• Title/Summary/Keyword: Sheath induced voltage

Search Result 27, Processing Time 0.023 seconds

Analysis of Sheath Induced Voltage in Transmission Power Cable Connected with CCPU (방식층 보호장치의 설치에 따른 지중송전케이블 시스 유기전압 해석)

  • Lee, Jun-Sung;Lee, Jong-Beom;Kim ,Young
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.1
    • /
    • pp.19-25
    • /
    • 2000
  • This paper describes the sheath induced voltage in underground transmission cable system which will be operated with cable cover protection unit(CCPU). Simulation was carried out to analyze the sheath induced voltage in the real cable system which was installed by 154㎸ CV cable in the case with and without CCPU. The sheath induced voltage will be also analyzed according to the change of grounding method, fault resistance and fault angle. Simulation was performed using EMTP and ATP Draw, the simulation results show whether the CCPU in necessary or not in underground transmission power cable system.

  • PDF

Analysis on the Effects of the Induced Noise Voltage with the Grounded or Non-grounded Cable Sheath in the Power Inducting Situation (전력 유도 발생 시 케이블 쉬스 접지 여부에 따른 유도 잡음 전압 영향 분석)

  • Lee, Sang-Mu;Choi, Mun-Hwan;Cho, Pyoung-Dong
    • 한국정보통신설비학회:학술대회논문집
    • /
    • 2007.08a
    • /
    • pp.285-288
    • /
    • 2007
  • This article presents the change characteristics of induced noise whether the sheath layer of the cable is grounded or not. As what affects the induced noise, there are power influence or longitudinal transverse voltages and its weighted filtered voltage. The sheath ground is basicaly predicted to have the effects of alleviation on the power influence. But practically the effects may not happen in the case of common cable's sheath layer. Rather there are cases that the ground of sheath affects so that the noise level could increase. So we need to scrutinize the effects of the sheath gorund in the measures for the protection against electromagnetic induction by powerline or traction line system. And the evaluation of using the designated shielding purpose cable is needed.

  • PDF

A Study on the Analysis of Induced Voltage of Sheath on 154kV Transmission Power Cable in Multi Fault Cases (다양한 고장조건에서 154kV 지중송전케이블 시스유기전압해석에 관한 연구)

  • Lee, Jun-Sung;Lee, Jong-Beom
    • Proceedings of the KIEE Conference
    • /
    • 1998.07c
    • /
    • pp.1179-1181
    • /
    • 1998
  • This paper describes the induced voltage of sheath on 154kV transmission power cable in multi fault states. Simulation was carried out to obtain the induced voltage of sheath according to change of, fault angle and grounding resistance using EMTP. Modeling of cable system is also established in EMTP to analyze. The simulation results can be useful reference to design cable system in power system.

  • PDF

Analysis of Induced Voltage on Sheath of Transmission Power Cable Connected with Surge Arrester (피뢰기 적용에 따른 지중송전케이블 시스 유기전압 해석)

  • Lee, Jun-Sung;Lee, Jong-Beom;Kim, Young
    • Proceedings of the KIEE Conference
    • /
    • 1999.07c
    • /
    • pp.1391-1393
    • /
    • 1999
  • This paper have analyzed sheath induced voltage in underground transmission cable system which will be operated with cable cover protection unit(CCPU). Simulation was carried out to analyze sheath induced voltage using on real cable system in the case with and without CCPU. Sheath induced voltage was also analyzed according to grounding method, fault resistance and fault angle. Simulation was performed using EMTP and ATP Draw, the simulation results represent whether the arrester is necessary or not in cable system.

  • PDF

Analysis of Sheath Induced Voltage and CCPU Operating Characteristic in Underground Transmission Cable (지중송전계통에서 시스유기전압 및 CCPU 동작 특성 해석)

  • Jin, Hye-Young;Lee, Jong-Beom;Kim, Young;Cho, Han-Koo
    • Proceedings of the KIEE Conference
    • /
    • 2001.07a
    • /
    • pp.494-496
    • /
    • 2001
  • This paper describes sheath induced voltage and operating characteristic of cable cover protection unit(CCPU) in underground transmission cable. Real cable system operating by 154kV XLPE cable was modelled for simulation. Sheath induced voltage and operating characteristic of CCPU were analyzed. In particular, sheath induced voltage was analyzed in case of individual grounding and common grounding, respectively, and operating characteristics of CCPU were compared each other.

  • PDF

Effect of the Sheath Layer Ground of Telecommunication Cable to Induced Voltage Measurement (통신 케이블 쉬스 층 접지가 전력선 전자유도 전압 측정에 미치는 영향)

  • Lee, Sangmu
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.1
    • /
    • pp.713-719
    • /
    • 2015
  • The change in induced voltage according to the relationship of ground connection between the aluminum sheath layer and a conductor pair in a general telecommunication cable is analyzed. When a measurement is practiced under the condition of separated sheath grounds with an averaged ground resistance of $42.6{\Omega}$, the induced voltage decreases 10 % to the induced voltage without sheath grounds. The induced voltage decreases approximately 50 % in the case of a one-sided common ground and decreases by more than 90 % in the case of a both-sided common ground. This experimental result is similar to the values calculated using the methods of the ITU Directives. In addition, according to a comparison analysis utilizing this ITU method, the measurement error range will be below 10 % in the state of ground resistance of central office less than $10{\Omega}$ and for the terminal side with $100{\Omega}$ less or more.

EMTP-analysis of Transposition Effects on Underground Transmission Cables (EMTP를 이용한 지중케이블의 도체 연가 영향 분석)

  • Ha, C.W.;Han, S.H.;Heo, H.D.;Lee, I.H.
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.93-94
    • /
    • 2006
  • The sheath of a single-conductor cable for ac service acts as a secondary of a transformer, the current in the conductor induces a voltage in the sheath. When the sheaths of single-conductor cables are bonded to each other, as is common practice for multi-conductor cables, the induced voltage causes current to flow in the completed circuit. This current causes losses in the sheath. Various methods of bonding may be used for the purpose of minimizing sheath losses. In korea, sheath cross bonding system was employed for the prevention of sheath losses, the sheaths wire subjected to at voltages, and the bonding was designed to keep the magnitude of the induced voltages within small limits so as to prevent the possibility of sheath corrosion. But, sheath cross bonding system without transposition of cable can not achieve an exact balance of induced sheath voltages unless the cables are lain in trefoil. This paper describes a transposition system with sheath cross bonding using EMTP(Electromagnetic Transient Program). The transposition system with cross bonding can be extended to longer cable circuits for laid in flat as wall as trefoil by the methods described in this paper.

  • PDF

Analysis of Switching Overvoltage in 345kV Underground and Combined Transmission Systems (345kV 지중 및 혼합 송전계통에서의 개폐 과전압 해석)

  • 정채균;이종범;강지원
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.12
    • /
    • pp.713-721
    • /
    • 2003
  • This paper analyzes the switching overvoltage occurred on 345kV underground power cable system as well as combined transmission system using EMTP. Cable length and closing time, preinsertion resistance have effect on switching overvoltage. Therefore, this paper analyzes the switching overvoltage occurred on conductor and sheath with change of those parameters. Specially, the cross bonding position becomes discontinuity point because of the difference between surge impedance of metal sheath and that of lead cable. Thus, the transmission and the reflection of traveling wave complexly occur at this connection point. According to these influences, voltage between sheath and earth as well as voltage between joint boxes rise. Time to crest point of switching overvoltage is longer than lightning overvoltage. Even though the voltage induced by switching surge is smaller than lightning surge, that voltage may have serious effect on the metal sheath. Therefore, this paper also analyses the reduction effect of switching overvoltage when the preinsertion resistance of circuit breaker is considered.

Effectiveness Evaluation and Operation Scheme on Cable Transposition in Underground Transmission Systems with Ungrounded Joint Box (접속함 비접지 지중송전계통에서 도체연가방식 채용의 효용성 평가 및 운용방안 수립)

  • Kim, June;Lee, Jong-Beom
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.64 no.2
    • /
    • pp.240-246
    • /
    • 2015
  • Length of most underground power cable in home is not so long. Therefore it is operated without transposition due to low unbalanced ratio. However, if cable length is long, line constant of each cable will be different. Different line constant can induce unbalanced voltage and current of sheath. Also it can induce several induced interference. This paper describes the effectiveness of transposition through sheath component analysis on transposition and untransposition of cable conductor. Especially sheath current and induced voltage are analyzed and compared in case of transposition and untransposition. EMTP is used for modeling and analysis.

Analysis of Sheath Induction Voltage for 154kV OF Underground Cable (154kV OF 지중케이블의 씨스 유도전압 해석)

  • Lee, H.G.;Kim, D.K.;Bae, J.H.;Ha, T.H.;Choi, S.B.;Jeong, S.H.
    • Proceedings of the KIEE Conference
    • /
    • 2000.11a
    • /
    • pp.156-158
    • /
    • 2000
  • As we are industrialized lately, power capacity is increased in the city urban areas. So the application of underground transmission line is largely expended. In this paper, we analysis the induction voltage on the sheath of 1,200[$mm^2$] OF underground cable being used 154kV underground transmission line. If the current on the cable conductor is 300[A], circulation current is induced the maximum 100[A] on the cable sheath.

  • PDF