Measurement of Heat Transfer Coefficient in a Flooded Evaporator through Wilson Plot Method

Wilson Plot을 이용한 만액식 증발기의 열전달계수 측정

  • Published : 2004.08.01

Abstract

Heat transfer coefficients of enhanced tubes in a flooded evaporator are measured through Wilson Plot method. And the correlations are proposed to design a flooded evaporators. Overall heat transfer coefficients are composed of the heat transfer coefficients both inside and outside tubes. Usually the experiments have been conducted separately. But there have been many difficulties like setting up the equipments and measuring the wall temperature. Wilson Plot method makes it possible to measure the separated transfer coefficients at the same equipment through experimental skills. So the cost and time can be reduced. And the results are reliable enough to use for design. Heat transfer coefficients inside the tube were able to be correlated uniquely in spite of various outside conditions. Boiling heat transfer of R134a is more dependent on the saturation temperature and much higher than that of R123.

Keywords

References

  1. Trans. Am. Soc. Mech. Engrs. v.37 A basis for rational design of heat transfer apparatus Wilson,E.E.
  2. Heat Transfer Engineering v.22 no.2 A comprehensive study of modified Wilson Plot technique to determine the heat transfer coefficient during condensation of steam and R-134a over single horizontal plain and finned tubes Kumar,R.;Varma,H.K.;Agrawal,K.N.;Mohanty,B. https://doi.org/10.1080/014576301462218
  3. Fluid Mechanics White,F.M.
  4. VDI Forschungsheft Laws of Flow in Rough Pipes Nikuradse,J.
  5. International Journal of Heat Mass Transfer v.6 Heat and momentum transfer in smooth and rough tubes at various Prandtl number Dipprey,D.F.;Sabersky,R.H. https://doi.org/10.1016/0017-9310(63)90097-8
  6. Principles of Enhanced Heat Transfer Webb,R.
  7. Int. J. Heat Mass Transfer v.35 no.8 Necleate pool boiling data for five refrigerants on plain, Integral-fin and enhanced tube geometries Webb,R.;Pais,C. https://doi.org/10.1016/0017-9310(92)90192-U
  8. Korean J. Air-Conditioning and Refrigeration v.11 no.6 Pool boiling performance of enhanced tubes at a flooded evaporator of turbo chiller Kim,T.H.;Kim,N.H.