• Title/Summary/Keyword: Smoke protection

Search Result 185, Processing Time 0.018 seconds

연기와 연기감지기술에 대한 고찰

  • Lee, Bok-Yeong
    • Fire Protection Technology
    • /
    • s.15
    • /
    • pp.28-38
    • /
    • 1993
  • This report is explain the nature of smoke and the principle of smoke detection. The object of this research is to understand the hazard of smoke and select the optimum smoke detectors, according to the types of smoke and the particle size of smoke produced by fire

  • PDF

Simulation Study of Smoke Control Accordance with Zoning in the Atrium Space of High-rise Buildings (초고층 건물 아트리움 공간에서의 제연구획에 따른 시뮬레이션 연구)

  • Ryu, Hyungkyou;Bae, Sanghwan;Lee, Byungseok
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.26 no.7
    • /
    • pp.335-342
    • /
    • 2014
  • The big issue in fire and life safety protection in atriums is that hot smoke can spread vertically via the atrium openings, and impact atrium floors remote from the fire. Three different strategies to provide fire and life safety protection for atrium space were evaluated in this study, using the FDS model. Strategy A is the atrium protection approach addressed in the Korean Building Fire Protection Code, where atria are required to be enclosed with fire shutters from the $2^{nd}$ floor to the atrium top, and the ground floor is allowed to open to the atrium; in this case, no smoke control is required. Strategy B is the atrium protection approach, with smoke control provided in accordance with NFPA 92B; in this case, no atrium floor is enclosed. Strategy C is the atrium protection approach, in which some of the upper atrium floors are enclosed (the case of the top atrium floor being enclosed is evaluated in this study), and atrium smoke control is also provided to protect the lower atrium floors.

Numerical Investigation on Fire of Stage in Theater: Effects of Natural Smoke Vent Area and Fire Source Location (공연장 무대부 화재에 대한 전산해석 연구: 자연 배연구 면적과 화원 위치 영향)

  • Park, Min Yeong;Lee, Chi Young
    • Journal of the Korean Society of Safety
    • /
    • v.37 no.1
    • /
    • pp.1-11
    • /
    • 2022
  • This numerical study investigates the effects of the size of the natural smoke vent area (10% and 1% of the floor area) and the location of the fire source (i.e., at the side and center of the stage) on the temperature distribution in the compartment and velocity distribution and mass flow rate of flow through a natural smoke vent for a reduced-scale model of a theater stage. Then, the mass flow rate of outflow through the natural smoke vent in the event of a fire for a real-scale theater stage was examined. The case with the larger natural smoke vent area and central fire source location showed lower temperature distributions and higher mass flow rates of outflow and inflow than the case with the smaller natural smoke vent area and side fire source location. The trends of the temperature distributions were closely related to those of the mass flow rates for the outflow and inflow. Additionally, the case with the larger natural smoke vent area and central fire source location exhibited the most non-uniform flow velocity distribution in all cases tested. A bidirectional flow, in which the outflow and inflow occur simultaneously, was observed through the natural smoke vent. In the event of a fire situation in a real-scale theater stage, it was predicted that the case with the larger natural smoke vent area and central fire source location would have a mass flow rate of outflow that is 43.53 times higher than that of the case with the smaller natural smoke vent area and side fire source location. The present results indicate that the natural smoke vent location should be determined by considering the location in a theater stage where a fire can occur.

Experimental Study on Smoke Production and Smoke Generation in Thermoplastic Resins Based on PP, PMMA, and PVC (열가소성 수지(PP, PMMA, PVC)의 연기생성 및 발생에 관한 실험적 연구)

  • Hwang, Euy-Hong;Choi, Don-Mook
    • Fire Science and Engineering
    • /
    • v.34 no.3
    • /
    • pp.1-7
    • /
    • 2020
  • Due to the complexity and large size of buildings, plastic resin is widely used as a building material. Accordingly, the occurrence of fires caused by plastics is increasing. Due to the nature of plastic resin fires, the amount of damage to properties and human life caused by combustion products such as smoke are large, and these damages are related to smoke production and smoke generation. Therefore, this study reviews smoke measurement methods and laws on domestic buildings and fire services. Experiments were conducted based on three smoke-related test standards (ISO 5660-1, ISO 12136, ASTM E 662). The experiment results indicate a total smoke production and generation by PP, PVC, and PMMA of 43.27, 32.83, and 12.33 ㎡, and 27.855, 9.599, and 6.975 g, respectively.

Analysis of Smoke Behavior in Fire within Real-scale Theater Using FDS: Influences of Fire Curtain and Natural Smoke Vent Area (FDS를 이용한 실규모 공연장 무대 내 화재 시 연기 거동 분석: 방화막 및 자연배출구 면적의 영향)

  • Kim, Jae Han;Lee, Chi Young;Jeong, Lee Gyu;Kim, Duncan
    • Fire Science and Engineering
    • /
    • v.32 no.6
    • /
    • pp.7-14
    • /
    • 2018
  • This study investigated numerically the influences of fire curtain and natural smoke vent area on smoke movement in the stage fire of a theater using FDS (Fire Dynamics Simulator). The dimension of the theater stage was 31 m in width, 34 m in depth, and 32 m in height. The area ratios between the natural smoke vent and stage were approximately 10%, 8%, 5%, and 1%. The gap distance between the fire curtain and proscenium wall was 0.5 m. The fire curtain and natural smoke vent area were observed to affect significantly the behavior of smoke movement to the auditorium and the mass flow rates of inflow and outflow through the natural smoke vent and proscenium opening. In addition, under the same natural smoke vent area, the pressure in the stage with a fire curtain was lower than that without a fire curtain.

A Comparative Study on Domestic and Foreign Standards for Air Supply for the Improvement of a Smoke Control System for High-Rise Buildings (국내 고층건축물의 제연설비 성능 개선을 위한 국내·외 급기량 관련 기준 비교연구)

  • Kim, Hye-Won;Lee, Byeong-Heun;Jin, Seung-Hyeon;Lee, Su-Gak;Kim, Jung-Yup;Kwon, Young-Jin
    • Fire Science and Engineering
    • /
    • v.33 no.4
    • /
    • pp.105-111
    • /
    • 2019
  • In South Korea, smoke control systems are designed according to the fire safety standards NFSC501 and NFSC 501A. However, there is a problem in that the design values are incompatible when measuring the performance of the system after the design construction for calculating the leakage crack area described in the standards. Therefore, we compared the standards for smoke control systems from South Korea, Japan, and the United Kingdom. In South Korea, designs are conducted uniformly according to the NFSC 501A Manual, but in Japan and the United Kingdom, designs consider smoke temperature, duct loss, and fire floor air supply. Furthermore, they use larger values than in South Korea.

Effects of Platycodi Radix on Passive Smoking in Rats (간접흡연에 노출시킨 흰쥐의 폐조직 손상에 대한 길경의 보호효과)

  • Kim, Bum-Hoi
    • Journal of Physiology & Pathology in Korean Medicine
    • /
    • v.26 no.1
    • /
    • pp.40-46
    • /
    • 2012
  • Cigarette smoking is known to be associated with various chronic pulmonary and cardiovascular diseases ranging from inflammation to cancer. Not only first-hand smoke but also second-hand smoke is suggested to be a factor of health risk. This study was to investigate whether Platycodi Radix extract administration would alter oxidative stress in lung leading to protection of cigarette smoke-induced lung damage. Sprague-Dawley rats were randomly divided into 3 groups; Intact, Smoke+PR and Smoke+Vehicle. In Smoke+PR and Smoke+Vehicle group, the exposure to cigarette smoke was performed for 15 min/day for 4 weeks in ventilated smoking chamber. The Platycodi Radix extract and saline were orally administrated to Smoke+PR and Smoke+Vehicle group each. The rats of Intact group were just kept in ventilated chamber without cigarette smoke. After the experiment for 4 weeks, the lung tissues were collected for histological observation and immunohistochemistry. In Results, airspace enlargement and goblet cell hyperplasia were observed after 4 weeks' exposure to cigarette smoke. Whereas, the oral administration of Platycodi Radix extract for 4 weeks reduced airspace enlargement and goblet cell hyperplasia. Moreover, the alterations of BAX/Bcl-2 proteins in lung tissues were observed. These results suggest that Platycodi Radix extract ameliorates lung damage in cigarette smoke-exposed rats and has protective effects on second-hand smoke injury.

Study on the Smoke Density Characteristics of Flame Retardant Sol Manufactured by a Sol-gel Method (졸-겔법으로 제조된 방염제졸의 연기밀도 특성에 관한 연구)

  • Cho, Kyeong-Rae;Lee, Chun-Ha;Kim, Si-Kuk
    • Fire Science and Engineering
    • /
    • v.31 no.3
    • /
    • pp.11-18
    • /
    • 2017
  • In this study, a non-halogen type organic-inorganic hybrid flame retardant sol, which can impart flame resistance to synthesize silicate of inorganic material and silane coupling agent of organic material by a sol-gel method, were newly manufactured. The addition of flame retardant will prevent loss of life in a fire because smoke from the flammability of interior finishing materials used as the construction materials poses a major danger. The smoke density measurement standard based on flame retardant performance standards, experiments were conducted according to the test equipment and procedures of ASTM E 662. The non-flaming mode experiment and the flaming mode experiment were conducted to confirm the performance of the manufactured flame retardant sol. As a result, the manufactured flame retardant sol improved the physical properties and heat resistance of existing flame retardants, and decreased the smoke production of the fire. Therefore, it may be possible to reduce the damage caused by smoke and expand the applications to various interior finishing materials.