• Title/Summary/Keyword: Single Line Diagram

Search Result 28, Processing Time 0.027 seconds

An Auto-drawing Algorithm for the Single Line Diagram of Distribution Systems (배전선로 회선별단선도 자동생성 알고리즘)

  • Son, Ju-Hwan;Lim, Seong-Il
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.5
    • /
    • pp.854-859
    • /
    • 2010
  • Distribution Automation System(DAS) is designed to improve operational efficiency by acquisition and control of remote data using its components such as central computation units, communication network and feeder remote terminal units. A conventional human machine interface of the DAS adopts a schematic diagram which is made by drawing power equipments on the geographic information system map. The single line diagram is more useful than the schematic diagram for the main tasks of distribution system operation such as protective relay coordination, service restoration and loss minimization. Since the configuration of the distribution line is changed according to the relocation of the open tie switches, the auto-drawing algorithm based on the connection between the sections and the switches is an essential technique. This paper proposes a new auto-drawing algorithm for a single line diagram of distribution systems based on tertiary tree and collision avoidance method. The feasibility of the proposed algorithm has been testified for various cases using practical distribution system with 12 feeders.

Service Oriented Architecture based Single Line Diagram Auto-drawing Technique in Distribution Automation Systems (서비스 지향적 방법론 기반의 배전선로 회선별단선도 생성 기법)

  • Lim, Seong-Il
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.7
    • /
    • pp.23-29
    • /
    • 2012
  • A single line diagram is a graphic user interface to represent electrical connectivity between power equipments in distribution automation systems. This paper proposes a new single line auto-drawing technique based on the service oriented architecture. Web service, CIM(Common Information Model) and SVG(Scalable Vector Graphics) are adopted to implement SOA concept. A web service demo system was established which is configured with the service provider, consumer and broker to verify the feasibility of this study.

Characteristic Analysis of Single Phase Line-start Permanent Magnet Synchronous Motor Considering Circuit Parameters (단상 직립 기동형 영구자석 동기기의 회로정수에 따른 특성 해석)

  • 강규홍;홍정표
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.52 no.6
    • /
    • pp.262-270
    • /
    • 2003
  • In this paper, the characteristics of single-phase line-start permanent magnet synchronous motor driven by constant voltage are analyzed on d-q axis vector diagram and compared with that of current controlled motor. The coupled method of symmetrical coordinates and d-q axis voltage equation are applied to the analysis method like the analysis of single-phase induction motor. From the result of the analysis, it is seen that motors driven by constant voltage source have effects on not only the amplitude of current and torque but also current and current phase angle, so overall characteristics such as power factor and load angle are affected by circuit parameters. For precise analysis and design of single-phase line-start synchronous motor, its characteristics should be analyzed on d-q axis vector plan in consideration of the variation of circuit parameters.

The Development of application for intelligent electrical system drawing generation program (Intelligent 전기계통 도면작성 Application 기술개발)

  • Cho, Sung-Don;Yoo, Gi-Hong
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2220-2221
    • /
    • 2008
  • 전기계통설계 도면인 Single Line Diagram(단선도), Schematic Diagram(전개접속도), Cable Block Diagram/Cable Schedule, Cable Termination/Connection Diagram(단말결선)의 도면 상호간 데이터 연계에 의한 자동, 통합형태의 Intelligent 전기계통 도면 작성 프로그램 개발에 대한 기본적인 방향에 대하여 소개하고자 한다.

  • PDF

An Improved Method for Fault Location based on Traveling Wave and Wavelet Transform in Overhead Transmission Lines

  • Kim, Sung-Duck
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.2
    • /
    • pp.51-60
    • /
    • 2012
  • An improved method for detecting fault distance in overhead transmission lines is described in this paper. Based on single-ended measurement, propagation theory of traveling waves together with the wavelet transform technique is used. In estimating fault location, a simple, but fundamental method using the time difference between the two consecutive peaks of transient signals is considered; however, a new method to enhance measurement sensitivity and its accuracy is sought. The algorithm is developed based on the lattice diagram for traveling waves. Representing both the ground mode and alpha mode of traveling waves, in a lattice diagram, several relationships to enhance recognition rate or estimation accuracy for fault location can be found. For various cases with fault types, fault locations, and fault inception angles, fault resistances are examined using the proposed algorithm on a typical transmission line configuration. As a result, it is shown that the proposed system can be used effectively to detect fault distance.

A Study on Description of IEC 61850 based Substation Topology for Implementing the Engineering Tool of Digital Substation (디지털변전소 엔지니어링 툴 구현을 위한 IEC 61850 국제규격 기반의 변전소 토폴로지 표현에 관한 연구)

  • Lee, Nam-Ho;An, Yong Ho;Jang, Byung-Tae
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.9
    • /
    • pp.23-32
    • /
    • 2015
  • In order to complete engineering works of the digital substation, Both Data transmission among a variety of IEDs and HMIs, and single line diagram of the substation might be done based on XML documents published in IEC 61850 international standards. This kind of XML based engineering process for the digital substation must be implemented not by manual written work but by the engineering tool using a computer. But most of the engineering tools do not support system based engineering works such as single line diagram of the substation but have only function to set IEDs as single device unit. Accordingly, this paper presents a new design method of the system based engineering description applicable to real IEC 61850 based substation through analyzing the current international standard and its sampled engineering file, and shows implementation of the engineering tool of the digital substation with the result of this study.

Misunderstanding and Understanding of the Phase Diagram for Water: Water Evaporation and Ice Sublimation in the Atmosphere (물의 상평형 그림에 대한 오해와 이해: 대기 중 물의 증발과 얼음의 승화)

  • Park, Jong-Yoon
    • Journal of the Korean Chemical Society
    • /
    • v.51 no.6
    • /
    • pp.577-584
    • /
    • 2007
  • The purpose of this study is to suggest how to use the phase diagram for water to explain the evaporation and sublimation in the atmospheric condition. In principle, the phase diagram for water represents a one component system so it cannot be applied to the water contact with the air. When the liquid or solid phase of water exists in the air, always water vapor also exists in the air. In this case, we cannot present this state as a single point on the phase diagram because the pressure of the liquid or solid is different from that of the vapor in the air. However, since the saturation vapor pressure of liquid or solid is altered by negligible amount due to the presence of air, the evaporation and sublimation in the atmospheric condition can be explained using the vapor pressure line and sublimation line on the phase diagram.

Spatio-temporal Load Analysis Model for Power Facilities using Meter Reading Data (검침데이터를 이용한 전력설비 시공간 부하분석모델)

  • Shin, Jin-Ho;Kim, Young-Il;Yi, Bong-Jae;Yang, Il-Kwon;Ryu, Keun-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.11
    • /
    • pp.1910-1915
    • /
    • 2008
  • The load analysis for the distribution system and facilities has relied on measurement equipment. Moreover, load monitoring incurs huge costs in terms of installation and maintenance. This paper presents a new model to analyze wherein facilities load under a feeder every 15 minutes using meter reading data that can be obtained from a power consumer every 15 minute or a month even without setting up any measuring equipment. After the data warehouse is constructed by interfacing the legacy system required for the load calculation, the relationship between the distribution system and the power consumer is established. Once the load pattern is forecasted by applying clustering and classification algorithm of temporal data mining techniques for the power customer who is not involved in Automatic Meter Reading(AMR), a single-line diagram per feeder is created, and power flow calculation is executed. The calculation result is analyzed using various temporal and spatial analysis methods such as Internet Geographic Information System(GIS), single-line diagram, and Online Analytical Processing (OLAP).

A Study on the Optimization of Power Supply Equipment for Plate Mill Plant in Steelworks (제철소 후판공장 전원공급설비의 용량 최적화에 관한 연구)

  • Ko, Hyun-Ok;Park, Ji-Ho;Kim, Dong-Wan
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.9
    • /
    • pp.1300-1305
    • /
    • 2014
  • In this paper, we suggest an optimization method which can save about 5[%] of the cost though the optimizing of configuration and capacity for the facility. To achieve this goal, we compared the design data of the power, motor and drive system with the actual operation data of the plate mill plant in K-Steelworks. Therefore we measured the actual loading data by facilities considering the operating conditions of the plate mill plant in K-Steelworks, after that analyzed these data. In addition, we review the optimal capacity for transformer, switchgear and drive, and also reconfigured the electrical room and power single line diagram through the validation of motor data by equipment and the confirmation of process data considering the load characteristics. Consequently, the optimization method of capacity for the facilities shall have effectiveness in building new plate mill plant to further reduce costs at future.

Failure Assessment Diagrams of Semi-Elliptical Surface Crack with Constraint Effect (구속상태를 고려한 반타원 표면균열의 파손평가선도)

  • Seo, Heon;Han, Tae-Su;Lee, Hyeong-Il
    • Transactions of the Korean Society of Mechanical Engineers A
    • /
    • v.23 no.11 s.170
    • /
    • pp.2022-2032
    • /
    • 1999
  • In recent years, the subject of remaining life assessment has drawn considerable attention in the power generation industry. In power generation systems a variety of structural components, such as steam pipes, turbine rotors, and superheater headers, typically operate at high temperatures and high pressures. Thus a life prediction methodology accounting for fracture and rupture is increasingly needed for these components. For accurate failure assessment, in addition to the single parameter such as K or J-integral used in traditional fracture mechanics, the second parameter like T-stress describing the constraint is needed. The most critical defects in such structures are generally found in the form of semi-elliptical surface cracks in the welded piping-joints. In this work, selecting the structures of surface-cracked plate and straight pipe, we first perform line-spring finite element modeling, and accompanying elastic-plastic finite element analyses. We then present a framework for including constraint effects (T-stress effects) in the R6 failure assessment diagram approach for fracture assessment.