• Title/Summary/Keyword: Thermal Overload Risk

Search Result 7, Processing Time 0.017 seconds

Prediction of Dynamic Line Rating Based on Thermal Risk Probability by Time Series Weather Models (시계열 기상모델을 이용한 열적 위험확률 기반 동적 송전용량의 예측)

  • Kim, Dong-Min;Bae, In-Su;Cho, Jong-Man;Chang, Kyung;Kim, Jin-O
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.7
    • /
    • pp.273-280
    • /
    • 2006
  • This paper suggests the method that forecasts Dynamic Line Rating (DLR). Thermal Overload Risk Probability (TORP) of the next time is forecasted based on the present weather conditions and DLR value by Monte Carlo Simulation (MCS). To model weather elements of transmission line for MCS process, this paper will propose the use of statistical weather models that time series is applied. Also, through the case study, it is confirmed that the forecasted TORP can be utilized as a criterion that decides DLR of next time. In short, proposed method may be used usefully to keep security and reliability of transmission line by forecasting transmission capacity of the next time.

A Study on Electrical Fire of Small Ventilators due to Aged Degradation (경년열화에 의한 소형 환풍기의 전기화재에 관한 연구)

  • Lim, Jong Yong;Lee, Sung Ill
    • Journal of the Korean Society of Safety
    • /
    • v.31 no.4
    • /
    • pp.22-26
    • /
    • 2016
  • "Always-on" small ventilators are likely to experience thermal decomposition of insulating material due to thermal, electrical, mechanical and environmental influences, and lose insulating properties by the process of oxidation and physiochemical reaction. This increases the risk of electrical fire because of layer short, short circuit, overload and Plastics are usually used to make ventilator and ventilator enclosures since they make less noise and are cheaper. Although more preferred than iron, plastic, a combustible material, has a higher risk of fire. In this study, several experiments were carried out to find out how RCD(Residual Current Protective Device) and Thermal fuses, which are electric motor protection devices, work and what needs to be done to reduce the risk of fire.

The Characteristic of Temperature in Ventilating Fans by Festraint or Nonrestraint (무 구속·구속 실험에 의한 환풍기 온도 특성)

  • Kim, Sung-Sam
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.30 no.1
    • /
    • pp.44-48
    • /
    • 2016
  • In this paper, we analyzed the operating characteristics of a ventilating fan due to overload and overheating. The experiment assumed the forcible restraint of the blade due to external objects and the aging process. We analyzed the experimental temperature and operating characteristics of the three places in the interior of the ventilating fan. As a result of the analysis, the temperature distribution was highest to lowest in the following order: the thermal fuse, the motor inside, and the above winding. There was smell of burning enamel in the restraint experiment. Following the thermal fuse operation, the insulation of motor winding was good. In the case of rated voltage and new ventilating fan restrained for about 4hours, and the results of restraint experiments in the presence or absence of the thermal fuse, no risk of deformation or fire due to overheating was identified. Henceforward, ignition hazard experiments will be required for additional factors of aging, pollution, and defective insulation.

Analysis of Thermal Characteristics for the Fire Risk Assessment According to Partial Disconnection on the VCTF and IV Electric Wire (VCTF와 IV전선의 반단선에 의한 화재위험성 평가를 위한 열적특성 해석)

  • Kim, Doo-Hyun;Kim, Sung-Chul;Lee, Jong-Ho;Park, Jong-Young;Park, Young-Ho;Lee, Hyung-Jun
    • Journal of the Korean Society of Safety
    • /
    • v.23 no.4
    • /
    • pp.47-52
    • /
    • 2008
  • Many researches on fire risk for normal electric wiring have been pursued in advanced countries such as the USA and Japan, but comparative studies of the partial disconnection and normal state of electric wires have not been conducted. Detection system for the cause of partial disconnection is not developed and prevention countermeasure for electrical fire by the cause is not effective. Therefore, in this paper, partial disconnection characteristics on electric wires were derived and analyzed by experiment and electrical-thermal finite element method(Flux 3D) on the model wires which consist of VCTF(PVC insulated PVC sheathed Cap Tyre Flexible Cord, KS C 3304) and IV(lndoorwire PVC, KS C 3302). VCTF is used in wiring portable electric appliances and the IV is used indoors. Interrelationships between partial disconnection premonitory symptom and current were derived and analyzed by the characteristics based on experiments and thermal analysis for electric wire according to current under normal state and 200% overload state of rated current.

Analysis of the Risk of Heat Generation due to Bolt Loosening in Terminal Block Connector Parts (볼트풀림에 의한 터미널 블록의 접속부 발열 위험성 분석)

  • Yeon, Yeong-Mo;Kim, Seung-Hee
    • Fire Science and Engineering
    • /
    • v.34 no.3
    • /
    • pp.67-75
    • /
    • 2020
  • In this study, the risk of heat generation due to normal and overload currents that vary with the abnormal loosening angle of wire-connecting bolts were identified. The risks were analyzed based on the thermal characteristics to minimize the carbonization accidents of terminal blocks inside distribution panels typically used in industrial sites. We applied a method for measuring the heating temperature and temperature variations in the terminal blocks in real-time by installing a resistance temperature detector sensor board in the terminal block. The experimental results showed that the terminal block model with a low-rated current exhibited a higher heating temperature, thus, confirming the need to select the terminal block capacity based on load currents. Additionally, the higher the rated current of the terminal block with a high-rated current and the higher the degree of loosening, the faster the carbonization point. Such heating temperature monitoring enabled real-time thermal temperature measurement and a step-by-step risk level setting through thermal analysis. The results of the measurement and analysis of carbonization risks can provide a theoretical basis for further research regarding the risk of fire due to carbonization. Furthermore, the deterioration measurement method using the temperature sensor board developed in this study is widely applicable to prevent fires caused by poor electrical contact as well as risk-level management.

Prediction of Dynamic Line Rating by Time Series Weather Models (시계열 기상 모델을 이용한 동적 송전 용량의 예측)

  • Kim, Dong-Min;Bae, In-Su;Kim, Jin-O;Chang, Kyung
    • Proceedings of the KIEE Conference
    • /
    • 2005.11b
    • /
    • pp.35-38
    • /
    • 2005
  • This paper suggests the method that forecast Dynamic Line Rating (DLR). Thermal Overload Risk (TOR) of next time is forecasted based on current weather condition and DLR value by Monte Carlo Simulation (MCS). To model weather element of transmission line for MCS, we will propose the use of weather forecast system and statistical models that time series law is applied. Also, through case study, forecasted TOR probability confirmed can utilize by standard that decide DLR of next time. In short, proposed method may be used usefully to keep safety of transmission line and reliability of supply of electric Power by forecasting transmission capacity of next time.

  • PDF

A Study on Utilization Ratio and Operation of Transmission Lines (송전선로의 이용률 평가 및 합리적 운영에 관한 연구)

  • Kim, Dong-Min;Bae, In-Su;Cho, Jong-Man;Kim, Jin-O
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.10
    • /
    • pp.426-432
    • /
    • 2006
  • This paper describes the concepts of Static Line Rating (SLR) and Dynamic Line Rating (DLR) and the computational methods to demonstrate them. Calculation of the line capacity needs the heat balance equation which is also used for computing the reduced tension in terms of line aging. SLR is calculated with the data from the worst condition of weather throughout the year. Even now, the utilization ratio is obtained from this SLR data in Korea. DLR is the improved method compared to SLR. A process for DLR reveals not only improved line ratings but also more accurate allowed line ratings based on line aging and real time conditions of weather. In order to reflect overhead transmission line aging in DLR, this paper proposes the method that considers the amount of decreased tension since the lines have been installed. Therefore, the continuous allowed temperature for remaining life time is newly acquired. In order to forecast DLR, this paper uses weather forecast models, and applies the concept of Thermal Overload Risk Probability (TORP). Then, the new concept of Dynamic Utilization Ratio (DUR) is defined, replacing Static Utilization Ratio (SUR). For the case study, the two main transmission lines which are responsible for the north bound power flow in the Seoul metropolitan area are chosen for computing line rating and utilization ratio. And then line rating and utilization ratio are analyzed for each transmission line, so that comparison of the present and estimated utilization ratios becomes available. Finally, this paper proves the validity of predictive DUR as the objective index, with simulations of emergency state caused by system outages, overload and so on.