• Title/Summary/Keyword: Smoke extraction system

Search Result 27, Processing Time 0.026 seconds

A Study on Smoke Movement by Using Large Eddy Simulation I. Smoke Control Systems and Extraction Flowrate (대와류모사를 이용한 연기이동의 연구 I. 제연방식과 배기풍량)

  • 박외철
    • Journal of the Korean Society of Safety
    • /
    • v.18 no.2
    • /
    • pp.40-45
    • /
    • 2003
  • To evaluate the smoke control systems, the large eddy simulation turbulence model based Fire Dynamics Simulate was applied to a 2m $\times$ 2m $\times$ 2.4m room with an opening. The smoke removal rate was investigated for three different smoke control systems: ventilation, extraction and pressurization. When the opening was closed, the smoke removal rates of the smoke control systems were almost the same as expected. The pressurization system showed a lower smoke removal rate compared with the other two smoke control systems for the room with the opening, and hence the pressurization system might not be efficient for a place with large openings. It was shown that the lower extraction flowrate is, the longer time the ventilation system requires to remove smoke. From these results, the ventilation system is recommended for subway stations where several large openings exist.

A Numerical Study for the Operation of Partial Smoke Extraction System in Tunnel Fire (터널화재시 부분배연설비의 운영방안을 위한 수치해석적 연구)

  • Yoo, Yong-Ho;Lee, Eui-Ju;Shin, Hyun-Jun;Shin, Han-Chol
    • Fire Science and Engineering
    • /
    • v.20 no.2 s.62
    • /
    • pp.72-79
    • /
    • 2006
  • The objective of this study is to analyze the smoke extraction efficiency using by the partial extraction system with CFD simulation for case of tunnel fire. The Comparison of CFD results with the preceding scaled model test results, it is equal to the smoke extraction efficiency and smoke stratification in tunnel by the partial smoke extraction system (distributed damper). It shows that the smoke extraction efficiency is increased about 7% by the distributed damper which is opened near fire, compare with the distributed damper which is all opened. The case of the fire occurs on a traffic jam in a tunnel, it is proposed that the operating method of partial smoke extraction system for the escaping passengers.

Comparison of Two Different Smoke Extraction Schemes of Transversely Ventilated Tunnel Fire

  • Rie, Dong-Ho;Kim, Hyung-Taek;Yoo, Ji-Oh;Shin, Hyun-Jun;Yoon, Sung-Wook
    • International Journal of Safety
    • /
    • v.4 no.2
    • /
    • pp.30-35
    • /
    • 2005
  • In case of tunnel fire, one of the most effective facilities to save lives is the smoke control system. In this study, two different smoke extraction schemes of transversely ventilated tunnel were compared. One is the smoke extraction using the fixed exhaust ports on the false ceiling to achieve the uniform and distributed smoke extraction (uniform exhaust). The other is that using the remote controlled smoke extraction where only vents close to the fire is opened whereas the others are closed to enhance the limitation of the smoke spread (localized exhaust). A number of numerical simulations were performed to find out the optimal smoke extraction rate at each smoke extraction scheme to allow the tunnel users to escape to the safe area without endangering their lives by smoke.

Study of the Smoke Extraction Efficiency Improvement by the Partial Smoke Extraction System in Tunnel Fire (터널화재시 부분배연설비에 의한 배연효율 향상에 관한 연구)

  • Yoo, Yong-ho;Lee, Eui-ju;Shin, Hyun-jun;Shin, Han-cho|;Yoon, Young-hoon;Kim, Chang-whan
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.8 no.1
    • /
    • pp.53-63
    • /
    • 2006
  • The objective of this study is to analyze the smoke movement and the smoke extraction efficiency using by the partial extraction system for case of tunnel fire. Based on Froude modeling and isothermal model, the 1/20 scaled model tunnel (12m long) was constructed. In the case of the upper critical velocity in the main tunnel, the smoke extraction efficiency shows almost same between group damper and distributed damper. Finally, if the fire occurs on a traffic Jam in a tunnel, it is proposed that the open dampers in partial gallery extract smoke from the main tunnel without jet fan operation. Then, after the passengers have escaped the tunnel, the jet fans work on. On the other hand, If the traffic is uncongested in the tunnel, the jet fans (smoke control system) and partial extraction system (smoke exhaust system) are operated at once in tunnel fire.

  • PDF

A Study on Smoke Movement by Using Large Eddy Simulation II. Smoke Control Systems and Opening Size (대와류모사를 이용한 연기이동의 연구 II. 제연방식과 개구부의 크기)

  • 박외철
    • Journal of the Korean Society of Safety
    • /
    • v.18 no.3
    • /
    • pp.34-38
    • /
    • 2003
  • The large eddy simulation based Fire Dynamics Simulator was utilized to investigate the effects of the size of an opening on smoke removal performance for the three smoke control systems-ventilation purge, and extraction. Three different opening sizes, $r_A$=1, 2, and 3 were investigated while the flow rate remained 0.75 $m^3/s$ at the inlet or outlet depending on the systems. Increase of the opening size did not give a significant difference in the smoke removal rate for the three smoke control systems, though the increasing opening size slightly improved smoke removal. The extraction system was shown the best smoke control system, and the purge system yielded low performance compared to the other two systems for all the different opening sizes.

A Numerical Simulation of Smoke Control in Daegu Subway Stations II. Air Flowrate of Extraction System (대구 지하철역 제연의 문제점과 대책 II. 배기방식 제연설비의 풍량)

    • Fire Science and Engineering
    • /
    • v.17 no.4
    • /
    • pp.105-110
    • /
    • 2003
  • In Part II, the temperature and smoke particle distributions of the extraction system, which yielded the best smoke removal performance among the three smoke control systems in Part I, for extraction flowrates of 0.6∼2.4 ㎥/s and two fire sizes of 200 ㎾ and 2 ㎿ were presented. The same numerical method was utilized to the same computational domain and configurations as Part I. It was shown that the extraction flowrate affects the smoke control performance significantly, and that a similar trend in improving the smoke removal performance with the increasing extraction flowrate between the two fire sizes. An extraction flowrate of 2.4 ㎥/s or higher was required for the temperature in the escape route less than $^{\circ}C$ for the given situations.

A Numerical Study on Characteristics of Smoke Exhaust in Road Tunnel Fires for Different Ventilation System (터널 화재 시 환기 방식에 따른 배연 특성의 수치해석 연구)

  • Kim, Jong-Yoon;Yoo, Ji-Oh
    • Fire Science and Engineering
    • /
    • v.22 no.3
    • /
    • pp.201-207
    • /
    • 2008
  • In this study, three Dimensional CFD simulations were carried out to investigate the effective smoke extraction system in bi-directional road tunnel fires using FLUENT. Characteristics of transverse system with big size extraction port or with uniform extraction port, semi-transverse system and longitudinal system for smoke extraction system were analyzed. Air velocity, port size, and operating method were used with variable. Distributions of smoke spread, CO was analyzed. As a result, the transverse ventilation system with big size port was found to be more effective than the uniform ports for bi-directional road tunnel.

A study on the effect of air velocity through a damper on smoke extraction performance in case of fire in road tunnels (도로터널 화재 시 집중배기방식의 배기포트 통과풍속이 배연성능에 미치는 영향에 관한 연구)

  • Ryu, Ji-Oh;Na, Kwang-Hoon
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.22 no.4
    • /
    • pp.347-365
    • /
    • 2020
  • In order to resolve traffic problems in urban areas and to increase the area of green spaces, tunnels in downtown areas are being increased. Additionally, the application of large port smoke extraction ventilation systems is increasing as a countermeasure to smoke extraction ventilation for tunnels with high potential for traffic congestion. It is known that the smoke extraction performance of the large port smoke extraction system is influenced not only by the amount of the extraction flow rate, but also by various factors such as the shape of the extraction port (damper) and the extraction air velocity through a damper. Therefore, in this study, the design standards and installation status of each country were investigated. When the extraction air flow rate was the same, the smoke extraction performance according to the size of the damper was numerically simulated in terms of smoke propagation distance, compared and evaluated, and the following results were obtained. As the cross-sectional area of the smoke damper increases, the extraction flow rate is concentrated in the damper close to the extraction fan, and the smoke extraction rate of the damper in downstream decreases, thereby increasing the smoke propagation distance on the downstream side. In order to prevent such a phenomenon, it is necessary to reduce the cross-sectional area of the smoke damper and increase the velocity of passing air through the damper so that the pressure loss passing through the damper increases, thereby reducing the non-uniformity of smoke extraction flow rate in the extraction section. In this analysis, it was found that when the interval distance of the extraction damper was 50 m, the air velocity passing through damper was 4.4 m/s or more, and when the interval distance of the extraction dampers was 100 m, the air velocity passing through damper was greater than 4.84 m/s, it was found to be advantageous to ensure smoke extraction performance.

Reduced-Scale Experiments of the Partial Smoke Extraction System in Tunnel Fires (풀화재를 이용한 터널화재 부분배연 모델실험)

  • Lee, Eui-Ju;Yoo, Yong-Ho
    • Fire Science and Engineering
    • /
    • v.20 no.4 s.64
    • /
    • pp.58-64
    • /
    • 2006
  • Smoke extraction in tunnel fire is investigated experimently with thermal model. The object is a immersed tunnel, of which the partial extraction system exists between the tubes. The model tunnel is measured 12 m long, 0.5 m wide and 0.35 m high. The fire is simulated to pool fire and the size corresponds to full scale fire of 5 MW based on Froude modeling. The performance of partial extraction system is determined under two ventilations, natural and longitudinal ones. The results show that compared with longitudinal ventilation, the smoke extraction efficiency of natural ventilation is increased about 30% because of smoke stratification in tunnel. Also the efficiency is identical to the iso-thermal model. The results will be help for activation of the ventilation system in emergency such as in the event of tunnel fires.

A Numerical Study on the Smoke Control in Side-Platform Type Subway Station Fires (상대식 지하철 역사내 화재시 연기제어에 관한 수치해석적 연구)

  • Lee, Sung-Ryong;Ryou, Hong-Sun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.2
    • /
    • pp.81-86
    • /
    • 2008
  • In this study, numerical simulations were carried out to analyze the effect of the smoke extraction system and fire shutters in subway station fires using FDS 4.0. Subway station used in the experiment was 205 m long. Simulation results are validated by comparing with experimental results. Simulation results showed good agreement with experimental results within $20\;^{\circ}C$. 20 MW polystyrene was used as a fuel in the numerical prediction. Numerical predictions were performed in the side-platform type subway station in case of a train fire. Temperature and CO concentration were lowered by the operation of smoke extraction system.