• 제목/요약/키워드: Three-phase ground faults

검색결과 32건 처리시간 0.031초

22.9[kV] 다중접지 배전계통에서 고장전류의 접지저항 영향 분석 (The Effect by Grounding Resistance of the ground Fault in the 22.9[kV] Multi-ground Distribution System)

  • 정금영;최선규;심건보;김경철
    • 조명전기설비학회논문지
    • /
    • 제24권10호
    • /
    • pp.85-89
    • /
    • 2010
  • During a ground fault the maximum fault current and neutral to ground voltage will appear at the pole nearest to the fault. Distribution lines are consisted of three phase conductors, an overhead ground wire and a multi-grounded neutral line. In this paper phase to neutral faults were staged at the specified concrete pole along the distribution line and measured the ground fault current distribution in the ground fault current, three poles nearest to the fault point, overhead ground wire and neutral line. A effect by grounding resistance of poles of ground fault current in the 22.9[kV] multi-ground distribution system. by field tests.

결상 시 누전전류 발생과 오동작 방지 기능을 갖는 결상보호기 개발에 관한 연구 (A Study on Development of Open-Phase Protector Having Leakage Current Generation and Incapable Operation Prevention at Open-Phase Accident)

  • 곽동걸
    • 전기학회논문지
    • /
    • 제64권1호
    • /
    • pp.182-187
    • /
    • 2015
  • In the three-phase power system, when any one-phase or two-phases is open-phase, the unbalanced current flows and the single-phase power supplies to three-phase loads. Specially, motor coil and transformer coil receive over-current. As a result, great damage as well as electrical fire can occur to the power system. In order to improve these problems, this paper proposes that an open-phase detection device is designed by a new algorithm using electric potential difference between the resultant voltage of neutral point and ground, and a control circuit topology of open-phase protector is composed of highly efficient semiconductor devices. It improves response speed and reliability. The control algorithm circuit also operates the cut-off of a conventional residual current protective device (RCD) which flows an enforced leakage current to ground wire at open-phase accident. Furthermore, time delay circuit is added to prevent the incapable operation of open-phase protector about instantaneous open-phase not open-phase fault. The time delay circuit improves more reliability.

ACI 기법을 이용한 송전선로 고장 종류 판별에 관한 연구 (A Study on the Algorithm for Fault Discrimination in Transmission Lines using Advanced Computational Intelligence(ACI))

  • 박재흥;이종범
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.619-621
    • /
    • 2004
  • This paper presents the rapid and accurate algorithm for fault discrimination in transmission lines. When faults occur in transmission lines, fault discrimination is very important. If high impedance faults occur in transmission lines, it cannot be detected by overcurrent relays. The method using current and voltage cannot discriminate high impedance fault. Because of this reason this paper uses voltage and zero sequence current, and the proposed algorithm uses fuzzy logic method. This algorithm uses voltage and zero sequence current per period in case of faults. Single line ground fault and three-phase fault can be detective using voltage. Two-line ground fault and line to line fault and high impedance can be detected using zero sequence current. To prove the performance of the algorithm, it test algorithm with signal obtained from ATPDraw simulation.

  • PDF

IoT 기반의 결상사고 원격알람 시스템에 관한 연구 (A Study on Remote Alarm System of Open-phase Faults based on IoT)

  • 정회중;곽동걸;최신형;김춘삼;양기철
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2018년도 추계학술대회
    • /
    • pp.4-6
    • /
    • 2018
  • This paper proposes an open-phase fault control system using 3-phase neutral voltage. The proposed control system is designed as a new topology which uses the potential difference between neutral point and ground(G) of three phase. And the open-phase detection system is configured to Y-wiring of three capacitance devices of the same capacity to each line of three phase power source R-S-T. This paper also designs a mobile phone application for remote alarm of open-phase fault.

  • PDF

비대칭 3상 선로에서 변압기의 철심구조별 문제점 분석 및 방지대책 (Problem Analysis by Iron Core Structure of the Transformer on Asymmetric three Phase lines and Prevention Measures)

  • 신동열;윤동현;차한주
    • 전기학회논문지
    • /
    • 제61권10호
    • /
    • pp.1536-1541
    • /
    • 2012
  • The study analyzed problems by iron core structure of the three phased transformer on asymmetric three phase lines, which included line disconnections, ground faults, COS OFF, and unbalanced loads on the power distribution system. In particular, by analyzing PT combustion cases within the MOF, the study was able to analyze the combustion cause of the core-type transformer and its effect on the system, conduct simulations and practice demonstrations on the characteristics for each iron core structure of the three phase transformer using PSCAD/EMTDC, and suggest measures to prevent the combustion of the core-type transformer.

배전선로 전압강하에 대한 이중 여자 풍력발전시스템 특성 해석 (Analysis of doubly-fed induction generator based wind power system for voltage sag)

  • 차한주;이상회
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.1234-1235
    • /
    • 2007
  • This paper represents the generating principles of the doubly-fed induction generator (DFIG) based wind power system and developes a simulation model of DFIG by using PSCAD/EMTDC. In addition, this paper analyzes the steady state operation and the transient operation during the voltage sags in the power common coupling. The voltage sags are occurred by three phase line-to-ground faults and full-voltage startup of an induction motor in the simulation.

  • PDF

A Study on the Agent (Protective Device)-based Fault Determination and Separation Methodology for Smart Grid Distribution System

  • Ko, Yun-Seok
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권1호
    • /
    • pp.102-108
    • /
    • 2015
  • This paper proposes a new fault isolation methodology for a smart protective device which plays an agent role on the smart grid distribution system with the distributed generation. It, by itself, determines accurately whether its protection zone is fault or not, identifies the fault zone and separates the fault zone through the exchange of fault information such as the current information and the voltage information with other protective devices using bi-directional communication capabilities on the smart grid distribution system. The heuristic rules are obtained from the structure and electrical characteristics determined according to the location of the fault and DG (Distributed Generation) when faults such as single-phase ground fault, phase-to-phase short fault and three-phase short fault occur on the smart grid distribution system with DG.

Hybrid Control and Protection Scheme for Inverter Dominated Microgrids

  • Xu, Xiaotong;Wen, Huiqing;Jiang, Lin;Hu, Yihua
    • Journal of Power Electronics
    • /
    • 제17권3호
    • /
    • pp.744-755
    • /
    • 2017
  • With the high penetration of various sustainable energy sources, the control and protection of Microgrids has become a challenging problem considering the inherent current limitation feature of inverter-based Distributed Generators (DGs) and the bidirectional power flow in Microgrids. In this paper, a hybrid control and protection scheme is proposed, which combines the traditional inverse-time overcurrent protection with the biased differential protection for different feeders with different kinds of loads. It naturally accommodates various control strategies such as P-Q control and V-f control. The parameter settings of the protection scheme are analyzed and calculated through a fast Fourier transform algorithm, and the stability of the control strategy is discussed by building a small signal model in MATLAB. Different operation modes such as the grid-connected mode, the islanding mode, and the transitions between these two modes are ensured. A Microgrid model is established in PSCAD and the analysis results show that a Microgrid system can be effectively protected against different faults such as the single phase to ground and the three phase faults in both the grid-connected and islanded operation modes.

변압기의 단락강도 시험 시 ANSI와 IEC 규격에 의한 시험 전류의 비교 연구 (The Study of Comparison of the Symmetrical Short Circuit Test Current with ANSI/IE Transformers.)

  • 김선구;김원만;나대열;노창일;이동준;정흥수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 B
    • /
    • pp.694-696
    • /
    • 2002
  • Transformers together with all equipment and accessories shall be designed and constructed to withstand the mechanical and thermal stresses produced by external short circuit which include three phase, single line-to-ground, double line-to-ground and line-to-line faults etc. Generally the Short Circuit Test of transformers is tested according to the ANSI/IEEE, IEC/JEC, KS etc, in domestic. In this study, it will be showed and compared the difference of symmetrical current for short circuit test of a Pad -mounted transformer according to with ANSI /IEEE and IEC.

  • PDF

변압기 단락강도시험 성능평가에 관한 고찰 (The Study of Characteristics evaluation of short-circuit tests for Power Transformers)

  • 노창일;김선구;정흥수;김원만;이동준;김선호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.913-914
    • /
    • 2007
  • Power transformer shall be designed and constructed to withstand the mechanical and thermal stresses produced by external short circuits which include three-phase, single line to ground, double line-to-ground, and line-to-line faults on any one set terminals at a time. This paper presents the method of short-circuit test and means of evaluation during and after each test to judge the results of short-circuit tests.

  • PDF