• Title/Summary/Keyword: Substations

Search Result 295, Processing Time 0.025 seconds

A Novel Non-contact Measurement Method for the Detection of Current Flowing Through Concealed Conductors

  • Yang, Fan;Liu, Kai;Zhu, Liwei;Hu, Jiayuan;Wang, Xiaoyu;Shen, Xiaoming;Luo, Hanwu;Ammad, Jadoon
    • Journal of Magnetics
    • /
    • v.22 no.1
    • /
    • pp.43-48
    • /
    • 2017
  • In order to detect the current flowing through concealed conductor, this paper proposes a new method based on derivative method. Firstly, this paper analyzes the main peak characteristic of the derivative function of magnetic field generated by a current-carrying conductor, and a relationship between the current flowing through the conductor and the main peak of the derivative function is obtained and applied to calculate the current. Then, the method is applied to detect the conductor current flowing through grounding grids of substations. Finally, the numerical experimental and field experiment verified the feasibility and accuracy of the method, and the computing results show that the method can effectively measure the conductor current of grounding grids with low error, and the error is within 5 %.

The Study of the Ferrite Transformer Design for the Development of the High-frequency Battery Charger (고주파방식 충전기 개발을 위한 페라이트 변압기 설계에 관한 연구)

  • 안용호;박종광;김상준;윤장완;윤기웅;한병성
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.07a
    • /
    • pp.683-686
    • /
    • 2000
  • The chargers for DC power supply of the contro1lers, which have been installed in the relay rooms in 345/154kV substations of KEPCO, lag in both aspects of technique and performance. Moreover, as they are SCR-based, they dont meet the performance requirements of todays digital and automated controllers. Now two controllers are running in pair and one of those is for reservation. There are lots of troubles because the patrol engineering team has to replace them manually whenever they are out of order. So it is expected to bring convenience if the charger replacement is automated. Also, the existing chargers take much space, weight and cost - which have increased the need of development to make them smaller, less expensive, and have high quality. We will develop a charger system which has one fifth of the weight of the existing system by double-integrating the volume. The new system will be ready for a future full unmanned system with integrated pores for remote control, state-of-the-art digital features, and more than 90% efficiency/power factor against 80% efficiency/power factor of the existing system.

  • PDF

Evaluation of the Application Scheme of SFCL in Power Systems

  • Kim, Jong-Yul;Lee, Seung-Ryul;Yoon, Jae-Young
    • KIEE International Transactions on Power Engineering
    • /
    • v.4A no.4
    • /
    • pp.221-226
    • /
    • 2004
  • As power systems grow more complex and power demands increase, the fault current tends to gradually increase. In the near future, the fault current will exceed a circuit breaker rating for some substations, which is an especially important issue in the Seoul metropolitan area because of its highly meshed configuration. Currently, the Korean power system is regulated by changing the 154kV system configuration from a loop connection to a radial system, by splitting the bus where load balance can be achieved, and by upgrading the circuit breaker rating. A development project applying a 154kV Superconducting Fault Current Limiter (SFCL) to 154kV transmission systems is proceeding with implementation slated for after 2010. In this paper, SFCL is applied to reduce the fault current in power systems according to two different application schemes and their technical and economic impacts are evaluated. The results indicate that both application schemes can regulate the fault current under the rating of circuit breaker, however, applying SFCL to the bus-tie location is much more appropriate from an economic view point.

A Novel Fault Location Scheme on Korean Electric Railway System Using the 9-Conductor Representation

  • Lee, Chang-Mu;Lee, Han-Sang;Yoon, Dong-Hee;Lee, Han-Min;Song, Ji-Young;Jang, Gil-Soo;Han, Byung-Moon
    • Journal of Electrical Engineering and Technology
    • /
    • v.5 no.2
    • /
    • pp.220-227
    • /
    • 2010
  • This paper presents a novel fault location scheme on Korean AC electric railway systems. On AC railway system, because of long distance, 40[km] or above, between two railway substations, a fault location technique is very important. Since the fault current flows through the catenary system, it must be modeled exactly to analyze the fault current magnitude and fault location. In this paper, suggesting the novel scheme of fault location, a 9-conductor modeling technique including boost wires and impedance bonds is introduced based on the characteristics of Korean AC electric railway. After obtaining a 9-conductor modeling, the railway system is constructed for computer simulation by using PSCAD/EMTDC. By case studies, we can verify superiority of a new fault location scheme and propose a powerful model for fault analysis on electric railway systems.

Theoretical and Experimental Analysis of Extremely Low Frequency Magnetic Field in the Vicinity of the Transformer Station of Overhead Power Lines

  • Ghnimi, Said;Rajhi, Adnen;Gharsallah, Ali;Bizid, Youssef
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.4
    • /
    • pp.1655-1662
    • /
    • 2018
  • This paper studies the magnetic fields between the power lines which are finite length and other ones which are infinitely long around the first tower in the proximity of the power transformers. They will be used as a source of disturbance applied to the power line. The method applied in this study was gradual; develop the theoretical formulation of the magnetic fields of these lines which are finite length and other ones which are infinitely long, examine the effects of different couplings between the different neighboring lines and the distribution transformers on behavior of magnetic fields. The method also focused on the experimental results analyzing the magnetic fields which will be used as a source applied to the auditory implants EMC. The theoretical and experimental results were compared and discussed for three power lines (90kV, 150kV and 225kV) near the power station, and it proved the effect of these substations on the simulated and measured results of the magnetic field. The maximum intensities of magnetic fields measured at the height of 1m from the ground for the circuit of three lines close to each substation were significantly lower than the ICNIRP reference levels for occupational and non occupational exposures.

The Prediction of Transformer Noise by Operating Situation at the Indoor Substation (옥내변전소 운전상황에 따른 변압기 소음예측)

  • Koo, Kyo-Sun;Kweon, Dong-Jin;Kwak, Ju-Sik
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.10
    • /
    • pp.104-110
    • /
    • 2008
  • Desire about agreeable habitat by enhancement of standard of living has been increased, and common complaints by transformer noise have been happening constantly. It has been installed resonator and sound-proof shutter in order to solve substation's noise problems. But those methods are not effective. Therefore, It is necessary to study transformer noise level that can satisfy noise regulation standard. In this paper described that predicted transformer noise level of substation boundary by operating situation at the indoor substation. Also, Presented most suitable noise level of transformer that satisfy noise regulation standard at the indoor substations through predicted results.

A Study on the Power Factor Improvement of DC Power Regenerating Systems Using SVPWM (SVPWM을 이용한 직류전력 회생시스템의 역률개선에 관한 연구)

  • Ko, Young-Min;Chae, Soo-Yong;Seo, Young-Min;Jeong, Dae-Taek;Bae, Young-Wook;Hong, Soon-Chan
    • Proceedings of the KIPE Conference
    • /
    • 2007.07a
    • /
    • pp.196-198
    • /
    • 2007
  • In the substations for traction systems and the large-scale discharging system of secondary batteries, the voltage of DC bus line goes up by the regenerated energy and the energy is usually wasted in resistor for system stability. This paper proposes the DC power regenerating system using a three phase PWM inverter. The proposed system can regenerate the excessive DC power from DC bus line to AC supply and control the power factor of AC supply to unity. To implement unity power factor, the magnitude of the inverter output voltage should be higher than that of AC supply and therefore SVPWM technique is adopted. Computer simulations are carried out to verify the validity of the proposed system.

  • PDF

The Temperature Distribution Analysis of Mold transformer (100kVA 주상용 몰드 변압기의 온도분포 해석)

  • Cho, Han-Goo;Lee, Un-Yong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.05b
    • /
    • pp.125-129
    • /
    • 2004
  • The mold transformers have been widely used in underground substations in large building and have some advantages in comparison to oil-transformer, that is low fire risk, excellent environmental compatibility, compact size and high reliability. In addition, the application of mold transformer for outdoor is possible due to development of epoxy resin. The mold transformer generally has cooling duct between low voltage coil and high voltage coil. A mold transformer made by one body molding method has been developed for small size and low loss, but it needs some cooling method because heat radiation between each winding is difficult. The life of transformer is significantly dependent on the thermal behavior in windings. Many transformer designers have calculated temperature distribution and hot spot point by FEM(finite element method) to analyze winding temperature rise. In this paper, the temperature distribution and thermal stress analysis of 100kVA pole cast resin transformer for power distribution are investigated by FEM program.

  • PDF

Breakdown Voltage and PD Characteristics of $SF_6/CF_4$ Mixtures in Nonuniform Field (불평등 전계에서 $SF_6/CF_4$ 혼합가스의 절연내력과 PD특성)

  • Hwang, Cheong-Ho;Sung, Heo-Gyung;Huh, Chang-Su
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.4
    • /
    • pp.635-640
    • /
    • 2008
  • New gas mixtures are now finding applications such as interrupting media for high-voltage circuit breakers. These mixtures consist of a high content of carbon tetrafluoride($CF_4$) added to sulfur hexafluoride($SF_6$). Nowdays $SF_6$ has been established for the use in gas insulated substations due to its high insulation withstand level and good arc quenching capability. At this paper Breakdown characteristics were investigated for $SF_6/CF_4$ mixtures when AC voltage and standard lightning impulse voltage(LI) was applied in a needle-plane electrodes. And partial discharge(PD) experiments were carried out in the test chamber which was made in needle-plane electrode. And ${\Phi}$-Q-N distribution of partial discharge signals was analyzed. The total pressure of the $SF_6/CF_4$ mixtures was varied within the range of 0.1-0.5 Mpa in the test chamber. The breakdown voltage in needle-plane electrode displayed N shape characteristics for increasing the content of $SF_6$ at positive impulse voltage and the PD inception voltage was increased slightly when pressure of $SF_6/CF_4$ Mixtures was increased. Maximum PD inception voltage is showed in 80% SF6/20%$CF_4$.

The Implementation of IED for Diagnosis of Electric Devices (전력 설비 진단을 위한 IED 의 구현)

  • Oh, Jae-Hoon
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.1110-1111
    • /
    • 2007
  • These days, the concerns about maintenance and repair of electric facilities for stable and reliable electric power supply are increasing day by day. Because, we can have enormous damages economically and socially from a problem of the facilities, no matter how it is a small one. Especially, electric facilities in our country had been built abruptly from 40 years ago, so it can be thought that here are great amount of old facilities that must be repaired or replaced with new one, and the number would be increased time by time. On this situation, many researchers are studying the efficient and reliable method of maintenance for electric facilities and the results are applied on the facilities gradually by growing interests of operators and managers of the facilities. In this paper, the IED(Intelligent Electronic Devices) for Diagnosis system of electric machines are described. It takes analog data from a sensing device and operates digital processor to get a optimum digital data for diagnosis system. Now, this device is applied on several high voltage substations to diagnose and maintain GIS. Brief schematic of total diagnosis system and the construction of the IED are included in this paper.

  • PDF