EMTP-analysis of Transposition Effects on Underground Transmission Cables

EMTP를 이용한 지중케이블의 도체 연가 영향 분석

  • Published : 2006.07.12

Abstract

The sheath of a single-conductor cable for ac service acts as a secondary of a transformer, the current in the conductor induces a voltage in the sheath. When the sheaths of single-conductor cables are bonded to each other, as is common practice for multi-conductor cables, the induced voltage causes current to flow in the completed circuit. This current causes losses in the sheath. Various methods of bonding may be used for the purpose of minimizing sheath losses. In korea, sheath cross bonding system was employed for the prevention of sheath losses, the sheaths wire subjected to at voltages, and the bonding was designed to keep the magnitude of the induced voltages within small limits so as to prevent the possibility of sheath corrosion. But, sheath cross bonding system without transposition of cable can not achieve an exact balance of induced sheath voltages unless the cables are lain in trefoil. This paper describes a transposition system with sheath cross bonding using EMTP(Electromagnetic Transient Program). The transposition system with cross bonding can be extended to longer cable circuits for laid in flat as wall as trefoil by the methods described in this paper.

Keywords