• Title/Summary/Keyword: Sheath current loss

Search Result 13, Processing Time 0.021 seconds

Analysis of Eddy Current Loss Considering Interaction Effect in Metal Sheath of 154 kV Three Phase Power Cable (154 kV 3상 전력 케이블의 상호작용에 따른 금속 Sheath에서 발생하는 와전류 손실 분석)

  • Im, Sang Hyeon;Kim, Ki Byung;Park, Gwan Soo
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.6 no.4
    • /
    • pp.389-392
    • /
    • 2020
  • In order to accurately predict the losses in the power cable, analysis of the eddy current losses in the metal sheath is required. The copper loss is easily calculated by the resistance and current of the conductor, but it is difficult to measure and predict the eddy current generated from the metal sheath. For this purpose, the previous study analyzed the eddy current loss in single phase cable, but there is a limit to apply it because three phase cables are used in real environment. Therefore, in this paper, the eddy current loss occurring in the metal sheath of three phase cable according to the cause was analyzed theoretically. In addition, the eddy current loss occurring in the triangular and horizontal array were predicted through electromagnetic numerical analysis.

Analysis of Eddy Current Distribution and Loss in Metal Sheath of 154 kV Single Power Cable (154 kV 단상 전력 케이블의 금속 Sheath에서 발생하는 와전류 분포 및 손실 분석)

  • Im, Sang Hyeon;Kim, Kyoung Youn;Kim, Ki Byung;Park, Gwansoo
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.6 no.2
    • /
    • pp.115-118
    • /
    • 2020
  • As interest in the reduction of energy loss has increased in recent years, analysis of losses in power cables is becoming more important. The overall loss in the transmission system can be measured, but there are many difficulties in researching the loss in each internal structure. There are various factors in the type of loss, and the loss of external factors by previous research has been studied. However, there is little research on the cable internal loss. Since the metal sheath inside the cable is made of aluminum having a high conductivity, an eddy current is generated due to the current flowing in the conductor, thereby causing an eddy current loss inevitably. In this paper, the eddy current loss in metal sheath of 154 kV Cable was researched through FEM (Finite Element Method) electromagnetic analysis.

A study or Metallic sheath for Extra-high voltage XLPE cable (초고압 XLPE 케이블 금속 차폐층 고찰)

  • Choi, C.S.;Lee, K.J.;Chung, M.Y.;Kwon, B.I.
    • Proceedings of the KIEE Conference
    • /
    • 1994.07b
    • /
    • pp.1652-1654
    • /
    • 1994
  • The Extra-high voltage XLPE cable is characterized by low transmission loss, large capacity, and high reliability. Conventionally, for XLPE cables of l54kV and above, aluminium sheath was used to be moisture barrier (thus preventing water tree deterioration of the insulation) and to protect cable core from physical stresses. However, as transmission capacity of the cable increases, so does the cable diameter and the corresponding aluminium sheath outer diameter and thickness. As a result, eddy-current loss in the sheath is increased, limiting the maximum current capacity of the cable itself. As an alternative to aluminium sheath, we have adopted stainless steel sheath with non-magnetic properties and a large resistivity, The new XLPE cable with stainless-steel sheath (CSZV cable) has drastically reduced eddy-current loss in the sheath.

  • PDF

A Study on the Characteristic and Rising Cause of Sheath Circulating Current by Analysis and Measurement (해석 및 측정을 통한 시스순환전류 특성 및 상승원인 검토)

  • Gang, Ji-Won;Yang, Hae-Won
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.10
    • /
    • pp.525-533
    • /
    • 2002
  • It is common to install multiple lines in the same route. Recently, excessive sheath circulating current was partially measured in underground cable systems of KEPCO. Especially, the installation type, unbalance section length between joint boxes and zero sequence current by distribution cable have an effect on the rising of sheath circulating current in the underground transmission system. If excessive current flows in sheath, sheath loss which is reduced the transmission capacity is produced. This paper describes the relation analysis of sheath circulating current and burying types. And also, a detailed analysis on rising cause and characteristic of sheath circulating current by considering various unbalanced conditions presents using analysis and measurement regarding cable systems which have the problem of excessive sheath circulation current.

A Study on the Reduction Methods of Sheath Circulating Current using the Reduction Equipment in Underground Transmission Systems (지중송전계통에서 저감장치를 이용한 시스 순환전류 저감방안에 관한 연구)

  • Gang, Ji-Won;Yang, Hae-Won
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.9
    • /
    • pp.474-481
    • /
    • 2002
  • Sheath circulating current is increased in the change of sheath mutual impedance which is caused by unbalanced cable system, and different section length between joint boxes. If excessive current flows in sheath, sheath loss which is reduced the transmission capacity is produced. Recently, excessive sheath circulating current was partially measured in underground cable systems of KEPCO. Accordingly, actual schemes to reduce excessive sheath circulating current are urgently required for installed cable system as well as newly-installing cable systems. This paper describes the relation analysis of sheath circulating current and burying types. And also, various schemes to reduce excessive circulating current using EMTP/ATPDraw and applicable schemes are proposed through a detailed analysis regarding cable systems by considering various electrical and environmental factors. It is evaluated that the proposed reduction schemes can be effectively applied to reduce the excessive sheath circulating current with the minimized electrical problems. And reduction effect is Proved with sheath circulating current reduction equipment.

Sheath Circulating Current Analysis of a Crossbonded Power Cable Systems

  • Jung, Chae-Kyun;Lee, Jong-Beom;Kang, Ji-Won
    • Journal of Electrical Engineering and Technology
    • /
    • v.2 no.3
    • /
    • pp.320-328
    • /
    • 2007
  • The sheath in underground power cables serves as a layer to prevent moisture ingress into the insulation layer and provide a path for earth return current. Nowadays, owing to the maturity of manufacturing technologies, there are normally no problems for the quality of the sheath itself. However, after the cable is laid in the cable tunnel and is operating as part of the transmission network, due to network construction and some unexpected factors, some problems may be caused to the sheath. One of them is the high sheath circulating current. In a power cable system, the uniform configuration of the cables between sections is sometimes difficult to achieve because of the geometrical limitation. This will cause the increase of sheath circulating current, which results in the increase of sheath loss and the decrease of permissible current. This paper will study the various characteristics and effects of sheath circulating current, and then will prove why the sheath current rises on the underground power cable system. A newly designed device known as the Power Cable Current Analyser, as well as ATP simulation and calculation equation are used for this analysis.

A Study on the Reduction of Sheath Circulating Current in Underground Transmission Systems (지중송전계통의 시스순환전류 저감에 관한 연구)

  • Jung, C.K.;Hong, D.S.;Lee, J.B.;Kang, J.W.;Yu, C.H.;Kang, W.T.
    • Proceedings of the KIEE Conference
    • /
    • 2001.11b
    • /
    • pp.29-33
    • /
    • 2001
  • Sheath circulating current results from the change of sheath mutual impedance which is caused by unbalanced cable system, and different section length between joint boxes. If circulating over current flows in sheath, it produces much sheath loss which reduces the transmission capacity. And also such large sheath current influences severely on the operator. Recently, large sheath circulating current was partially measured in underground cable system of KEPCO. Accordingly, actual schemes to reduce sheath circulating over current is urgently required for installed cable system as well as newly-constructing cable system. This paper describes the analysis of sheath circulating current and various schemes to reduce the large circulating current in case of operating cable system using EMTP/ATPDraw. And also, possible schemes are proposed through a detailed analysis regarding cable systems by considering various electrical and environmental factors. It is evaluated that the proposed reduction schemes can be effectively applied to reduce the large sheath circulating over current with the minimized electrical problems.

  • PDF

A Study on the Protection Methods of Sheath Circulating Current Reduction Device in Transient State (과도상태에서의 시스순환전류 저감장치 보호방안에 관한 연구)

  • Kang, Ji-Won;Jung, Chae-Kyun;Lee, Jong-Beom;Lee, Dong-Il;Jung, Gil-Jo
    • Proceedings of the KIEE Conference
    • /
    • 2002.11b
    • /
    • pp.53-58
    • /
    • 2002
  • Sheath circulating current is increased as the change of sheath mutual impedance which is caused by imbalance of cable system, and different section length between joint box. If excessive current flows in sheath. sheath loss will be increased and then transmission capacity of underground transmission system is reduced. Accordingly, This paper proposed sheath current reduction device using resistor and reactor and proved the reduction effect of that device using EMTP/ATP. And also in this paper, when transients are occurred at the underground system with reduction device by ground fault and lightning surge. we analyzes transient effect of system variously. From this result. authors establish the protection methods of sheath circulating current reduction device.

  • PDF

Mechanical properties at Bi-2223 HTS tapes with various sheath materials (기지금속을 달리한 Bi-2223 초전도 선에서의 기계적 특성 변화)

  • Ha, Dong-Woo;Lee, Dong-Hoon;Yang, Joo-Sang;Kim, Sang-Chul;Hwang, Sun-Yuk;Ha, Hong-Soo;Oh, Sang-Soo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07a
    • /
    • pp.551-554
    • /
    • 2004
  • Bi-2223 HTS tapes are used widely for application of superconducting power systems. However there are need the properties of high strength and low AC loss. Two kinds of Bi-2223 HTS tapes with different Ag sheath were used to know the effect of sheath alloying for the strength and the resistivity. The workability and reaction degree of superconducting phase at Bi-2223 HTS tapes were investigated. We designed conventional type-Ag/alloy and double sheathed mono filament type-Ag/alloy/alloy in order to increase the strength and resistivity of matrix in Bi-2223 HTS tapes. The effect of axial strain and thermal cycling on the critical current was investigated for the Bi-2223 HTS tapes. Because the workability of double sheath Bi-2223 HTS tape was lower than one sheath Bi-2223 HTS tape, it was need additional softening treatment. Bi-2223 formation reaction was decreased by Ag alloy matrix during sintering process. Two kinds of Bi-2223/Ag tapes with different Ag sheath were used to know the effect of sheath alloying for the tensile strain. Critical current is drastically decreased for Ag/alloy and Ag/alloy/alloy sheathed tapes at tensile strain above 0.24 % and 0.34 %, respectively. This result showed that mechanical strength was increased over than 40 % by introduce double sheath at mono filament stage.

  • PDF

A Study on unperfected circuiting current of undergrounded cable (지중송전케이블의 불완전 순환전류에 관한 연구)

  • Lee, Kwan-Woo;Lee, Yong-Sung;Kim, Bo-Kyeng;Park, Bok-Ki;Park, Dae-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.05b
    • /
    • pp.3-6
    • /
    • 2004
  • In this paper, we studied on permissible current of unperfected earthing for cross-bond system. The factors of unperfected earth were jacket damage, cross-bonding mistake, arrestor damage, effect of other circuit but we only studied permissible current of arrestor or jacket damage. In the result, we earned that permissible current of normal 154[[kV]] CV $1C{\times}400SQMM$ cable is 760[A] but current of unperfected earthing cable is 76[A], unperfected earthing confirmed that accident of underground cable could occur. So, we could confirmed that Earthing resistance of unperfected earthing need to limit.

  • PDF