• Title/Summary/Keyword: Two-stage absorption

Search Result 82, Processing Time 0.02 seconds

Simulation of a two-stage absorption heat pump cycle using treated sewage (하수처리수 이용 흡수식 열펌프 사이클의 시뮬레이션)

  • 이용화;신현준;최국광
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.3
    • /
    • pp.422-430
    • /
    • 1999
  • This paper concerns the study of a two-stage absorption heat pump cycle to utilize treated sewage. This two-stage cycle consists of coupling double-effect with parallel or series flow type and single effect cycle so that the first stage absorber and condenser produces hot water to evaporate refrigerant in the evaporator of the second stage. The effects of operating variables such as absorber temperature on the coefficient of performance have been studied for two-stage absorption heat pump cycle. The working fluid is lithium bromide and water solution. The efficiency of the two-stage absorption heat pump cycle has been studied and simulation results show that higher coefficient of performance could be obtained for the first stage with parallel flow type. The optimum ratio of solution distribution can be shown by considering the COP, the crystallization of solution and the generator temperature.

  • PDF

Heating and Cooling System using the Sewage Source Absorption Refrigeration and Heat Pump Cycle (하수열을 이용한 냉난방시스템에 관한 연구)

  • Lee, Yong-Hwa;Shin, Hyun-Joon;Yoon, Hee-Chul;Park, Hyun-Gun
    • Journal of the Korean Solar Energy Society
    • /
    • v.27 no.4
    • /
    • pp.19-26
    • /
    • 2007
  • This paper concerns the study of absorption refrigeration and heat pump cycle to use sewage. Simulation analysis on the double-effect absorption refrigeration cycle with parallel and two-stage heat pump cycle has been performed. The working fluid is Lithium Bromide and water solution. The absorption refrigeration cycle use sewage as a cooling water for the absorber and condenser, and absorption refrigeration cycle does that as a chilled water for the evaporator of the first stage cycle. And the two-stage cycle consists of coupling double-effect with parallel and single effect cycle so that the first stage absorber and condenser produces heating water to evaporate refrigerant in the evaporator of the second stage. The effects of operating variables such as a absorber temperature on the coefficient of performance have been studied for absorption refrigeration and heat pump cycle.

Performance and Parameter Comparison between single stage and Two-Stage Compression/Absorption Heat Pump System (단단 및 2단 압축/흡수 히트펌스시스템의 성능 및 중요인자비교 분석)

  • Tian, Huaizhang;Park, Seong-Ryong
    • Proceedings of the SAREK Conference
    • /
    • 2005.11a
    • /
    • pp.451-456
    • /
    • 2005
  • The mathematical model for the heat exchangers of absorber and desorber is made in the elementary control volume method and the thermodynamic properties of working fluid. water/ammonia mixture. are calculated by some fundamental subroutines in RefProp 7.0 and flash subroutines made by authors The simulation results show that two-stage cycle has higher COP than single stage if temperature lift is high: the performance of single stage compression cycle can be improved by increase of absorber pressure. but the performance of two-stage compression cycle can not be improved in this way : the compressor discharging temperature of two-stage compression is much lower than that of single stage cycle. which is very important to the safety operation of CA heat pump. Major parameter comparison between the cycles at their optimal configurations is also given.

  • PDF

Themodynamic Characteristics of a Two-Stage Binary Absorption Cycle (2단(段) 2원(元) 흡수(吸收)사이클의 특성(特性)에 관(關)한 연구(硏究))

  • Lee, Y.H.;Rie, D.H.;Kashiwagi, T.;Seo, J.Y.
    • Solar Energy
    • /
    • v.15 no.1
    • /
    • pp.29-38
    • /
    • 1995
  • This paper concerns the study of a two-stage binary absorption cycle employing the refrigerant/absorbent combinations of $LiBr/H_2O$ and $NH_3/H_2O$. This cycle consists of coupling two single-effect absorption cycles so that the first stage absorber and condenser produces heating water to evaporate refrigerant in the evaporator of the second stage. The effect of operating variables such as evaporator temperature, condenser and absorber temperature, and generator temperature on the coefficient of performance and temperature lift have been studied for two-stage binary absorption heat pump systems. It is found that this cycle has a large temperature lift at $105^{\circ}C$ of optimum generator temperature to obtain $50^{\circ}C$ of condenser temperature.

  • PDF

Performance analysis for the Characteristics of Double Stage Evaporator/Absorber for Large temperature Difference Absorption System (흡수식 대온도차 시스템에서 2단 증발/흡수기의 성능 특성에 관한 수치적 연구)

  • Park, Chan-Woo;Kang, Yong-Tae;Im, Ick-Tae;Moon, Sang-Done
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.304-308
    • /
    • 2008
  • The optimal design of two stage evaporation & absorption system which is related to the large temperature difference system was investigated numerically in the absorption refrigeration system. The concentrations at inlet & oulet of absorber are 62.9% and 56.9%, but in two stage absorption system the values are 62.2% and 56.2%. Therefore strong solution & weak solution became diluted than the standard value. The amount of weak solution circulation can be reduced in absorption refrigeration system, and the sensible heat load is more reduced to enhance the COP of system. As UAR is increased, COP becomes larger, and this means the role of top section is more important than bottom section in two stage evaporation & absorption system. But the increase of COP becomes slower at 0.7 of UAR ratio. The performance of Type2 is higher than Type1 in COP with the flow direction of cooling waters. This phenomena is due to the active absorption of vapor -absorption & lower temp. cooling water is more effective. The pressure at bottom section becomes higher & that at top section becomes lower and therefore the circulation rate can be diminished more.

  • PDF

Optimum design of the Characteristics of Double Stage Evaporator/Absorber for Large temperature Difference Absorption System (냉수 대온도차 흡수식 냉동기용 2단 증발기/ 흡수기 최적 설계)

  • Park, Chan-Woo;Im, Ick-Tae;Kang, Yong-Tae
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.203-211
    • /
    • 2008
  • The optimal design of two stage evaporation & absorption system which is related to the large temperature difference system was investigated numerically in the absorption refrigeration system. The concentrations at inlet & oulet of absorber are 62.9% and 56.9%, but in two stage absorption system the values are 62.2% and 56.2%. Therefore strong solution & weak solution became diluted than the standard value. The amount of weak solution circulation can be reduced in absorption refrigeration system, and the sensible heat load is more reduced to enhance the COP of system. As UAR is increased, COP becomes larger, and this means the role of top section is more important than bottom section in two stage evaporation & absorption system. But the increase of COP becomes slower at 0.7 of UAR ratio. The performance of Type2 is higher than Type1 in COP with the flow direction of cooling waters. This phenomena is due to the active absorption of vapor -absorption & lower temp. cooling water is more effective. The pressure at bottom section becomes higher & that at top section becomes lower and therefore the circulation rate can be diminished more.

  • PDF

evaluation of Performance Characteristic on Triple Effect Absorption Cycle (삼중효용 흡수사이클의 성능특성 평가)

  • 권오경
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.22 no.6
    • /
    • pp.782-791
    • /
    • 1998
  • This paper presents a computer simulation of five types of triple effect absorption cycles employ-ing the refrigerant absorbent combinations of NH3/LiNO3 low-pressure type NH3/LiNO3+H2O/LiBr binary two-stage type series flow cycle and two types of parallel flow cycle for H2O/LiBr. The absorption systems is investigated through cycle simulation to obtain the system characteristics with the cooling water inlet temperature approach temperature of absorber loss temperature of absorber and chilled water outlet temperature. The most important characteristic temperature of absorber and chilled water outlet temperature. The most important characteristic of NH3/LiNO3 low-pressure type and a NH3/LINO3+H2O/LiBr binary two-stage type is that it obtains a coefficient of performance higher than the sum of the performance coefficients of its part operating independently. As a result of this analysis the optimum designs and operating conditions were determined based on the operating conditions and the coefficient of performance.

  • PDF

Sequential Approximate Optimization of Shock Absorption System for Lunar Lander by using Quadratic Polynomial Regression Meta-model (2차 다항회귀 메타모델을 이용한 달착륙선 충격흡수 시스템의 순차적 근사 최적설계)

  • Oh, Min-Hwan;Cho, Young-Min;Lee, Hee-Jun;Cho, Jin-Yeon;Hwang, Do-Soon
    • Journal of the Korean Society for Aeronautical & Space Sciences
    • /
    • v.39 no.4
    • /
    • pp.314-320
    • /
    • 2011
  • In this work, optimization of two-stage shock absorption system for lunar lander has been carried out. Because of complexity of impact phenomena of shock absorption system, a 1-D constitutive model is proposed to describe the behavior of shock absorption system. Quadratic polynomial regression meta-model is constructed by using a commercial software ABAQUS with the proposed 1-D constitutive model, and sequential approximate optimization of two-stage shock absorption system has been carried out along with the constructed meta-model. Through the optimization, it is verified that landing impact force on lunar lander can be considerably reduced by changing the cell size and foil thickness of honeycomb structure in two-stage shock absorption system.

Effects of Various Anions on Absorption and Toxicity of Lead in Plants (식물체의 연(Pb) 흡수 및 유해성에 미치는 음이온의 영향)

  • 성민웅
    • Journal of Plant Biology
    • /
    • v.20 no.1
    • /
    • pp.7-14
    • /
    • 1977
  • The seeds of bean(Glycine max M.) and corn(Zea mays L.) soaked in 5000ppm lead solution for 24 hours were sowed in the flowerpots being placed sandy-clay soil under the field condition. The fixed concentrations of various anions and 2000 ppm lead were supplied alternately in the sandy-clay soi of the flowerpots at two days interval from May to July in 1976. After the plants were harvested prior to the flowering stage, the lead contents of plnat and soil were analyzed by atomic absorption spectrophotometer. The lead contents absorbed by the plant roots showed the highest in an weak acid soil of the best suitable condition of plant growth. The absorption of lead by the plant roots was inhibited by the various anions, especially divalent anions of the soil. Some phosphate anions inhibited lead absorption more than otehr various anions in the soil. The more various anions were in the soil, the more plants could be protected from the lead toxicity. In the case of lead supply in the soil, 99.5% of lead was accumulated in the upper layer of the soil(0-10cm), and 0.5% of lead accumulated in the lower layer (10-20cm). Therefore, the yellow-brown and white symptoms on the leaves and the inhibition of root growth by lead toxicity was increased in the early stage of the germination, however decreased in accordance with the progress of the growing stage becuase of the root growth toward beneath the lower layer of the soil. In spite of the contents of 3773ppm lead in the soil, the symptoms of lead toxicity was not found in the grown plants. At that time the lead contents of the plants absorbed from the soil were minimum 0.78ppm and maximum 3.64ppm through the growing stage.

  • PDF

Analysis of High Volume Slit Type Two-Stage Virtual Impactor for Particle Size Classification (특정크기 입자농축을 위한 대유량 슬릿형 2단 가상충돌기의 성능분석)

  • 박성호;김상수;오명도
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.15 no.1
    • /
    • pp.285-291
    • /
    • 1991
  • A two-stage slit type virtual impactor based on the concept of the single stage virtual impactor has been designed, fabricated, and evaluated for the purpose of concentrating the suspended particles in the air with the size range of 1.8-4.5 .mu.m and handling large flow volume. Monodisperse methylene blue particles have been generated with vibrating orifice aerosol generator (VOAG). The separation efficiency and concentration efficiency have been measured by the UV-visible absorption spectrometry. Previous study for a single stage virtual impactor were used to determine the design parameters such as 50% cut-off sizes and dimensions of the two stage virtual impactor. The separation efficiency curve and 50% cut-off Stokes number(cut-off sizes) are not sensitive to the nozzle Reynolds number, but sensitive to the ratio between the minor flow rate and the total flow rate, The measured concentration efficiency was compared with the maximum concentration efficiency determined by the separation efficiencies of the first and the second stages. The differences between the measured and the maximum concentration efficiencies result from the wall loss due to the deposited particles on the internal walls inside the impactor.