• Title/Summary/Keyword: Tripping

Search Result 124, Processing Time 0.028 seconds

Power Quality Analysis and Failure Survey of Earth Leakage Breakers in Factory Electrical Installation (공장전기설비의 누전차단기 오동작 조사 및 전력품질분석)

  • Lee, Sang-Ick;Choe, Gyu-Ha
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.13 no.1
    • /
    • pp.15-21
    • /
    • 2008
  • This paper presented a actual conditions on a false-tripping of ELB(Earth Leakage Breakers) and an assessment of the harmonics due to non-linear electronic equipment such as personal computers, rectifier, electric furnace and test equipments in factory electrical installation. Actual conditions on a failure of ELB were surveyed and analyzed by making up a question to safety managers of factory electrical installation. Also, power quality measurements such as harmonic currents, voltage and current waveform and current imbalance were made at various factory electrical installation where nuisance tripping of ELB is often occurred. The results of this study can be used in making decisions regarding cause of ELB trip and operating and tripping characteristics test of ELB when subjected to distorted current waveform.

A New Stabilizing Method for Transiently Unstable Systems by Using Transient Energy Function (에너지함수를 이용한 과도불안정 시스템의 안정화 방법)

  • Kim, Jung-Woo;Chun, Yeong-Han
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.4
    • /
    • pp.567-575
    • /
    • 2008
  • Transient security assessment(TSA) is becoming an essential requirement not only for security monitoring but also for stabilizing control of power systems under new electricity environments. It has already been pointed out that fast transient stability study is an important part for monitoring and controlling system security. In this paper, we discuss an energy function method for stabilizing control of transiently unstable systems by introducing generator tripping system to enhance the transient stability of power systems. The stabilization with less tripped power can be obtained by tripping the generators faster than out-of-synchronism relay. Fast transient stability assessment based on the state estimation and direct transient energy function method is an important part of the stabilizing scheme. It is possible to stabilize the transiently unstable system by tripping less generators before the action of out-of-synchronism relay, especially when a group of generator are going to be out-of-synchronism. Moreover, the amount of generator output needed for tripping can be decided by Transient Energy Function(TEF) method. The main contribution of this paper is on the stabilizing scheme which can be running in the Wide Area Control System.

Failure of Earth Leakage Breaker and Power Quality Analysis in Office Buildings (사무용 빌딩에서의 누전차단기 오동작과 전력품질 분석)

  • Lee, Sang-Ick;Yoo, Jae-Geun;Jeong, Jong-Wook;Lim, Yong-Bae;Jeon, Jeong-Chay
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.211-216
    • /
    • 2004
  • This paper presented a actual conditions on a false-tripping of ELB(Electrical Leakage Breaker) and an assessment of the harmonics due to non-linear electronic equipment such as personal computers, printers, fax machines, and test equipments in several office buildings. Actual conditions on a failure of ELB were surveyed and analyzed by making up a question to safety managers of in office buildings. Also, power quality measurements such as harmonic currents, voltage and current waveforms and current imbalance were made at various office buildings where nuisance tripping of ELB is often occurred. The results of this study can be used in making decisions regarding cause of ELB trip and operating md tripping characteristics test of ELB when subjected to distorted current waveforms.

  • PDF

Power Quality Analysis and Failure of Earth Leakage Breakers in Plant (공장전기설비에서의 누전차단기 오동작과 전력품질 분석)

  • Lee, S.J.;Yoo, J.G.;Jeon, J.C.;Jeon, H.J.;Heo, H.S.;Choe, G.H.
    • Proceedings of the KIPE Conference
    • /
    • 2007.07a
    • /
    • pp.479-481
    • /
    • 2007
  • This paper presented a actual conditions on a false-tripping of ELB(Earth Leakage Breakers) and an assessment of the harmonics due to non-linear electronic equipment such as personal computers, rectifier, electric furnace and test equipments in plant installations. Actual conditions on a failure of ELB were surveyed and analyzed by making up a question to safety managers of plant installations. Also, power quality measurements such as harmonic currents, voltage and current waveform and current imbalance were made at various plant installations where nuisance tripping of ELB is often occurred. The results of this study can be used in making decisions regarding cause of ELB trip and operating and tripping characteristics test of ELB when subjected to distorted current waveform.

  • PDF

Analysis of Tripping Characteristics of Earth Leakage Circuit Breakers against Parallel Arcing (병렬아크에 대한 누전차단기의 트립특성 분석)

  • Kim, Il-Kwon;Park, Dae-Won;Choi, Su-Yeon;Cho, Young-Jin;Kil, Gyung-Suk
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.11a
    • /
    • pp.478-479
    • /
    • 2007
  • Many electrical fires are occurred by leakage currents and sparks generated by a short circuit. Earth leakage circuit breakers (ELCBs) should be tripped at the moment of the faults mentioned above. In this paper, we described the tripping characteristics of ELCBs against parallel arcing faults. A diesel engine generator with the capacity of 375 kVA source was adopted to provide enough large current when a parallel arcing occurred. The experimental results showed that most ELCBs we experimented were not tripped against short-duration pulse currents produced by parallel arcing because the ELCBs are designed to be tripped by a large current with long duration similar to power frequency.

  • PDF

Transformer Differential Relay by Using Neural-Fuzzy System

  • Kim, Byung Whan;Masatoshi, Nakamura
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 2001.10a
    • /
    • pp.157.2-157
    • /
    • 2001
  • This paper describes the synergism of Artificial Neural Network and Fuzzy Logic based approach to improve the reliability of transformer differential protection, the conventional transformer differential protection commonly used a harmonic restraint principle to prevent a tripping from inrush current during initial transformer´s energization but such a principle can not performs the best optimization on tripping time. Furthermore, in some cases there may be false operation such as during CT saturation, high DC offset or harmonic containing in the line. Therefore an artificial neural network and fuzzy logic has been proposed to improve reliability of the transformer protection relay. By using EMTP-ATP the power transformer is modeled, all currents flowing ...

  • PDF

An Experimental Study of Mutual Relation between Wake and Boundary Layer of a Flat Plate; Mean Velocity Field (평판 경계층과 후류와의 상호관계에 관한 연구; 평균속도장)

  • Kim, Dong-Ha;Chang, Jo-Won
    • Journal of the Korean Society for Aeronautical & Space Sciences
    • /
    • v.32 no.10
    • /
    • pp.1-11
    • /
    • 2004
  • An experimental study was carried out to investigate the influence of flow conditions of a boundary layer on the near-wake of a flat plate. Various attaching positions of tripping wires were selected to change flow conditions on a boundary layer. Laminar, transitional, and turbulent boundary layer conditions at 0.98C from the leading edge are imposed to investigate the evolution of symmetric and asymmetric wake. An x-type hot-wire probe(55P61) is employed to measure at 8 stations of the near-wake region. Measured mean velocity distributions are presented in terms of similarity parameter. It is found that the symmetric wake collapses well to the universal profile in the central part of the wake. However, the universal profile is not suitable in describing an asymmetric wake.

The Method of Reinforcing the Immunity of Residual Current Circuit Breaker for the EMC Composite Surge (누전차단기의 EMC 조합서지 내성 강화를 위한 방안)

  • Kim Jae-Chul;Han Yoon-Tak;Kim Oun-Seok;Seol Kyu-Hwan;Kang Jang-Kyou;Moon Jong-Fil
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.8
    • /
    • pp.322-328
    • /
    • 2006
  • In this paper, The impulse un-tripping characteristics and the electro magnetic compatibility characteristics are compared with each other. The performance of impulse un-tripping test exists at domestic standard (KSC 4613). However test items are insufficient because the more test items such as EMC exist at international standard (IEC). Also, Electric Appliances Safety Certificate has taken the certificate test since July 2004 in Korea but did not confirm the EMC performance for RCCBs made in Korea. Thus, in this paper, We experiment with Oscillatory waves immunity test and the 7 EMC tests for 32 RCCBs of 4 types (mini, home standard, plug, outlet) for 16 brands according to IEC standard 61009-1 and 61008-1. As a result, 24 RCCBs proved to be poor for surge immunity test. However the RCCBs operating incorrectly for surge immunity test operate correctly for oscillatory waves immunity test. Thus, the correlation between oscillatory waves immunity test and EMC test is little and standard for compatibility of combination surge at IEC 61000-4-5 should be added to KS standard as soon as possible.

A Study on the Operating Characteristic of RCB by Synthesize Harmonic Current (복합고조파에 의한 누전차단기의 동작 특성 연구)

  • Yoo, Jae-Geun;Choi, Myung-Il;Park, Chee-Hyun;Son, Jae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.9 no.1
    • /
    • pp.59-63
    • /
    • 2008
  • This paper analyze the operating characteristic of RCB due to the synthesize harmonic current. The RCB of rated sensitivity electric current with 30[mA] test to operating characteristic by synthesize harmonic current and it analyzed the tripping operation due to a harmonic current. The test result, the operating current of RCB changed by synthesize harmonic current.

Effect on Molded Case Circuit Breaker of Harmonic Current (고조파 전류가 배선용차단기에 미치는 영향)

  • Yoo, Jae-Geun;Choi, Myung-Il;Park, Chee-Hyun;Son, Jae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.9 no.1
    • /
    • pp.53-58
    • /
    • 2008
  • This paper analyze the operating characteristic of MCCB due to the synthesize harmonic current. Four types of MCCBs, divided by the type of operation system and a principle of operation, tested with 200[%] of rated current. The test result nuisance tripping did not occur but the time delay characteristic of the hydraulic magnetic type MCCB is appeared. From the place where the synthesize harmonic content is high it is good the hydraulic magnetic type MCCB not to use.