• Title/Summary/Keyword: Transformer failure

Search Result 117, Processing Time 0.033 seconds

A Study on Optimal Design for Linear Electromagnetic Generator of Electricity Sensor System using Vibration Energy Harvesting (진동에너지 하베스팅을 이용한 전력감지시스템용 리니어 전자기 발전기에 관한 최적설계)

  • Cho, Seong Jin;Kim, Jin Ho
    • Journal of the Korean Society of Manufacturing Process Engineers
    • /
    • v.16 no.2
    • /
    • pp.7-15
    • /
    • 2017
  • Recently, an electricity sensor system has been installed and operated to prevent failures and accidents by identifying whether a transformer is normal in advance of failure. This electricity sensor system is able to both measure and monitor the transformer's power and voltage remotely and send information to a manager when unusual operation is discovered. However, a battery is required to operate power detection devices, and battery systems need ongoing management such as regular replacement. In addition, at a maintenance cost, occasional human resources and worker safety problems arise. Accordingly, we apply a linear electromagnetic generator using vibration energy from a transformer for an electric sensor system's drive in this research and we conduct optimal design to maximize the linear electromagnetic generator's power. We consider design variables using the provided design method from Process Integration, Automation, and Optimization (PIAnO), which is common tool from process integration and design optimization (PIDO). In addition, we analyze the experiment point from the design of the experiments using "MAXWELL," which is a common electromagnet analysis program. We then create an approximate model and conduct accuracy verification. Finally, we determine the optimal model that generates the maximum power using the proven approximate kriging model and evolutionary optimization algorithm, which we then confirm via simulation.

Robust Design for Parts of Induction Bolt Heating System (유도가열시스템의 구성부품에 대한 강건설계)

  • Kim, Doo Hyun;Kim, Sung Chul;Lee, Jong Ho;Kang, Moon Soo;Jeong, Cheon Kee
    • Journal of the Korean Society of Safety
    • /
    • v.36 no.2
    • /
    • pp.10-17
    • /
    • 2021
  • This paper presents the robust design of each component used in the development of an induction bolt heating system for dismantling the high-temperature high-pressure casing heating bolts of turbines in power plants. The induction bolt heating system comprises seven assemblies, namely AC breaker, AC filter, inverter, transformer, work coil, cable, and CT/PT. For each of these assemblies, the various failure modes are identified by the failure mode and effects analysis (FMEA) method, and the causes and effects of these failure modes are presented. In addition, the risk priority numbers are deduced for the individual parts. To ensure robust design, the insulated-gate bipolar transistor (IGBT), switched-mode power supply (SMPS), C/T (adjusting current), capacitor, and coupling are selected. The IGBT is changed to a field-effect transistor (FET) to enhance the voltage applied to the induction heating system, and a dual-safety device is added to the SMPS. For C/T (adjusting current), the turns ratio is adjusted to ensure an appropriate amount of induced current. The capacitor is replaced by a product with heat resistance and durability; further, coupling with a water-resistant structure is improved such that the connecting parts are not easily destroyed. The ground connection is chosen for management priority.

Representative Dissolved Gases indicating Aging of Power Transformers (전력용 변압기 경년열화와 관련된 DGA 대표가스에 관한 연구)

  • Kweon, Dongjin;Kim, Yonghyun;Joo, Byoungsoo
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.3 no.1
    • /
    • pp.23-28
    • /
    • 2017
  • The life management technology becomes important as the failure risk of the aged power transformers increases. Asset management technology, therefore, has been developed to evaluate the remaining life and build replacement strategies of power transformers, which enables an optimal investment decisions based on reliability and economic feasibility. The remaining life assessment technology uses data related to such as installation, operation, maintenance, refurbishment, and disposed history of power transformers. The optimal investment decision additionally uses data related to failure and social costs. To develop the asset management technology in power transformers, it is important to find deterioration parameters directly indicating degradation of power transformers. In this study, 110,000 DGA data during the past 35 years have been analyzed in order to find the deterioration parameters related to the degradation of power transformers. The alarm rates of combustible gases ($H_2$, $C_2H_2$, $C_2H_4$, $CH_4$, $C_2H_6$), TCG CO, and $CO_2$ were analyzed as deterioration parameters. The origin of the gas was discussed in connection with discharge, overheating and insulation aging.

A Comparison Study on Mechanical Properties of XLPE Insulation Thermally Degraded at Equivalent and Variable Temperature Conditions (XLPE 절연체의 등가 및 가변온도 가속열화실험을 통한 기계적 특성 비교 분석)

  • Taejoon, Kim;Jae-Sang, Hwang;Sung Hoon, Jung;Tae Young, Kim
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.8 no.2
    • /
    • pp.73-77
    • /
    • 2022
  • Recently, as the number of years of operation has increased for more than 30 years, interest in evaluating the remaining life of major power facilities such as transformers and ultra-high voltage cables is increasing. In particular, the risk of failure is increasing because the underground transmission XLPE cable has been built since 1980 and has been operating in excess of 30 years of design life or close proximity. Therefore, it is necessary to develop an algorithm to evaluate the residual life of the XLPE cable considering the load to determine the risk of failure. Since load data is large amount of data, it is necessary to make the variable load information equivalent to the time unit first in order to calculate the remaining life of the system quickly. In overseas literature, transformers are reported to be standardized for variable load equivalent conversion formulas, but they have not been reported for ultra-high voltage cables. Therefore, in this paper, whether the equivalent conversion formula of a transformer can be applied to XLPE cables was reviewed through accelerated degradation tests under equivalent and variable temperature conditions, and considerations were studied when evaluating the remaining operating life of XLPE cables based on the experimental results.

A Study on the Detection of Asynchronous State of the Synchronous Generator

  • Choi, Hyung-Joo;Lee, Heung-Ho
    • Journal of international Conference on Electrical Machines and Systems
    • /
    • v.2 no.4
    • /
    • pp.405-412
    • /
    • 2013
  • This paper includes new protection concepts and practices to avoid mechanical damage of three-phase transformer by asynchronous operation of synchronous generator. this failure is often caused just after synchronous generator was connected to the grid because of a malfunction of the controller or misconnections of the synchronous devices. The results of the studies on the analyzing the phenomenon of asynchronous operation experienced in Korea and rapidly detecting asynchronous state are descrived.

Performance Improvement of an Active Neutral Harmonic Suppressor System Under Unbalanced Load Conditions

  • Choi, Se-Wan;Jang, Min-Soo
    • Proceedings of the KIPE Conference
    • /
    • 2001.10a
    • /
    • pp.822-828
    • /
    • 2001
  • Three-phase four-wire electrical distribution systems are widely employed in manufacturing plants, commercial and residential buildings. Due to the nonlinear loads connected to the distribution system, the neutral conductor carries excessive harmonic currents even under balanced loading since the triplen harmonics in phase currents do not cancel each other. This may result in wiring failure of the neutral conductor and overloading of the distribution transformer. In response to these concerns, a cost-effective neutral current harmonic suppressor system has been proposed [6]. This paper proposes an improved control method for the harmonic suppressor system under unbalanced load conditions. The proposed control method compensates for only the harmonic components in the neutral conductor, and the zero-sequence fundamental component due to unbalanced loading is prevented from flowing through the harmonic suppressor system. This remedies overloading and power loss of the system. The experimental results on a prototype validate the proposed control approach.

  • PDF

Study on the Failure Case of Potential Transformer for Generator Protection Relay (발전기 보호계전기용 계기용변성기(PT) 손상 사례에 관한 연구)

  • Park, Jin-Yeub;Chin, Soo-Hwan;Park, In-Kyoo
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.2065-2066
    • /
    • 2011
  • 기계적에너지를 전기적에너지로 변환하는 발전기를 내 외부 고장으로부터 보호하기 위해 보호계전기가 설치되어 있으며, 이러한 보호계전기의 동작신호 중 하나인 전압신호를 검출하기 위해 발전기와 변압기를 연결하는 모선에 설치된 계기용변성기를 이용한다. 본 논문은 발전기의 보호계전기용 계기용변성기 손상원인에 관한 연구로서, 계기용변성기의 철공진에 이한 손상가능성을 고찰하였고 발전소에 많이 사용되는 G사의 계기용변성기와 손상된 I사의 계기용변성기에 대한 전기적 시험결과를 비교하였으며, 계기용변성기를 직접 절개하여 제작 및 적용특성을 분석하였다. 그 결과 발전기 전압신호 검출용 계기용변성기는 발전기 중성점 접지형태에 관계없이 반드시 Line to Line type을 적용해야 함을 도출했다.

  • PDF

Model based monitoring for the failure detection of oil immersed transformer (유입변압기 고장검출을 위한 감시기반 모델링 기법)

  • Choi, Kwang-Bum;Eo, Soo-Young;Kim, Sok-Il
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.2079-2080
    • /
    • 2011
  • 유중가스 감시 방식은 직관적이며 높은 정확도를 가져 변압기 건전성 감시를 위한 최적의 솔루션으로 공인받고 있다. 그러나 변압기는 본체외에도 OLTC, 냉각기, 붓싱등 절연유 감시만으로 완벽하게 건전성을 감시할 수 없는 부속장치들이 있으며 이러한 부속장치들의 고장은 변압기 고장의 시발점이 될 수 있다. 또한 절연유에서 이상 징후가 나타났을 때 변압기의 부속장치들의 건전성을 분석하면 고장부위를 예측하여 유지보수를 효율적으로 할 수 있다. 본 논문에서는 변압기의 유중가스 센서 이외에도 별도 외부 센서들을 추가로 이용하여 어떻게 변압기 운영에 유용한 정보를 만들 수 있는지에 대한 방법으로서의 모델링을 논하고자 한다.

  • PDF

Investigation and Countermeasure of P.T Ferroresonance in the 154kV GIS Substation (154kV GIS 변전소 P.T. 철공진 규명 및 방지대책)

  • Choi, W.S.;Kim, S.K.;Jee, S.K.;Kim, S.T.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.541-543
    • /
    • 2002
  • This paper describes the analysis resulates on the P.T ferroresonance at 154kV GIS(Gas Insulated Substation) by EMTP(Electromagnetic transient program). We had simulated the PT ferroresonance between a potential transformer(PT) and open circuit braker's grading capacitance. The ferroresonance leads to very large power frequency overvoltage on PT bus and subsequent insulation failure. The damping circuit connected on the secondary winding were considered in the model. The actual countermeasure include a saturable inductor and a resistor series mounted, but the 2 ohms of damping resistance was used in the computational model.

  • PDF

A Study on the Elimination of Temporary overvoltage Due to Ferroresonance at Gas Insulated Switchgear (Gas 색연(絶綠) 개폐장치(開閉裝置)의 철공진(鐵共振) 제어대책(制御對策)에 관한 연구(硏究))

  • Kim, S.K.;Kim, T.S.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.05b
    • /
    • pp.216-221
    • /
    • 2000
  • This paper describes the analysis results on the PT ferroresonance at 154 kV GIS (gas Insulated substation by EMTP(Electro- magnetic Transient Program). We had simulated the PT ferroresonance between a potential transformer(PT) and an open circuit breaker's grading capacitance. The ferroresonance leads to very large power frequency overvoltages on PT bus and subsequent insulation failure. The large power can be supplied to the PT by the high voltage on the opened circuit due to the grading capacitance and equivalent capacitance of the buses during the ferroresonance. The damping circuit connected on the secondary winding were considered in the model. The actual countermeasure include a saturable inductor and a resistor series-mounted, but the 2 ohms of damping resistance was used in the computationl model.

  • PDF