• Title/Summary/Keyword: Smoke layer

Search Result 119, Processing Time 0.025 seconds

An Experimental Study of Smoke Movement in Tunnel Fires (터널화재시 연기 거동에 관한 실험적 연구)

  • Lee, Sung-Ryong;Kim, Choong-Ik;Ryou, Hong-Sun
    • Proceedings of the KSME Conference
    • /
    • 2001.06d
    • /
    • pp.121-126
    • /
    • 2001
  • In this study, reduced-scale experiments were conducted to understand smoke movements in tunnel fires with the natural ventilation. The 1/20 scale experiments were conducted under the Froude scaling since the smoke movement in tunnels is governed by buoyancy force. Six cases of experiments(pool diameter is 6.5cm, 7.3cm, 8.3cm, 10cm, l2.5cm and l5.4cm), in which vertical vents positioned 1m from the fire source symmetrically, were conducted in order to evaluate the effect of the vent on smoke movement. In case of heat release rate under 2MW, smoke front reached to the tunnel exit about 20 see delayed with ventilation and the smoke velocity was proportional to the power of the heat release rate. Temperature after the vent was lower than without vent. In case of l5.4cm pool, the temperature difference was about $50^{\circ}C$. It was confirmed that the thickness of smoke layer was maintained uniformly under the 35% height of tunnel through the visualized smoke flow by a laser sheet and the digital camcoder.

  • PDF

A Study on the Evacuation Performance Review for the Office Buildings (업무용 빌딩의 피난 성능 검토에 관한 연구)

  • 오혁진;백승태;김우석;이수경
    • Fire Science and Engineering
    • /
    • v.17 no.3
    • /
    • pp.1-6
    • /
    • 2003
  • In this study, it reviewed about evacuation performance of a specified Office Building. assessment tools is FAST 3.1.7 (Estimation of Flash Over, Estimation of Layer Height Down Flow Time), SIMULEX 32-bit (Estimation of Evacuation Time), JASMINE 3.25d. (Smoke Flow Assessment of a specified time) Result from Fire Scenario # 1, Flash Over is not generated in Compartment. Evacuation Time is estimated 25.2 sec by SIMULEX 32-bit. layer height until this time (25.2 sec) was estimated 2.4 m by FAST 3.1.7. After ignition until this time (25.2 sec), smoke was not release to the a corridor. In consequence, We concluded that people in building are completing the safe evacuation without the damage of smoke. Result from Fire Scenario # 1, Flash Over generated 6 min 33.2 sec in Compartment. Evacuation Time is estimated 1 min 25.5 sec by SIMULEX 32-bit. layer height down flow time is 1 min 40.8 sec by FAST 3.1.7 and 5 min 23 sec by theoretical calculation. Also, total building evacuation time was estimated 2 min 26.6 sec. After ignition until this time (2 min 26.6 sec), smoke released to the a corridor but it amount was few little. Therefore, generated smoke in compartment not effected to the people in buildings.

Evaluation of Smoke Control Performance of Ventilation System Using by Hot Smoke Test (Hot Smoke Test를 이용한 주차장 환기설비의 제연 성능평가)

  • Joung, Suckhwan
    • Journal of Korean Society of Disaster and Security
    • /
    • v.12 no.2
    • /
    • pp.47-56
    • /
    • 2019
  • Recently, in order to overcome the difficulty of entering a fire source due to the occurrence of a large amount of smoke in the event of a fire in a parking lot, it has used that a method of discharge smoke using air supply, exhaust fans and jet fans installed for ventilation of parking lots. In this study, the variation of flow in the smoke layer was observed using CCTV under two conditions, in which only the air supply fan operates and the manned fan operates together, and the temperature around the plume was compared to Albert eq. to assess its suitability as a parking lot ventilation performance evaluation method. As a result, it was found that the smoke layer could be disturbed if the Jet Fan was operated at the same time, which could lead to the possibility of an initial evacuation disturbance. However, the additional operation of the Jet Fan has been confirmed by the observation CCTV that the emission performance is improved, which is believed to help conduct the suppression operation. The temperature around the plume was measured and compared to Alpert eq, and was analyzed to be about $2^{\circ}C$ lower at the center axis of the plume and $9.0^{\circ}C$ higher at 8 m in the direction of the discharge of smoke. The results of temperature measurements around the plume were lower than the maximum temperature expected in AS 4391 and did not exceed the expected temperature risk caused by the experiment. As with these results, the temperature risk from the progression of hot smoke tests is foreseeable, so it will be available as one of the general evaluation methods for assessing smoke control performance in a parking lot without relevant criteria.

Prediction of sprinkler activation time in compartment fire (구획화재에서의 스프링클러 작동시간 예측 연구)

  • 김명배;한용식
    • Fire Science and Engineering
    • /
    • v.10 no.4
    • /
    • pp.13-18
    • /
    • 1996
  • A general description of sprinkler activation time in compartment-fire-generated smoke layers is made. For calculation of the time hot layer temperature is obtained from two-layer zonal model and time constant of sprinkler is measured. Upper-layer thickness at the instant of sprinkler activation is also presented with changes of opening area. The output of the present study provide inputs for the interaction modeling of sprinkler spray and compartment fire environment, which simulates fire suppression phenomena. Futhermore, experiments are performed in mock-up with gasoline pool fire in order to evaluate the reliability of the model.

  • PDF

A Study on the Combustion Characteristics of the Automotive Interior Materials (자동차 내장재의 연소 특성에 관한 연구)

  • Kim, H.;Kang, Y.G.;Park, H.J.
    • Journal of the Korean Society of Safety
    • /
    • v.13 no.2
    • /
    • pp.88-95
    • /
    • 1998
  • Five parts of the automotive interior materials were sampled to determine their combustion characteristics. Oxygen Indexer, Smoke chamber, Differential Scanning Calorimeter(DSC) were used as the analysis apparatus. All LOI values of samples appear less than 21. The combustion phenomena of the interior materials primarily depends on properties of each layer material. The amount of generated smoke are reached the maximum value within 30 - 90sec after ignition. The experimental results of combustion characteristics and DSC of H/Line also indicated that the layer of foam was melt first and it caused the propagation of flame through the sample. The combustion characteristics of multi-layer materials primarily depends on thermal characteristics of single layer material.

  • PDF

The combustion characteristics of vehicle upholsteries

  • Park, Hyung-Ju;Kang, Young-Goo;Kim, Hong
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1997.11a
    • /
    • pp.211-218
    • /
    • 1997
  • Five parts of vehicle upholsteries were sampled to determine its combustion characteristics. Oxygen Indexer, Smoke chamber, Differential Scanning Calorimetry(DSC) are applied as the analysis apparatus. All LOI values of samples appear less than 21. The combustion phenomena of vehicle upholster primarily depends on properties of each layer material. The amount of smoke generated is the experiment reached the maximum value within 30-90sec after ignition. The experimental results of combustion characteristics and DSC of H/Line also indicated that the layer of foam was melt first and it caused the propagation of flame through the sample. The combustion characteristics of multi layer materials primarily depend on thermal characteristic of single layer material.

  • PDF

The Analysis on the Effect of Supply Air Velocities by Location of Supply Air Damper on the Performance Efficiency of the Smoke Exhaust Systems (공기유입구 위치에 따른 유입공기의 풍속이 배연시스템 성능효율에 미치는 영향 연구)

  • Yeo, Yong-Ju;Lim, Chae-Hyun;Kim, Hak-Jung;Kim, Bum-Gyu;Park, Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.24 no.6
    • /
    • pp.20-27
    • /
    • 2010
  • In smoke control systems the amount of air supply is almost the same as that of smoke exhaust. This study analyzed the effect of supply air velocity on the smoke exhaust behavior using FDS tool. The results showed that fire plume can be disheveled by the rapid air velocities developed when the air supply inlet is located near the fire plume. Disheveled smoke caused the rapid descent of smoke layer level and the reduced visibility. To increase the efficiency of smoke exhaust systems supply air inlet should be located sufficiently far from the location of the fire plume.

An Experimental Study of Smoke Movement in Tunnel Fires with a Vertical Shaft (수직갱이 설치된 터널내 화재시 연기거동에 관한 실험적 연구)

  • 이성룡;유홍선;김충익
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.2
    • /
    • pp.135-141
    • /
    • 2004
  • The present paper concerns a smoke movement in a tunnel fire with a vertical shaft. The model tunnel measured 13.4m long, 0.4m wide and 0.4m high. The cross section is 1: 20 of a full scale tunnel. Ethanol was used as a fuel. The fire size in model tests varied from 1.35 kW to 13.37 kW, which corresponds to full scale fires of 2.41 to 23.91 MW. Smoke front velocity and temperatrue were decreased due to the vertical shaft install. Temperature was reduced maximum about 2$0^{\circ}C$ at ceiling and about 23$^{\circ}C$ at vertical position. CO concentration was reduced as the vent width widened. When vent width was more than 15 cm, CO concentration was not reached 100 ppm. Descent degree of the smoke layer was confirmed through the visualization.

Experimental study on smoke-logging phenomenon caused by sprinklers during a compartment fire (구획 화재시 스프링클러에 의한 스모크-로깅현상에 관한 실험적연구)

  • Kwon, Young-Jin;Yoon, Ung-Gi;Seo, Dong-Goo
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2014.11a
    • /
    • pp.121-122
    • /
    • 2014
  • This study contemplated the descending air current from the smoke layers related to the smoke logging phenomenon in the sprinkler applied design for effective evacuation safety design. As a result, database on the average particle diameter, particle velocity and distribution of sprinkling was obtained and the relationship between the water amount and particle diameter was obtained. Also, in relation to descending air current, the movement of smoke layer to the bottom at the descending air current velocity of 0.6m/s was observed and stable descending air current was observed in existence of fire source over 100kW in size.

  • PDF

A Study on the Radiation Effect of the Smoke Movement in Room Fires

  • Jeong, Jin-Yong;Ryou, Hong-Sun
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.10 no.3
    • /
    • pp.162-175
    • /
    • 2002
  • To investigate smoke movement with radiation in a room fires, a numerical and experi-mental analysis were performed. In this paper, results from a field model based on a self-developed SMEP (Smoke Movement Estimating Program) were compared with Stockier's ex-periment and the experiments on various sized pool fires in a room with door The SMEP using PISO algorithm solves conservation equations for mass, momentum, energy and species, together with those for the modified k- $\varepsilon$ turbulence model with buoyancy term. Also it solves the radiation equation using the S-N discrete ordinates method (DOM). The result of the cal-culated smoke temperature considering radiation effect has shown good agreement compared with the experimental data, although there are large discrepancy in the hot smoke layer be-tween the temperature predicted by the SMEP with only convection effect and obtained by the experimental result. This large discrepancy is caused from the radiation effect of $H_2O$ and $CO_2$ gas under smoke productions. Hence the radiation effect under smoke in fire is the point to be specially considered in order to produce more realistic result.