to those of R22 while those of R410A were 60% higher than those of R22. For the mass fluxes of 200 and 300kg/$m^2$,/TEX>s, HTCs of R407C were almost the same as those of R22, while HTCs of R134a and R410A were 12-13% and 20~23% higher than those of R22 respectively. For pure refrigerant, Shah\`s correlation yielded a good agreement with the measured data both qualitatively and quantitatively.

  • PDF

대체냉매 관내 열전달특성 시험을 위한 동심이중원관의 환상유로의 열전달계수 (Heat Transfer Coefficients of Concentric Annuli for Testing Heat Transfer Characteristics of Alternative Refrigerants in Tubes)

  • 김만회
    • 한국수소및신에너지학회논문집
    • /
    • 제32권1호
    • /
    • pp.63-67
    • /
    • 2021
  • Accurate measurements of the heat transfer coefficients of concentric annular space for the test section is important to measure the tube-side heat transfer coefficients of working fluids. This paper presents the annular side heat transfer coefficients of concentric annuli with variation of tube diameter ratios using Wilson plot method. The test facility has a straight, horizontal test section with an active length of 3.0 m. Inner/outer diameters of test tubes are 7.0/7.5 and 8.0/8.56 mm, respectively. An outer diameter of annulus side is 16.0 mm. The test results show that convective heat transfer coefficients in annuli increase with annular diameter ratio. The correlations for convective heat transfer coefficients in annuli are also developed.

대구경 타원관을 적용한 건조기용 핀-관 열교환기의 성능특성 (Performance Characteristics of Fin-Tube Heat Exchanger having Large Diameter Oval Tube for Dryer)

  • 배경진;차동안;권오경
    • 설비공학논문집
    • /
    • 제27권1호
    • /
    • pp.8-13
    • /
    • 2015
  • The objective of this paper is to provide design data of fin-tube heat exchanger which have a large diameter oval tube for dryer application. In this study, the heat transfer and pressure drop performance characteristics of the fin-tube heat exchanger were compared with Dittus-Boelter and a new correlation equation using Wilson plot method. The simulation results based on section by section method were compared with experimental results. These results showed that a new correlation equation using Wilson plot method provided better prediction, about 3 to 12%, than the Dittus-Boelter equation, from the experiment comparison. Also, the pressure drop of simulation results showed much more deviation with the experimental results.

자동차용 에어컨 응축기의 설계기술 개발 (Development of design technique for automotive condenser)

  • 조영두;한창섭;유성연
    • 설비공학논문집
    • /
    • 제11권1호
    • /
    • pp.10-17
    • /
    • 1999
  • The present work presents condensation heat transfer and pressure drop data for the flow of R-12 in flat extruded aluminum tubes with small hydraulic diameters. The tube outside dimensions are $18mm(width){\times}1.7mm(height)$. Three types of internal geometry with the same outside dimensions are tested : sample 1 (7 tube holes), sample 2 (13 tube holes) and sample 3 (7 tube holes, micro-fin). The overall heat transfer coefficient is obtained for air-to-refrigerant heat transfer, and the Wilson plot method is used to determine the heat transfer coefficient for refrigerant flow. The sample 2 and sample 3 show significantly higher performance than sample 1. The heat transfer rates for the sample 2 and sample 3 are 9% and 12% higher, respectively, than sample 1. The friction factors for the sample 2 and sample 3 are 11.9% and 2.4% higher, respectively, than sample 1.

  • PDF

선박용 중속엔진 오일냉각용 판형쿨러의 전열성능에 관한 연구 (A Study on Thermal Performance of Plate Cooler for Cooling Medium Speed Engine Lubricant Oil)

  • 박재홍
    • 한국응용과학기술학회지
    • /
    • 제37권1호
    • /
    • pp.83-90
    • /
    • 2020
  • 판형 열교환기는 1920년대부터 본격적으로 상업화되었으며, 이후 판형 열교환기의 기본 컨셉은 지금까지도 거의 변화가 없었지만 고온, 고압 그리고 대용량 열교환에 적용되기 위해 설계 및 제작 방법들이 혁신적으로 발전하여 지금에 이르게 되었다. 판형 열교환기의 개발 트렌드는 전열 효율이 좋으면서 압력강하가 낮고 또한 유체 분배가 잘되는 전열판의 개발과 일치한다. 본 연구에서는 이러한 트렌드를 만족시키는 선박용 중속엔진 오일 냉각용 판형 쿨러 개발과 관련된 주요 과정들을 소개하고, 또한 개발된 판형 오일쿨러의 전열성능을 실험적으로 분석하여 이에 대한 결과를 제공하고자 한다. 본 연구에서 판형 쿨러는 구조적 특징으로 인해 직접 판벽 온도를 측정할 수 없어 수정된 Wilson Plot 방법을 응용하여 열전달계수를 구하였다. 오일-물 실험 전에 물-물 실험을 통해 우선 물측의 열전달계수와 압력강하량을 구하였고, 그 결과를 바탕으로 오일측의 열전달계수를 구하였다. 양측 모두 유량 증가에 따라 열전달 성능은 증가하였지만, 압력강하량도 동시에 증가하였다. 그리고 실험을 통해 본 연구에서 개발된 판형 오일쿨러가 개발목표치를 성공적으로 달성하였음을 확인할 수 있었다.

건조기용 타원관 대구경 핀-관 열교환기의 성능특성 (Performance Characteristic of Large Diameter Oval Finned-Tube Heat Exchanger for Dryer)

  • 배경진;차동안;권오경
    • 동력기계공학회지
    • /
    • 제18권5호
    • /
    • pp.22-27
    • /
    • 2014
  • The objectives of this paper are to obtain an empirical equations regarding the correlations between heat transfer and pressure drop of oval fin-tube heat exchanger having large diameter using wilson plot method. It was difficult to find any recommendable heat transfer and friction factor correlation available for our large diameter experimental cases. Overall heat transfer coefficients are composed of the heat transfer coefficients both inside and outside tubes. The resulting empirical correlations for the Nui and f-factor are given as $Nu_i=0.0146Re^{0.809}Pr^{0.3}$ and $f=4.366Re^{-0.64}$, respectively. The empirical correlations of the Nui and f-factors were developed for the large diameter oval finned-tube heat exchanger as a function of the Reynolds number. As the EG(Ethylene glycol) and air flow rate increases, the heat transfer rate and pressure drop is increased largely.