Abstract
This paper presented a actual conditions on a false-tripping of ELB(Earth Leakage Breakers) and an assessment of the harmonics due to non-linear electronic equipment such as personal computers, rectifier, electric furnace and test equipments in factory electrical installation. Actual conditions on a failure of ELB were surveyed and analyzed by making up a question to safety managers of factory electrical installation. Also, power quality measurements such as harmonic currents, voltage and current waveform and current imbalance were made at various factory electrical installation where nuisance tripping of ELB is often occurred. The results of this study can be used in making decisions regarding cause of ELB trip and operating and tripping characteristics test of ELB when subjected to distorted current waveform.
공장전기설비에서 개인용 컴퓨터, 정류기, 전기로와 시험장치 등의 비선형 부하 사용 증가에 따른 고조파 발생으로 누전차단기가 오동작하거나 불필요 동작을 하고 있다. 따라서 공장전기설비의 안전관리자를 대상으로 누전차단기의 오동작 상태에 대한 조사를 실시하였다. 또한 누전차단기가 오동작하거나 불필요 동작을 하고 있다는 수용가에서 전압, 전류, 고조파와 불평형 등 전력품질을 측정하고 분석하였다. 본 연구결과는 왜형된 전류파형으로 누전차단기의 트립특성 시험과 누전차단기 오동작 원인분석시 자료로 활용하고자 한다.