• Title/Summary/Keyword: Transient fault current limiting characteristics

Search Result 15, Processing Time 0.019 seconds

Transient Current Limiting Characteristics of Flux-Lock Type SFCL Using Double Quench (이중퀜치를 이용한 자속구속형 초전도한류기의 과도전류제한 특성)

  • Choi, Sang-Jae;Lim, Sung-Hun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.30 no.2
    • /
    • pp.96-100
    • /
    • 2017
  • In this paper, the flux-lock type superconducting fault current limiter (SFCL) using double quench was suggested and its transient current limiting characteristics were analyzed. The suggested flux-lock type SFCL using double quench consists of two magnetically coupled windings and two $high-T_{c}$ superconducting (HTSC) elements connected in series with each winding. To analyze the transient current limiting characteristics of the flux-lock type SFCL using double quench, the short-circuit tests according to the fault angles, which affect the transient component of the fault current right after the fault occurs, were executed. From the comparative analysis for the short-circuit tests at both $0^{\circ}$ and $90^{\circ}$ fault angles, the useful transient current limiting operations of the suggested flux-lock type SFCL through the double or the single quench occurrence were confirmed.

Transient Fault Current Limiting Characteristics of a Transformer Type SFCL Using an Additional Magnetically Coupled Circuit

  • Lim, Seung-Taek;Lim, Sung-Hun
    • Transactions on Electrical and Electronic Materials
    • /
    • v.18 no.1
    • /
    • pp.42-45
    • /
    • 2017
  • In this paper, a transformer type SFCL (superconducting fault current limiter) using an additional magnetically coupled circuit was suggested. Its transient fault current limiting characteristics, due to the winding direction of additional coupled circuit, were analyzed through fault current limiting tests. The suggested transformer type SFCL was composed of the primary winding, and one secondary winding wound on the same iron core together with an additional magnetically coupled circuit. That circuit consists of the other secondary winding together with the other SC (superconducting) element connected in parallel with its other secondary winding. As one of the effective design parameters to affect the transient fault current of the SFCL, the fault current limiting tests of the suggested SFCL were carried out considering the winding direction of its additional coupled circuit. It was confirmed that, through the analysis on the fault current tests of the SFCL, the quench sequence of two SC elements comprising the suggested SFCL could be adjusted by the winding direction of the additional coupled circuit.

Analysis on Current Limiting Characteristics of Transformer Type SFCL with Additionally Coupled Circuit

  • Lim, Seung-Taek;Ko, Seok-Cheol;Lim, Sung-Hun
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.2
    • /
    • pp.533-539
    • /
    • 2018
  • In this paper, the transformer type superconducting fault current limiter (SFCL) with additionally coupled circuit was suggested and its peak fault current limiting characteristics due to the fault condition to affect the fault current were analyzed through the fault current limiting tests. The suggested transformer type SFCL is basically identical to the previous transformer type SFCL except for the additional coupled circuit. The additional coupled circuit, which consists of the magnetically coupled winding to the primary and the secondary windings together with another superconducting element and is connected in parallel with the secondary winding of the transformer type SFCL, is contributed to the peak fault current limiting operation for the larger transient fault current directly after the fault occurrence. To confirm the fault current limiting operation of the suggested SFCL, the fault current limiting tests of the suggested SFCL were performed and its effective peak fault current limiting characteristics were analyzed through the analysis on the electrical equivalent circuit.

Study on Transient Current Limiting Operational Characteristics of Transformer Type SFCL with Two Peak Current Limiting Function (두 번의 피크전류제한 기능을 갖는 변압기형 초전도한류기의 과도전류제한 동작 특성 연구)

  • Han, Tae-Hee;Lim, Sung-Hun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.29 no.8
    • /
    • pp.499-504
    • /
    • 2016
  • In this paper, we analyzed the operational characteristics of the fault current limiting according to the amplitude of the fault current for the transformer type superconducting fault current limiter (SFCL). If the fault current happens, the superconducting element connected to the secondary coil is occurred quench and the fault current is limited. When the larger fault current occurs, the superconducting element connected to the third coil is occurred additional quench and the peak fault current is limited. We found that the fault current can be more effectively controlled through the analysis of the fault current limiting and the short-circuit tests.

Current limiting characteristics of transformer type SFCL with coupled secondary windings according to its winding direction

  • Han, Tae Hee;Lim, Sung Hun
    • Progress in Superconductivity and Cryogenics
    • /
    • v.19 no.2
    • /
    • pp.44-47
    • /
    • 2017
  • In this paper, the current limiting characteristics of the transformer type superconducting fault current limiter (SFCL) with the two coupled secondary windings due to its winding direction were analyzed. To analyze the dependence of transient fault current limiting characteristics on the winding direction of the additional secondary winding, the fault current limiting tests of the SFCL with an additional secondary winding, wound as subtractive polarity winding and additive polarity winding, were carried out. The time interval of quench occurrence between two superconducting elements comprising the transformer type SFCL with the additional secondary winding was confirmed to be affected by the winding direction of the additional secondary winding. In case of the subtractive polarity winding of the additional secondary winding, the time interval of the quench occurrence in two superconducting elements was shorter than the case of the additive polarity winding.

Current Limiting Characteristics of a Resistive SFCL for a Single-line-to-ground Fault in the 22.9 kV System (1선 지락사고에 대한 배전급 저항형 초전도 한류기의 전류제한특성)

  • 최효상;황시돌;현옥배
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.14 no.6
    • /
    • pp.505-510
    • /
    • 2001
  • We simulated the current limiting characteristics of a resistive superconducting fault current limiter (SFCL) for a single line-to-ground fault in the 22.9 kV system. The transient current during the fault increased to 6.33 kA, 5.80 kA and 3.71 kA without SFCL at the fault angles 0$^{\circ}$, 45$^{\circ}$ and 90$^{\circ}$, respectively, a resistive SFCL limited effectively the fault current to 2.27 kA in a half cycle without any DC components. The maximum quench resistance of an SFCL, 16Ω was suggested to be appropriate to limit the fault current in the 22.9 kV distribution system, considering the operating cooperation of a protective relay and the current limiting performance of an SFCL.

  • PDF

Analysis on the Operational Characteristic between the Protective devices and Superconducting Fault Current Limiter with a Peak Current Limiting Function in the Power Distribution System (피크전류 제한 기능을 갖는 초전도한류기의 계통 적용에 따른 보호기기간 동작특성 분석)

  • Cho, Yong-Sun;Kim, Jin-Seok;Kim, Jae-Chul;Lim, Sung-Hun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.11
    • /
    • pp.75-80
    • /
    • 2012
  • In this paper, the operational characteristics due to the introduction of the superconducting fault current limiter(SFCL) with a peak current limiting function were analyzed in the power distribution system. The parallel structure of the superconducting element can operate the peak current limiting function depending on the transient amplitude of fault current. We studied the operating characteristics of the introduction of the SFCL with a peak current limiting function in the power distribution system. Furthermore, we were analyzed between the SFCL with a peak current limiting function and the protection devices in the power distribution system, through the short circuit experiments.

Simulation for current limiting characteristics of a resistive SFCL in the 22.9 kV distribution system (배전급 저항형 초전도 한류기의 전류제한특성에 대한 EMTDC 시뮬레이션)

  • Choi, Hyo-Sang;Hyun, Ok-Bae;Hwang, Si-Dole;Kim, Sang-Joon
    • 한국초전도학회:학술대회논문집
    • /
    • v.10
    • /
    • pp.268-271
    • /
    • 2000
  • We simulated the current limiting characteristics of a resistive SFCL with 16 ${\Omega}$ of resistance for a single line-to-ground fault in the 22.9 kV system. The transient current during the fault increased up to 6.33 kA, 5.80 kA and 3.71 kA without SFCL at the fault angles of 0${\circ}$,45${\circ}$ and 90${\circ}$, respectively. An resistive SFCL limited the fault current to 2.27 kA in a half cycle. The quench resistance of 16 ${\Omega}$ was suggested to be appropriate to limit the fault current in the 22.9 kV distribution system.

  • PDF

Analysis of Transient Characteristics of a SFCL Applied Into Third-winding Transformer in a Single Line-to-ground Fault (1선 지락 사고 시 3 권선 변압기에 적용된 초전도 한류기의 동작 특성 분석)

  • Choi, Hye-Won;Choi, Hyo-Sang;Jung, Byung-Ik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.7
    • /
    • pp.1033-1037
    • /
    • 2013
  • Coercion transformer is commonly used in the electrical grid which in three phase of distribution system. The accident of the electrical grid is divided into a single, a double, a third line-to-ground faults and a double, a third line-to-line faults. A single line-to-ground fault accounts for nearly 75[%] among them. In this research, when a Superconducting Fault Current Limiters (SFCL) was applied to the three phase power system, operation in a single line-to-ground fault and limiting characteristics of fault current according to turns ratio of third winding were analyzed. When a single line-to-ground fault happened, secondary winding's circuit was open. Then third winding's circuit with a SFCL was closed. So fault current was limited by diverted circuit. At this time, we could find out that size of the limited fault current could be changed according to third winding rate. We confirmed that limiting operation of the fault current was carried out within one-period. These results will be utilized in adjusting the size of the SFCL.

Quench Characteristics of a Inductive Superconducting Fault Current Limiter (유도형 초전도사고전류제한기의 퀜치특성)

  • Choi, K.D.;Lee, S.J.;Kim, D.S.;Lee, J.K.;Kim, D.H.;Cha, G.S.;Hahn, S.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1994.11a
    • /
    • pp.114-116
    • /
    • 1994
  • Recently a superconducting fault current limiter(SFCL) has public attentions for the solution of large fault currents of power systems. Though a SFCL has more effective characteristics than the other current limiting devices, there are many problems to apply it to real power systems. For the analysis of transient fault characteristics of the SFCL, we designed and fabricated a inductive SFCL and tested it in 35V line. The superconducting cable of the SFCL was quenched at lower current(49A) than the designed critical current but it limited the fault current to the lower value(150A) than the one expected without SFCL(250A). And within one period the fault current decreased lower than normal laod current.

  • PDF