A Study on velocity Characteristics in a staggered tube array (엇갈림 원주열 주위의 속도 특성에 관한 연구)

  • Bae, Bong-Gap;Park, Chan-Su;Cho, Dae-Hwan
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2006.06a
    • /
    • pp.291-292
    • /
    • 2006
  • This experimental study investigates the wake flow behind the flow characteristics around staggered tube arrays. In this experiment, the principal aim is to investigate the transition mechanism of the large vortex generating process in the wake having unique vortex shedding pattern. The detailed visualization is carried out using the PIV measurement. The transition mechanism of the large generating vortex is clarified by showing the streak lines. the vorticity and the statistical fluctuating velocity distributions.

  • PDF

The Convective Heat Transfer for the Flow Perpendicular to the Tube Array (튜브배열 방향과 수직한 유동에 의한 관외 대류 열전달)

  • Jeon Yong-Han;Kim Jong-Yoon;Kim Nam-Jin;Kim Chong-Bo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.8
    • /
    • pp.656-663
    • /
    • 2006
  • The convective heat transfer on the outer surface of tube arrays perpendicular to the flow direction was experimentally investigated. The test sections which include the aligned and staggered arrangements were made and the local heat transfer coefficients on the outer surface of the tube were measured after the flow has been fully developed. The results showed that the local heat transfer coefficients of the staggered arrangement, which has transverse pitch of 0.075 m and longitudinal pitch of 0.08 m, were about 15% greater than that of the aligned arrangement. Also, the overall mean Nusselt number of the former was greater than that of the latter. It is verified that the results obtained by using the simulation show the same tendency with those of experiment.

A Study on the Performance of a Cross-Flow Beat Exchanger by Tube Array Change (튜브배열 변화에 따른 직교류형 열교환기의 성능에 관한 연구)

  • Jeon Yong-Han;Kim Nam-Jin;Kim Chong-Bo
    • Journal of Energy Engineering
    • /
    • v.15 no.1 s.45
    • /
    • pp.28-34
    • /
    • 2006
  • The convective heat transfer on the outer surface of tube arrays perpendicular to the flow direction was experimentally investigated. The test sections which include the aligned and staggered arrangements were made and the local heat transfer coefficients on the outer surface of the tube were measured after the Hour has been fully developed. The results showed that the local heat transfer coefficients of the staggered arrangement, which has transverse pitch of 0.075 m and longitudinal pitch of 0.08 m, were about 15% greater than that of the aligned arrangement. Also, the overall mom Nusselt number of the former was greater thu that of the latter.

A Study on the Flow Characteristics around Cooling Tubes of Fan Coil Unit for Ship (선박용 팬코일장치 냉각관 주위의 유동특성에 관한 연구)

  • Bae, Bong-Gap;Choi, Keom-Ran;Ro, Byeong-Su
    • Journal of the Korean Society of Marine Environment & Safety
    • /
    • v.15 no.2
    • /
    • pp.151-156
    • /
    • 2009
  • This experimental study investigated in to the flow characteristics around staggered cooling tube arrays of fan coil unit for ship. A particle image velocimetry technique was employed to obtain detailed measurements at inlet-velocity-based Reynolds numbers of $Re=1.5{\times}10^3{\sim}Re=2.5{\times}10^3$. As for the results, the flow evolves rapidly and becomes spatially periodic in the streamwise direction after a relatively short distance. The flow exhibits strong Reynolds number dependence in developing region but no significant Reynolds number effects are observed in spatially periodic region.