• 제목/요약/키워드: Surge immunity

검색결과 15건 처리시간 0.02초

누전차단기의 EMC 조합서지 내성 강화를 위한 방안 (The Method of Reinforcing the Immunity of Residual Current Circuit Breaker for the EMC Composite Surge)

  • 김재철;한윤탁;김언석;설규환;강장규;문종필
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제55권8호
    • /
    • pp.322-328
    • /
    • 2006
  • In this paper, The impulse un-tripping characteristics and the electro magnetic compatibility characteristics are compared with each other. The performance of impulse un-tripping test exists at domestic standard (KSC 4613). However test items are insufficient because the more test items such as EMC exist at international standard (IEC). Also, Electric Appliances Safety Certificate has taken the certificate test since July 2004 in Korea but did not confirm the EMC performance for RCCBs made in Korea. Thus, in this paper, We experiment with Oscillatory waves immunity test and the 7 EMC tests for 32 RCCBs of 4 types (mini, home standard, plug, outlet) for 16 brands according to IEC standard 61009-1 and 61008-1. As a result, 24 RCCBs proved to be poor for surge immunity test. However the RCCBs operating incorrectly for surge immunity test operate correctly for oscillatory waves immunity test. Thus, the correlation between oscillatory waves immunity test and EMC test is little and standard for compatibility of combination surge at IEC 61000-4-5 should be added to KS standard as soon as possible.

EUT와 서지 발생기 사이의 거리가 서지 내성 시험에 미치는 영향 (An effect of length between the EUT and surge generator in surge immunity test)

  • 이주광;임순재
    • 한국전자파학회지:전자파기술
    • /
    • 제6권4호
    • /
    • pp.57-61
    • /
    • 1995
  • 일반적으로 서지발생기의 출력은 전원선을 통하여 피시험기에 전달된다. 이 논문에서는 전원선의 길이에 따라 전달되는 서지의 감쇄량을 이론적, 실험적으로 조사하였다. 서지출력은 전원선에 의해 비례적으로 감쇄되어 40m 전원선을 사용할 경우에 77%의 서지에너지만이 피시험기에 전달되었다.

  • PDF

전지관리장치(BMS)의 서지내성 성능향상 기법 (Surge Immunity Performance Enhancement Techniques on Battery Management System)

  • 김용성;임성정;서우현;정중일
    • 전기학회논문지
    • /
    • 제64권1호
    • /
    • pp.196-200
    • /
    • 2015
  • The switching noise in the power electronics of the power conversion equipment (Power Conditioning System) for large energy storage devices are generated. Since the burst-level transient noise from being generated in the power system at a higher power change process influences the control circuit of the low voltage driver circuit. Noise may cause the malfunction of the control device even if no dielectric breakdown leads to a control circuit. To overcome this, this paper proposes the installation of an additional nano-surge protection device on the power supply DC output circuit of the battery management unit.

광 LAN을 적용한 765kV변전소 감시제어 시범시스템 설계 (Prototype design of fiber optics based 765kV substation control system)

  • 송인호;박종화;최종협
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 1996년도 한국자동제어학술회의논문집(국내학술편); 포항공과대학교, 포항; 24-26 Oct. 1996
    • /
    • pp.996-999
    • /
    • 1996
  • This paper introduces prototype design of 765kV Substation control system based on fiber optics LAN and distributed network protocol. Two major important facts, immunity of any surge which frequently occurs in Ultra High Voltage Substation and the most suitable communication protocol for substation control system, are considered on the system design conception. To meet the first fact, use of fiber optics cable and isolation transformer are considered, and to satisfy the second fact, DNP3.0(Distributed Network Protocol) which is IEC870-5 compatible is adopted.

  • PDF

정밀기기의 낙뢰서지 대책에 관한 연구 (Protecting electronic equipment against lightning surge)

  • 임순재;이주광;이완규;최만용
    • 한국정밀공학회:학술대회논문집
    • /
    • 한국정밀공학회 1995년도 춘계학술대회 논문집
    • /
    • pp.358-362
    • /
    • 1995
  • Precision electronic equipments are composed of sophisticated microcircuits that are extremely vulnerable to lightning-caused voltage spike. This transient voltage spike may cause upset, latent failure or interference on electronic equipments. In order to develop efficient lightning protection measures on AC power lines for a road traffic controller, experimental surge immunity tests were conducted according to IEC standard 801-5. The combination of gas tube arrester and metal-oxide varistor was installed at the input of AC power lines and the silicon avalanche suppressor installed at the output of DC power supply as lightning protection measures.

  • PDF

서지전류에 의한 누전차단기의 의도하지 않은 트립에 대한 신뢰성 (Reliability on the Unintended Trips of Residual Current Operated Circuit Breakers due to Surge Currents)

  • 이복희;김상현;김유하
    • 조명전기설비학회논문지
    • /
    • 제26권5호
    • /
    • pp.79-84
    • /
    • 2012
  • As the huge economical loss and function paralysis of information technology-based systems can be caused by the misoperation of residual current devices(RCDs) due to surge voltages and currents, RCDs shall not operate by surge currents. In this paper, in order to evaluate the reliability of residual current operated circuit-breakers with integral overcurrent protection for household and similar uses((RCBOs) stressed by surges, the unintended trip characteristics of RCBOs under surge currents were experimentally investigated using the combination wave generator. Seven different types of single-phase RCBOs being present on the domestic market were investigated according to KS C IEC 61009-1 standard. As a result, all kinds of specimens were satisfied the requirements for 0.5 [${\mu}s$]/100[kHz] ring wave impulse currents. Most of specimens stressed by the 8/20[${\mu}s$] impulse current tripped at least one or more, and some of them were broken down during consecutive tests. It was found that only one type of specimens meets the L-N mode immunity to the combination wave of 1.2/50[${\mu}s$] impulse voltage and 8/20[${\mu}s$] impulse current.

옥외용 전자장비의 낙뢰 서지 대책 (Protecting electronic equipment against lightning surge)

  • 임순재;이주광;이완규;최만용
    • 한국안전학회지
    • /
    • 제12권1호
    • /
    • pp.29-36
    • /
    • 1997
  • Precision electronic equipments for outdoor use are composed of sophisticated microcircuits that are extremely vulnerable to lightning-caused voltage spike. This transient voltage spike may cause upset, latent failure or Interference on electronic equipments. In order to develop efficient lightning protection measures on AC power lines of a road traffic controller as a electronic equipment for outdoor use, experimental surge immunity tests were conducted according to IEC standard 801-5. The combination of gas tube arrester and metal-oxide varistor was installed at the input of AC power lines and the silicon avalanche suppressor installed at the output of DC power supply for the lightning protection measures.

  • PDF

조명기기의 임펄스내전압 성능의 분석 (Analysis of Impulse Withstand Voltage Performance of Lighting Equipment)

  • 이복희;방평호
    • 조명전기설비학회논문지
    • /
    • 제28권3호
    • /
    • pp.91-96
    • /
    • 2014
  • Modern electronic circuits are becoming more vulnerable to damage by surges, and it is required to improve the impulse withstand voltage performance of electrical and electronic equipment. This paper presents the impulse withstand voltage performance of lighting equipment connected to power lines, and the impulse withstand voltage tests for fluorescent lamp, LED lamp and halogen lamp were carried out according to the reference standards under normal service conditions. To conduct performance tests against lightning surge, a combination wave ($1.2/50{\mu}s$ voltage - $8/20{\mu}s$ current) was employed. The test surge was applied between lines or between line and ground of the specimen to be measured. The test surge was applied synchronized at the peak value of the positive and negative AC voltage waves. As a consequence, some specimens satisfied the impulse withstand voltage test criteria, but lighting equipment such as 36W fluorescent lamps, 5W and 5.5W LED lamps and 50W halogen lamp were damaged at the test voltage levels between power lines. It is needed to improve the qualities of lighting equipment to satisfy EMC immunity requirements of equipment for general lighting purposes.

Assessing the risk of recurrence of porcine epidemic diarrhea virus in affected farms on Jeju Island, South Korea

  • Jang, Guehwan;Lee, Sunhee;Lee, Changhee
    • Journal of Veterinary Science
    • /
    • 제22권4호
    • /
    • pp.48.1-48.15
    • /
    • 2021
  • Background: Porcine epidemic diarrhea virus (PEDV) is a swine enteropathogenic coronavirus that has devastated the swine industry in South Korea over the last 30 years. The lack of an effective method to control the endemics has led to a surge in PEDV recurrences in affected farms throughout the country. Objectives: In the first step toward establishing systematic monitoring of and active control measures over the swine populations, we constructed an assessment model that evaluates the status of (1) biosecurity, (2) herd immunity, and (3) virus circulation in each of the PEDV-infected farms. Methods: A total of 13 farrow-to-finish pig farms with a history of acute PEDV infection on Jeju Island were chosen for this study. The potential risk of the recurrence in these farms was estimated through on-site data collection and laboratory examination. Results: Overall, the data indicated that a considerable number of the PEDV-infected farms had lax biosecurity, achieved incomplete protective immunity in the sows despite multi-dose vaccination, and served as incubators of the circulating virus; thus, they face an increased risk of recurrent outbreaks. Intriguingly, our results suggest that after an outbreak, a farm requires proactive tasks, including reinforcing biosecurity, conducting serological and virus monitoring to check the sows' immunity and to identify the animals exposed to PEDV, and improving the vaccination scheme and disinfection practices if needed. Conclusions: The present study highlights the significance of coordinated PEDV management in infected farms to reduce the risk of recurrence and further contribute towards the national eradication of PEDV.

전자파 대응 단위세대 분전반의 설계 및 제작 (Design and Fabrication of a Home-panel Board for Electromagnetic Compatibility)

  • 길경석;송재용;이종혁;권장우;송동영
    • 조명전기설비학회논문지
    • /
    • 제14권6호
    • /
    • pp.18-25
    • /
    • 2000
  • 본 논문에서는 과도전압과 전원선 방해파로부터 가전기기틀 안전하게 보호할 수 있는 전자파 대용 단위세대 분전반의 설계 및 제작에 대하에 기술하였다. 제안한 분전반은 바리스터, 캐패시터 및 간선도채의 인덕턴스로 구성한 과도전업 차단장치와 전자파 필터를 내장하고 있다. 시제작한 분전반은 IEC 규격의 조합형 서지 발생장치와 회로밍 분석키를 이용하여, 과도전압에 대한차단특성과 전원선 방해파의 감쇠특성을 평가하였다. 실험 결과로부E] 본 연구에서 제안한 분전빈은 IEC 61000-4-5에 규정한 서지내생기준을 만족하였으며, 150[kHz]-30[MHz] 대역의 전원선 방해파에 대해 20[dB] 이상의 감소효과를 나타내었다.

  • PDF