• 제목/요약/키워드: Theoretical grounding

검색결과 36건 처리시간 0.026초

임펄스전류에 의한 매설지선의 과도임피던스특성에 대한 모의해석 (Simulated Analysis for the Transient Impedance Behaviors of Counterpoises Subjected to the Impulsive Currents)

  • 조정현;이복희
    • 전기학회논문지
    • /
    • 제58권10호
    • /
    • pp.1861-1868
    • /
    • 2009
  • A ground electrode subjected to lightning surge current shows the transient impedance behaviors. The ground electrode for protection against lightning should be evaluated in view of the transient grounding impedance and conventional grounding impedance, not ground resistance. The transient impedance characteristics of ground electrodes are influenced by the shape of ground electrode and the soil characteristics, as well as the waveform of lightning surge current. In order to propose a simulation method of analyzing the transient impedance characteristics of the grounding system in practical use, this paper suggests a theoretical analysis method of distributed parameter circuit model to simulate the transient impedance characteristics of counterpoise subjected to lightning surge current. EMTP and Matlab programs were employed to compute the transient grounding impedances of three counterpoises with different lengths. As a consequence, the simulated results using the proposed distributed parameter circuit model are in good agreement with the measured results.

매설지선 방식을 적용한 에너지 자립마을용 수상 태양광 발전 시스템의 접지저항 분석 (Analysis of Grounding Resistance for Zero Energy Town Floating PV System Using Underground Wiring)

  • 고재우;임종록;;차혜림;김시한;이창구;안형근
    • 한국전기전자재료학회논문지
    • /
    • 제29권5호
    • /
    • pp.303-306
    • /
    • 2016
  • Floating PV system is installed on the water such as artificial lake, reservoir, river for the purposes of zero energy town and/or large scale of PV station. There are electrical gains from cooling effect by water and reflection of water surface. Particularly, floating PV power station with high efficiency solar cell modules receives a lot of attention recently. Floating PV system is installed on the water, which means grounding method to the frame of solar cell and electrical box such as connector band and distribution panelboard should be applied in different way from grounding method of PV system on land. The grounding resistance should be 10[${\Omega}$] in case the voltage is over 400[V] in accordance with Korean Standard. The applicable parameters are the resistivity of water in various circumstances, depth of water, and length of electrode in order to meet 10[${\Omega}$] of grounding resistance. We calculated appropriate length of the electrode on the basis of theoretical equation of grounding resistance and analyzed the relation between each parameters through MATLAB simulation. This paper explains grounding system of floating PV power station and presents considerations on grounding design according to the resistivity of water.

낙뢰침입에 의한 대지전위상승이 발전소 저압전원회로에 미치는 과전압 해석 (Transient Voltage Analysis of Low-Voltage Source Circuit inn Thermal Power Plant due to Grounding Potential Rise by Lightening)

  • 양병모;정재기;민병욱;이종석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 E
    • /
    • pp.1644-1646
    • /
    • 1998
  • High-Smokestacks have been the symbol of the thermal power plant. Those cause the thermal power plant to be damaged by lightening for reaching several hundreds meter. In this paper, we investigated the accident of low-voltage source circuit due to grounding potential rise by lightening via high-smokestack in practically driving power plant, described examination into the cause and the impulse analysis. We analysed the transient voltage by EMTP(ElectroMagnetic Transient Program) via modeling the grounding system of power plant. This theoretical results coincided with practical accidental state. Therefore, it was verified that we could apply the grounding system of power plant and substation with the distribution-circuit analysis(EMTP).

  • PDF

Theoretical Grounding of Perceived Risk in Adoption of Mobile Payment System and Behavioural Intention

  • Bharti Ramtiyal;Deepak Verma;Ajay Pal Singh Rathore
    • Asia pacific journal of information systems
    • /
    • 제31권4호
    • /
    • pp.543-574
    • /
    • 2021
  • This study focuses on a better understanding of the importance of risk perception in adopting Mobile Payment Systems (MPS) by conducting a systematic literature review. From the social science field (using Scopus and Web of Science database) articles were selected. Overall, forty-four significant pieces were determined using a systematic methodology. In addition to providing a summary of the most used theories used to address perceived risk in MPS this paper also investigates the definition for the perceived risk in MPS literature. The study is performed through the identification of dominant theories used to explain perceived risk in the literature. The article gives a thematic analysis of theories and the relation of perceived risk with behavioural intention. As far as we know, this is the first effort of its kind to give a holistic, systematic literature review in light of perceived risk in MPS. Consequently, it is a crucial first step in establishing a solid theoretical framework involving the constructs of perceived risk and laying the groundwork for future research in this area.

봉상 접지전극 상호간의 전위간섭에 대한 평가 (Evaluations on the Potential Interferences between Ground Rods)

  • 이복희;이수봉;이태형;정현욱;길형준
    • 조명전기설비학회논문지
    • /
    • 제20권5호
    • /
    • pp.92-98
    • /
    • 2006
  • 본 논문은 봉상접지전극 주변에서 접지전극간 전위간섭에 대해 다루었다. 접지전극 상호간의 전위간섭을 저감하는 기법을 제안하기 위해서 실규모 접지전각에서 발생될 수 있는 대지전위와 전위간섭을 이론적 해석과 축소모델 실험을 이용하여 실험적으로 분석하였다. 반구형 수조모의접지 실험장치로 접지전극 상호간 이격거리에 따른 전위 상승과 전위간섭계수를 측정하고, CDEGS 소프트웨어를 이용하여 이들 현상을 해석하였다. 그 결과 전위상승과 전위간섭계수는 접지전극의 이격거리에 강하게 의존하였으며, 실측결과는 이론적 계산결과와 잘 일치는 결과를 얻었다.

매설지선의 접지임피던스의 주파수의존성에 대한 모사기법 (A Method of Simulating the Frequency-dependent Ground Impedance of Counterpoises)

  • 이복희;신희경;성창훈
    • 조명전기설비학회논문지
    • /
    • 제26권3호
    • /
    • pp.73-79
    • /
    • 2012
  • A counterpoise is commonly employed in grounding systems installing near the ground surface of low resistivity soils and radial-type counterpoises are used in the limited space. Recently some studies on the evaluation of ground impedance of paralleling ground electrodes have carried out, but the data for providing the frequency-dependent ground impedances considering potential interferences are not yet sufficient. In order to provide the information about the design of grounding systems for surge protection, the simulations of the frequency-dependent ground impedance of various shaped counterpoises are carried out by using the distributed parameter circuit model including the effect of potential interferences. This paper presents the theoretical simulations and actual experiments of the frequency-dependent ground impedance of paralleling and 3 or 4-arms star counterpoises. The accuracy of the simulation methodology is examined by the comparison with the measured results, and the results show a good agreement between the simulation and the experiment.

접지임피던스에 대한 접지봉 크기의 영향 분석 (The Analysis for the grounding impedance influenced by the ground rod's dimension)

  • 이복희;조정현;신희경;이강수;황등과;김정철
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2008년도 추계학술대회 논문집
    • /
    • pp.333-336
    • /
    • 2008
  • This paper resents a theoretical analysis for the grounding impedance influenced by the ground rod's dimension using the distributed parameter model. In this paper, EMTP and Matlab Program were used to simulate the distributed parameter model and to analyze the frequency-dependent characteristics of the ground rods. We compared two kinds of ground rods having different dimensions and the frequency-dependent characteristics of two ground rods were quite different from each other. It is estimated that these different characteristics are caused by the distributed parmeters which are changed by the length of ground rod.

  • PDF

제주-해남 HVDC 시스템에서 클리폰 릴레이 오동작 분석에 관한 연구 (A Study on the Analysis of Klippon Relay Malfunction in Cheju-Heanam HVDC System)

  • 김찬기;박종광;최영도
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2005년도 전력전자학술대회 논문집
    • /
    • pp.173-175
    • /
    • 2005
  • Malfunction of Klippon relay in Cheju-Haenam HVDC system has been caused by the inflow of high voltage arc. In this paper, we have studied on the theoretical examination and data analysis of Klippon relay, and the countermeasures against the problems were suggested according to their causes. Grounding problem in Klippon relay is removed by one-point earth connection and by modification of grounding circuit. The effects of over current surge was removed by attaching blocking diodes by series In Klippon relay to remove surge input in Klippon relay's mercury contact. The problem of Induced overvoltage by 86re1ay excitation coil, was removed by attaching Free-wheeling diode in parallel with the excitation coil of Lock-out relay.

  • PDF

Deep learning classifier for the number of layers in the subsurface structure

  • Kim, Ho-Chan;Kang, Min-Jae
    • International journal of advanced smart convergence
    • /
    • 제10권3호
    • /
    • pp.51-58
    • /
    • 2021
  • In this paper, we propose a deep learning classifier for estimating the number of layers in the Earth's structure. When installing a grounding system, knowledge of the subsurface in the area is absolutely necessary. The subsurface structure can be modeled by the earth parameters. Knowing the exact number of layers can significantly reduce the amount of computation to estimate these parameters. The classifier consists of a feedforward neural network. Apparent resistivity curves were used to train the deep learning classifier. The apparent resistivity at 20 equally spaced log points in each curve are used as the features for the input of the deep learning classifier. Apparent resistivity curve data sets are collected either by theoretical calculations or by Wenner's measurement method. Deep learning classifiers are coded by Keras, an open source neural network library written in Python. This model has been shown to converge with close to 100% accuracy.

매설지선의 유효길이 산정에 관한 이론적 해석 (Theoretical Analysis of Determination of Effective Length of Counterpoise)

  • 이복희;김정철;김종호;유재덕;김동규
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.1420_1422
    • /
    • 2009
  • Lightning currents are one of major influences on the dynamic performance of counterpoise. High lightning current causes the dynamic grounding performance of counterpoise due to very fast fronted pulses. The previous analysis has often been based on quasi-static approximation that can not be applicable to very fast fronted pulses. To extend the analysis for fast fronted pulses in this paper, the full-wave analysis method based on the rigorous electromagnetic-field theory approach is used and the effects of the ionization of the soil are disregarded. Based on the simulation results, the empirical formulas applicable for slow and fast fronted lightning current pulses are reviewed; therefore, the validity of the theoretical approach is verified through comparison between the calculated and measured results.

  • PDF